| 2005-10-04 00:00:00 | DENIED:2004 FBC - CLUBHOUSE | | | 1.PLAN SHEET M0.1 MECHANICAL NOTE 1 | | | REFERENCES ASHRAE STANDARDS THAT ARE NOT | | | CURRENT WITH WHAT IS ACCECPTED UNDER THE | | | 2004 CODE.SHOULD READ ASRAE 15-01, | | | 34-01, 62-01 NFPA AS FOLLOWS; 90A-02, | | | 90B-02, 91-99, 96-01.MECHANICAL NOTES | | | ALSO REFERENCE THE 2001 FBC. | | | | | | 2.PLAN SHEET M2.1 DETAIL A-A, | | | INDICATES AHU-1 & 2 IN A 'MECHANICAL | | | ROOM' WILL SERVE AS A PLENUM.PER 2001 | | | FBC(M)602.2.1, NO COMBUSTIBLES ALLOWED. | | | | | | 3.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | IS REQUIRED PER 2001 FBC(M)606.2.2. | | | | | | 4.FRESH AIR INTAKE IS LOCATED ABOVE | | | THE DOOR WITH THE CONDENSING UNITS | | | LOCATED BELOW.PLEASE NOTE, HEAT FROM | | | CONDENSING UNIT EXHAUST SHALL NOT BE | | | RECIRCULATED OR DRAWN IN BY THE FRESH | | | AIR INTAKE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|