| Date |
Text |
| 2005-11-10 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 11 |
| | FBC-2001 CHAPTER 1 |
| | |
| | |
| | 1. TABLE 403.1 A DRINKING FOUNTAIN IS |
| | REQUIRED. |
| | 2. SHTS LA-POOL-3 & LA-POOL-4 SEPARATE |
| | POOL PLANS & PERMIT ARE REQUIRED FOR |
| | EACH POOL. PLANS SHALL BE ROUTED TO THE |
| | PALM BEACH COUNTY HEALTH DEPT FOR REVIEW |
| | AND SHALL BE STAMPED PRIOR TO SUBMITTING |
| | TO CITY WPB FOR REVIEW. (MIN. 2 SETS OF |
| | PLANS). |
| | 3. ALL PLANS DESIGNED BY A PROFESSIONAL |
| | ARCHITECT OR ENGINEER, THEN ALL SHEETS |
| | SHALL BE SIGNED, SEALED, & DATED AS |
| | REQUIRED BY FLORIDA STATUTES. SECTION |
| | 106.1. |
| | 4. SHT CH A2.1.1 KITCHEN SINK SHALL BE |
| | ACCESSIBLE. SUBMIT A DETAIL SHOWING |
| | COMPLIANCE WITH SECTION 11-4.24 AND ALL |
| | SUBSECTIONS. CLEAR FLOOR SPACE FOR SINK |
| | SHALL BE FORWARD APPROACH. |
| | 5. SHT P3.1 WATER RISER DIAGRAM, WATER |
| | HAMMER ARRESTORS SHALL BE LOCATED NEAR |
| | THE FIXTURES IN AN "EFFECTIVE RANGE" NOT |
| | IN THE CEILING AS SHOWN. PDI-WH 201 AND |
| | MANUF. INSTALLATION INSTRUCTIONS. (SEE |
| | NOTE 13 SHT P0.1). |
| | 6. SHT P3.1 THE FOLLOWING INFORMATION IS |
| | REQUIRED FOR GAS PERMIT: |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | C. TYPE OF GAS, (LP OR NATURAL) |
| | D. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | E. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | F. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 506. |
| | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2 |
| | H. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | I. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND |
| | APPURTENANCES PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |