| 2005-11-17 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05080677 |
| | ADD: 719 EXECUTIVE CENTER DR |
| | (CLUBHOUSE) |
| | CONT: THE WEITZ CO. |
| | TEL: (561)686-5511 |
| | CELL:(954)675-4302 |
| | |
| | ARCHITECT: ACI ARCHITECRTURALGROUP |
| | PAUL M. TWITTY |
| | TEL:(561)832-5599 |
| | STRUC ENGINEER: ONM&J |
| | PHILLIP RIZZO |
| | TEL:(561)835-9994 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE |
| | ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET |
| | OR SPECIFICATION PAGE WHERE THE CHANGES |
| | CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 2) 105.8* PROVIDE NOC RECORDED WITH THE |
| | CLERK OF COURT BEFORE A PERMIT CAN BE |
| | ISSUED. |
| | |
| | 3)109.3.7*THIS PARTICUAL TYPE OF |
| | BUILDING "WILL NOT" REQUIRE A SPECIAL |
| | INSPECTOR, ALTHOUGH THERE WILL BE A |
| | THRESHOLD INSPECTOR FOR THE MID RISE AND |
| | HIGH RISE BUILDINGS.WILL THIS INSPECTOR |
| | ALSO BE INSPECTING THIS BUILDING? IF SO |
| | THREE (3) SET OF ALL DOCUMENTS WILL NEED |
| | TO BE SUBMITTED AS IF FOR ATHRESHOLD |
| | BUILDING.WILL THIS INSPECTOR BE THE SAME |
| | PERSON AS THE THRESHOLD INSPECTOR? OR |
| | WILL THERE BE TWO INDIVIDUALS? |
| | FORMS WILL NEED TO BE FILLED OUT FOR THE |
| | SPECIAL INSPECTOR, CONTACT HAROLD |
| | PISKURA, INSPECTION SERVICES MANAGER @ |
| | (561)805-6711 TO SEET UP AN APPOINTMENT. |
| | |
| | 4) 106.3.3* PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY DCA RULE |
| | 9B-72 SHALL BE REVIEWED AND APPROVED IN |
| | WRITTING BY THE DESIGNER OF RECORD PRIOR |
| | TO SUBMITTAL FOR " JURISDICTIONAL |
| | APPROVAL", (LOCAL PRODUCT APPROVAL). |
| | |
| | 5) SITE PLAN NEEDS TO BE SUBMITTED TO |
| | ADDRESSING PERSONEL JOHN HIGGINS FOR |
| | ADDRESSING AS WELL AS NEW PLAT MAP FOR |
| | THE COMBINATION OF LOTS. JOHN HIGGINS |
| | CONTACT NUMBER IS (561)822-1239. |
| | |
| | 6A) THERE IS A DISCREPANCY IN THE PLANS |
| | SINCE THE BOUNDRY SURVEY FOR PARCEL# 7, |
| | ONLY INDICATES 2 LOTS PARCEL 1&2.NOTE: |
| | FOR TOWNHOUSES EACH UNIT WILL REQUIRE |
| | INDIVIDUAL PROPERTY CONTROL NUMBERS |
| | WITH ASSOCIATED PROPERTY LINE. |
| | 6B) THE SURVEY DOES SHOW 2 SEPERATE LOTS |
| | WHICH APPEAR TO CUT THROUGH BULDING "B" |
| | AND BUILDING "C". A UNITY OF TITLE SHALL |
| | BE REQUIRED, TABLE 601 AND 602. |
| | |
| | |
| | 7) ENERGY COMPLIANCE FORMS: |
| | 7A) UPDATE FORM TO FORM 400A-04 |
| | |
| | 8) GEOTECHNICAL REPORT THAT WORK WAS |
| | PREFORMED BY ARDAMAN NEEDS TO BE AN |
| | ORIGINAL WITH SIGNATURE AND RAISED SEAL. |
| | PLANS, SPECIFICATIONS,REPORTS OR OTHER |
| | DOCUMENTS PREPARED BY THE DESIGN |
| | PROFESSIONAL AND BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | FL ATATE STAT: 61G16.003 ARCHITECTS |
| | |
| | 9A) SHEET A3.2.1 WALL SECTIONS DO NOT |
| | INDICATE WHAT TYPE OF TERMITE TREATMENT |
| | FOR SOILS WILL BE USED, SEE 1816.1. |
| | 9B) THIS SAME SHEET INDICATES THE USE OF |
| | A VAPOR BARRIER, MUST BE A MINIMUM OF 6 |
| | MIL TO BE USED WITH CHEMICALLY TREATED |
| | TERMITE TREATMENT FOR SOILS BENEATH |
| | SLAB.1806.1.4. |
| | 9C) 1816.1.6 IF SOIL TREATMENT IS USED |
| | FOR SUBTERRANEAN TERMITE PREVENTION, |
| | CHEMICAL SOIL TREATMENT SHALL BE APPLIED |
| | UNDER ALL EXTERIOR CONCRETE OR GRADE |
| | WITHIN 1 FT OF THE PRIMARY STRUCTURE |
| | SIDEWALLS. |
| | |
| | 10) SHEET A6.1.1: |
| | 10A) THE WALL SECTION# 8 DOESN'T |
| | INDICATE COMPLIANCE WITH ATTIC |
| | VENTILATION REQUIREMENTS FOUND IN |
| | 1203.2. PLEASE INDICATE COMPLIANCE |
| | WITH BOTH THE EAVE REQUIREMENTS AS |
| | WELL AS 1/150 OF THE AREA OF THE |
| | SPACE TO BE VENTILATED AND 50% OF |
| | THE REQUIRED VENTILATION BE IN THE |
| | UPPER PORTION OF THE SPACE TO BE |
| | VENTILATED. |
| | 10B) THE DETAIL#8 DOESN'T MATCH SHEET |
| | A3.2.1VARIOUS CUT SECTIONS |
| | THROUGH THE ROOF SHEATHING, IN THE |
| | PLANS REVEAL 2 THICKNESSES AND THE |
| | USE OF 1/2" THICK HIGH DENSITY |
| | SUBSTATE, CLARIFY.PLEASE CORRECT |
| | ALL DETAILS TO THE SAME THICKNESS. |
| | 10C) TABLE 2304.7(5) FOOTNOTE (D) LIMITS |
| | |
| | THE USE OF ROOF SHEATHING TO |
| | 19/32" WOOD STRUCTURAL PANELS IN |
| | WIND REGIONS OF 110 - 140MPH, |
| | EXPOSURE B. |
| | 10D) DETAIL# 8 INDICATES THE USE OF BOTH |
| | |
| | WOOD AND METAL TRUSSES? |
| | 10E) BOTH THIS SHEET AND A2.1.1 ARE |
| | MISSING THE ATTIC ACCESS |
| | |
| | 10F) THE FLOOR PLAN NOR WALL SECTIONS |
| | INDICATE ATTIC ACCESS? |
| | |
| | 11) PLANS SUBMITTED ALSO INDICATE A BUS |
| | SHELTER (A6.13)THIS WILL BE STRUCK SINCE |
| | THE BUS SHELTER SHOULD BE PART OF A SITE |
| | AMENITIES PACKAGE THAT WOULD BE |
| | PERMITTED SEPARATELY. |
| | |
| | 12A) PRODUCT APPROVALS REQUIRE; |
| | RULE 9B-72- PRODUCT APPROVALS SUBMITTED |
| | WITH PERMIT APPLICATION AFTER OCTOBER 1, |
| | 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION PLEASE SEE THE STATE WEBSITE |
| | AT WWW.FLORIDABUILDING.ORG. PRODUCTS |
| | WITH STATEWIDE APPROVAL ARE REQUIRED TO |
| | BE SUBMITTED WITH A COVER SHEET THAT |
| | LISTS THE PRODUCT IDENTITY NUMBER FROM |
| | THE STATE WITH THE ASSOCIATED REPORT. IF |
| | THE PRODUCT DOES NOT HAVE STATEWIDE |
| | APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL ON THE CITY FORM |
| | PER RULE 9B-72. SEE ATTACHMENT. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 12B) CONTRACTOR SUBMITTED PRODUCT |
| | APPROVALS WHICH WILL NOT BE USED ON THIS |
| | PROJECT, PLEASE REMOVE FROM PACKAGE. |
| | |
| | 12C)FL BLD CODE 1602/COMPONENTS & |
| | CLADDING, 1609.6 : COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) GLAZED FRONT ENTRY DOORS |
| | B) SOLID SWING DOOR |
| | C) TRUSS ANCHORS |
| | D) ROOF ASSEMBLIES TILE ROOF |
| | E) DENSEGLASS SHEATHING |
| | |
| | 13) SHEET S-3 : |
| | 13A)WIND LOAD SCHEDULE INDICATES |
| | COMPLIANCE WITH THE 2001 FL BLDG CODE, |
| | PLEASE CORRECT. |
| | 13B) TRUSS TIE DOWN SCHEDULE, SIMPSON |
| | HETAL-12 THE VALUE SHOWN IS FOR A TWO |
| | PLY MEMBER NOT INDICATED AS SUCH, THE |
| | VALUE FOR A SINGLE MEMBER IS 1265. |
| | |
| | 14) 1503.6 PROTECTION AGAINST DECAY & |
| | TERMITES. CONDENSATE LINES & ROOF DOWN |
| | SPOUTS SHALL DISCHARGE AT LEAST 1 FT. |
| | AWAY FROM THE STRUCTURE SIDEWALL, |
| | WHETHER BY UNDERGROUND PIPING, TAIL EX- |
| | TENSIONS, OR SPLASH BLOCKS. |
| | |
| | 15)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |