| Date |
Text |
| 2006-05-13 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FHA-98 DESIGN MANUAL |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | FROM PREVIOUS REVIEW: |
| | |
| | 1. INFORMATIONAL. |
| | |
| | 2. ALL PLANS DESIGNED BY A PROFESSIONAL |
| | ARCHITECT OR ENGINEER, THEN ALL SHEETS |
| | SHALL BE SIGNED, SEALED, & DATED AS |
| | REQUIRED BY FLORIDA STATUTES. SECTION |
| | 106.1. |
| | ***RESPONSE NOTED, BUT BOUNDRY SURVEY, |
| | SHTS PP1 OF 9 THRU PP9 OF 9, LA-POOL-1 |
| | THRU LA-POOL-4, LA-FW-1 THRU LA-FW-6 |
| | HAVE NOT BEEN SIGNED, SEALED, DATED. |
| | |
| | 3. SHT P0.1 REFERENCES FBC-2001 CODE. |
| | PER SHT LT-2 CODE SUMMARY BUILDING HAS |
| | BEEN DESIGNED ACCORDING TO FBC-2004. |
| | PLEASE CORRELATE PLUMBING SHEETS WITH |
| | CODE SUMMARY SHEET. |
| | ***RESPONSE NOTED, BUT PLUMBING NOTES 1 |
| | & 24 HAVE NOT BEEN CHANGED. ALSO SEE |
| | WATER HEATER DETAIL & GENERAL NOTES (2) |
| | UNDER PLUMBING FIXTURE SCHEDULE FOR |
| | REFERENCES TO FBC-2001 CODE. |
| | |
| | 5. SHT P5.1 WATER RISER ISO. WATER |
| | HAMMER ARRESTORS SHALL BE LOCATED NEAR |
| | THE FIXTURE IN AN "EFFECTIVE RANGE" NOT |
| | IN THE CEILING AS SHOWN. (SEE SHT P0.1 |
| | PLUMBING NOTE 13 AND W/M CONNECTION |
| | DETAIL). PDI-WH 201 AND MANUF. |
| | INSTALLATION INSTRUCTIONS. - WATER |
| | HAMMER ARRESTORS REQUIRED AT REF. AND |
| | DISHWASHER BOTH UNIT TYPES. SECTION |
| | 604.9. |
| | ***RESPONSE NOTED, BUT THERE ARE NO |
| | WATER HAMMER ARRESTORS AT THE REF. |
| | |
| | 9. SHT P5.1 THE FOLLOWING INFORMATION IS |
| | REQUIREMENTS FOR GAS PERMIT: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | ***RESPONSE NOTED, BUT THE LENGHTS OF |
| | CUT SECTIONS IS NOT SHOWN. |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | ***RESPONSE NOTED, BUT PIPE MATERIAL NOT |
| | FOUND ON ISOMETRIC. |
| | |
| | I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ***RESPONSE NOTED, BUT MANUF. SHEETS NOT |
| | SUBMITTED. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | ***NO RESPONSE NOTED, VOIDED SHEETS TO |
| | BE REMOVED FROM SETS OF PLANS. |
| | |
| | **************NEW COMMENTS************** |
| | |
| | 1B. SHT P5.1 WATER RISER DIAGRAMS. |
| | SHUTOFF VALVES SHALL BE INSTALLED ON THE |
| | WATER SUPPLY PIPE TO EACH SILLCOCK. |
| | SECTION 606.2(2). |
| | |
| | 2B. SEE ATTACHED SHEET CONCERNING THE |
| | DESIGN PROFESSIONAL & FS 553.80(2)(B). |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |