Plan Review Notes
Plan Review Notes For Permit 05080677
Permit Number 05080677
Review Stop B
Sequence Number 1
Notes
Date Text
2005-11-17 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05080677
 ADD: 719 EXECUTIVE CENTER DR
 (CLUBHOUSE)
 CONT: THE WEITZ CO.
 TEL: (561)686-5511
 CELL:(954)675-4302
  
 ARCHITECT: ACI ARCHITECRTURALGROUP
 PAUL M. TWITTY
 TEL:(561)832-5599
 STRUC ENGINEER: ONM&J
 PHILLIP RIZZO
 TEL:(561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE
 ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) 105.8* PROVIDE NOC RECORDED WITH THE
 CLERK OF COURT BEFORE A PERMIT CAN BE
 ISSUED.
  
 3)109.3.7*THIS PARTICUAL TYPE OF
 BUILDING "WILL NOT" REQUIRE A SPECIAL
 INSPECTOR, ALTHOUGH THERE WILL BE A
 THRESHOLD INSPECTOR FOR THE MID RISE AND
 HIGH RISE BUILDINGS.WILL THIS INSPECTOR
 ALSO BE INSPECTING THIS BUILDING? IF SO
 THREE (3) SET OF ALL DOCUMENTS WILL NEED
 TO BE SUBMITTED AS IF FOR ATHRESHOLD
 BUILDING.WILL THIS INSPECTOR BE THE SAME
 PERSON AS THE THRESHOLD INSPECTOR? OR
 WILL THERE BE TWO INDIVIDUALS?
 FORMS WILL NEED TO BE FILLED OUT FOR THE
 SPECIAL INSPECTOR, CONTACT HAROLD
 PISKURA, INSPECTION SERVICES MANAGER @
 (561)805-6711 TO SEET UP AN APPOINTMENT.
  
 4) 106.3.3* PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 SHALL BE REVIEWED AND APPROVED IN
 WRITTING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR " JURISDICTIONAL
 APPROVAL", (LOCAL PRODUCT APPROVAL).
  
 5) SITE PLAN NEEDS TO BE SUBMITTED TO
 ADDRESSING PERSONEL JOHN HIGGINS FOR
 ADDRESSING AS WELL AS NEW PLAT MAP FOR
 THE COMBINATION OF LOTS. JOHN HIGGINS
 CONTACT NUMBER IS (561)822-1239.
  
 6A) THERE IS A DISCREPANCY IN THE PLANS
 SINCE THE BOUNDRY SURVEY FOR PARCEL# 7,
 ONLY INDICATES 2 LOTS PARCEL 1&2.NOTE:
 FOR TOWNHOUSES EACH UNIT WILL REQUIRE
 INDIVIDUAL PROPERTY CONTROL NUMBERS
 WITH ASSOCIATED PROPERTY LINE.
 6B) THE SURVEY DOES SHOW 2 SEPERATE LOTS
 WHICH APPEAR TO CUT THROUGH BULDING "B"
 AND BUILDING "C". A UNITY OF TITLE SHALL
 BE REQUIRED, TABLE 601 AND 602.
  
  
 7) ENERGY COMPLIANCE FORMS:
 7A) UPDATE FORM TO FORM 400A-04
  
 8) GEOTECHNICAL REPORT THAT WORK WAS
 PREFORMED BY ARDAMAN NEEDS TO BE AN
 ORIGINAL WITH SIGNATURE AND RAISED SEAL.
 PLANS, SPECIFICATIONS,REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 9A) SHEET A3.2.1 WALL SECTIONS DO NOT
 INDICATE WHAT TYPE OF TERMITE TREATMENT
 FOR SOILS WILL BE USED, SEE 1816.1.
 9B) THIS SAME SHEET INDICATES THE USE OF
 A VAPOR BARRIER, MUST BE A MINIMUM OF 6
 MIL TO BE USED WITH CHEMICALLY TREATED
 TERMITE TREATMENT FOR SOILS BENEATH
 SLAB.1806.1.4.
 9C) 1816.1.6 IF SOIL TREATMENT IS USED
 FOR SUBTERRANEAN TERMITE PREVENTION,
 CHEMICAL SOIL TREATMENT SHALL BE APPLIED
 UNDER ALL EXTERIOR CONCRETE OR GRADE
 WITHIN 1 FT OF THE PRIMARY STRUCTURE
 SIDEWALLS.
  
 10) SHEET A6.1.1:
 10A) THE WALL SECTION# 8 DOESN'T
 INDICATE COMPLIANCE WITH ATTIC
 VENTILATION REQUIREMENTS FOUND IN
 1203.2. PLEASE INDICATE COMPLIANCE
 WITH BOTH THE EAVE REQUIREMENTS AS
 WELL AS 1/150 OF THE AREA OF THE
 SPACE TO BE VENTILATED AND 50% OF
 THE REQUIRED VENTILATION BE IN THE
 UPPER PORTION OF THE SPACE TO BE
 VENTILATED.
 10B) THE DETAIL#8 DOESN'T MATCH SHEET
 A3.2.1VARIOUS CUT SECTIONS
 THROUGH THE ROOF SHEATHING, IN THE
 PLANS REVEAL 2 THICKNESSES AND THE
 USE OF 1/2" THICK HIGH DENSITY
 SUBSTATE, CLARIFY.PLEASE CORRECT
 ALL DETAILS TO THE SAME THICKNESS.
 10C) TABLE 2304.7(5) FOOTNOTE (D) LIMITS
  
 THE USE OF ROOF SHEATHING TO
 19/32" WOOD STRUCTURAL PANELS IN
 WIND REGIONS OF 110 - 140MPH,
 EXPOSURE B.
 10D) DETAIL# 8 INDICATES THE USE OF BOTH
  
 WOOD AND METAL TRUSSES?
 10E) BOTH THIS SHEET AND A2.1.1 ARE
 MISSING THE ATTIC ACCESS
  
 10F) THE FLOOR PLAN NOR WALL SECTIONS
 INDICATE ATTIC ACCESS?
  
 11) PLANS SUBMITTED ALSO INDICATE A BUS
 SHELTER (A6.13)THIS WILL BE STRUCK SINCE
 THE BUS SHELTER SHOULD BE PART OF A SITE
 AMENITIES PACKAGE THAT WOULD BE
 PERMITTED SEPARATELY.
  
 12A) PRODUCT APPROVALS REQUIRE;
 RULE 9B-72- PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE WITH THE ASSOCIATED REPORT. IF
 THE PRODUCT DOES NOT HAVE STATEWIDE
 APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL ON THE CITY FORM
 PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 12B) CONTRACTOR SUBMITTED PRODUCT
 APPROVALS WHICH WILL NOT BE USED ON THIS
 PROJECT, PLEASE REMOVE FROM PACKAGE.
  
 12C)FL BLD CODE 1602/COMPONENTS &
 CLADDING, 1609.6 : COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) GLAZED FRONT ENTRY DOORS
 B) SOLID SWING DOOR
 C) TRUSS ANCHORS
 D) ROOF ASSEMBLIES TILE ROOF
 E) DENSEGLASS SHEATHING
  
 13) SHEET S-3 :
 13A)WIND LOAD SCHEDULE INDICATES
 COMPLIANCE WITH THE 2001 FL BLDG CODE,
 PLEASE CORRECT.
 13B) TRUSS TIE DOWN SCHEDULE, SIMPSON
 HETAL-12 THE VALUE SHOWN IS FOR A TWO
 PLY MEMBER NOT INDICATED AS SUCH, THE
 VALUE FOR A SINGLE MEMBER IS 1265.
  
 14) 1503.6 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 15)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026