2005-09-11 00:00:00IN ELECTRIC FOR REVIEW.
 REVIEWS IN PROGRESS .
 ********* UNSAT ************
  
 SAIL CLUB
 CLUBHOUSE BUILDING.
  
 1)NOTE:PLEASE SEE EM/ EXT LTS ARE
 SHOWN CIRCUITED TO THE LOCAL BRANCH
 CIRCUIT FOR LIGHITNG IN THAT AREA,
 HOWEVER EM/EXT LTS ARE SHOWN ON A
 SEPARATE CIRCUIT ON PANEL SCHEDULE.
 700.12E.
  
 2)NOTE: PLEASE SEE PLANS REFERENCE THE
 1999 NEC. PLEASE SEE AS OF JULY 7TH,2003
 THE STATE ADOPTED THE 2002 NEC.
 PLEASE SEE COVER SHEETS FOR PROJECT.
  
  
 3)NOTE: PLEASE SEE WATER HEATER MAY NOT
 BE LOCATE DIN "STORAGE" AREA/CLOSET.
 PLEASE SEE THIS LOCATION WILL BE PRONE
 TO STORAGE OF COMBUSTIBLES AND CREATE A
 FIRE HAZARD.
 PLEASE SEE 422.17 AND ANY COMMENTS FROM
 FIRE PLAN REVIEW.
  
 4)NOTE: PLEASE SEE 210.8B3 IN KITCHENS
 IN OTHER THAN DWELLING UNITS, WHICH
 REQUIRES ALL 15/20A 125V RECEPTS TO BE
 GFI PROTECTED WHEATHER OR NOT SERVICE
 KITCHEN AREA COUNTERSPACES.
  
 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 IT IS NOTED THE AIC RATING IS INDICATED
 FOR CH PANEL, HOWEVER PLEASE INDICATE
 FOR MAIN AS SHOWN ON RISER.
  
 6)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. IF LOADS ON PANEL
 SCHEDULE/LOADS CALCS ARE ALREADY FIG AT
 125%, PLEASE NOTE:
 215.3,230.42 ETC.
  
 7)NOTE: PLEASE ALSO SEE SERVICE IS SHOWN
 AS SINGLE PHASE, HOWEVER PANEL SCHEDULE
 INDICATES "A" AND "C" PHASE?
 A& B.
  
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ****************************************
 PLEASE COMPLETELY REMOVE ALL OLD/ VOIDED
 SHEETS FROM SETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 ONE COPY OF ALL OLD/VOIDED SHEETS SHOULD
 BE ATTACHED TO EACH OTHER TO COMPOSE OF
 ONE SET OF VOIDED SHEETS ONLY AND WILL
 BE SUBMITTED ALONG WITH NEW SETS FOR
 REFERENCE.
 **************************************
  
 PLEASE SEE BLDG REVIEW COMMENTS WITH
 RESPECT TO PRODUCT NOA'S ATTACHED TO
 PLANS.
 PLEASE ALSO SEE COMMENTS WITH REPECT TO
 PRODUCT APPROVALS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  