2005-10-04 00:00:00DENIED:2004 FBC - CLUBHOUSE
 1.PLAN SHEET M0.1 MECHANICAL NOTE 1
 REFERENCES ASHRAE STANDARDS THAT ARE NOT
 CURRENT WITH WHAT IS ACCECPTED UNDER THE
 2004 CODE.SHOULD READ ASRAE 15-01,
 34-01, 62-01 NFPA AS FOLLOWS; 90A-02,
 90B-02, 91-99, 96-01.MECHANICAL NOTES
 ALSO REFERENCE THE 2001 FBC.
  
 2.PLAN SHEET M2.1 DETAIL A-A,
 INDICATES AHU-1 & 2 IN A 'MECHANICAL
 ROOM' WILL SERVE AS A PLENUM.PER 2001
 FBC(M)602.2.1, NO COMBUSTIBLES ALLOWED.
  
 3.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 IS REQUIRED PER 2001 FBC(M)606.2.2.
  
 4.FRESH AIR INTAKE IS LOCATED ABOVE
 THE DOOR WITH THE CONDENSING UNITS
 LOCATED BELOW.PLEASE NOTE, HEAT FROM
 CONDENSING UNIT EXHAUST SHALL NOT BE
 RECIRCULATED OR DRAWN IN BY THE FRESH
 AIR INTAKE.
  