| 2005-09-11 00:00:00 | IN ELECTRIC FOR REVIEW. |
| | REVIEWS IN PROGRESS . |
| | ********* UNSAT ************ |
| | |
| | SAIL CLUB |
| | CLUBHOUSE BUILDING. |
| | |
| | 1)NOTE:PLEASE SEE EM/ EXT LTS ARE |
| | SHOWN CIRCUITED TO THE LOCAL BRANCH |
| | CIRCUIT FOR LIGHITNG IN THAT AREA, |
| | HOWEVER EM/EXT LTS ARE SHOWN ON A |
| | SEPARATE CIRCUIT ON PANEL SCHEDULE. |
| | 700.12E. |
| | |
| | 2)NOTE: PLEASE SEE PLANS REFERENCE THE |
| | 1999 NEC. PLEASE SEE AS OF JULY 7TH,2003 |
| | THE STATE ADOPTED THE 2002 NEC. |
| | PLEASE SEE COVER SHEETS FOR PROJECT. |
| | |
| | |
| | 3)NOTE: PLEASE SEE WATER HEATER MAY NOT |
| | BE LOCATE DIN "STORAGE" AREA/CLOSET. |
| | PLEASE SEE THIS LOCATION WILL BE PRONE |
| | TO STORAGE OF COMBUSTIBLES AND CREATE A |
| | FIRE HAZARD. |
| | PLEASE SEE 422.17 AND ANY COMMENTS FROM |
| | FIRE PLAN REVIEW. |
| | |
| | 4)NOTE: PLEASE SEE 210.8B3 IN KITCHENS |
| | IN OTHER THAN DWELLING UNITS, WHICH |
| | REQUIRES ALL 15/20A 125V RECEPTS TO BE |
| | GFI PROTECTED WHEATHER OR NOT SERVICE |
| | KITCHEN AREA COUNTERSPACES. |
| | |
| | 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | IT IS NOTED THE AIC RATING IS INDICATED |
| | FOR CH PANEL, HOWEVER PLEASE INDICATE |
| | FOR MAIN AS SHOWN ON RISER. |
| | |
| | 6)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS |
| | AT 125%. IF LOADS ON PANEL |
| | SCHEDULE/LOADS CALCS ARE ALREADY FIG AT |
| | 125%, PLEASE NOTE: |
| | 215.3,230.42 ETC. |
| | |
| | 7)NOTE: PLEASE ALSO SEE SERVICE IS SHOWN |
| | AS SINGLE PHASE, HOWEVER PANEL SCHEDULE |
| | INDICATES "A" AND "C" PHASE? |
| | A& B. |
| | |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | **************************************** |
| | PLEASE COMPLETELY REMOVE ALL OLD/ VOIDED |
| | SHEETS FROM SETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | ONE COPY OF ALL OLD/VOIDED SHEETS SHOULD |
| | BE ATTACHED TO EACH OTHER TO COMPOSE OF |
| | ONE SET OF VOIDED SHEETS ONLY AND WILL |
| | BE SUBMITTED ALONG WITH NEW SETS FOR |
| | REFERENCE. |
| | ************************************** |
| | |
| | PLEASE SEE BLDG REVIEW COMMENTS WITH |
| | RESPECT TO PRODUCT NOA'S ATTACHED TO |
| | PLANS. |
| | PLEASE ALSO SEE COMMENTS WITH REPECT TO |
| | PRODUCT APPROVALS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |