Plan Review Notes
Plan Review Notes For Permit 05080676
Permit Number 05080676
Review Stop P
Sequence Number 2
Notes
Date Text
2006-05-13 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
  
 1. INFORMATIONAL.
  
 2. ALL PLANS DESIGNED BY A PROFESSIONAL
 ARCHITECT OR ENGINEER, THEN ALL SHEETS
 SHALL BE SIGNED, SEALED, & DATED AS
 REQUIRED BY FLORIDA STATUTES. SECTION
 106.1.
 ***RESPONSE NOTED, BUT BOUNDRY SURVEY,
 SHTS PP1 OF 9 THRU PP9 OF 9, LA-POOL-1
 THRU LA-POOL-4, LA-FW-1 THRU LA-FW-6
 HAVE NOT BEEN SIGNED, SEALED, DATED.
  
 3. SHT P0.1 REFERENCES FBC-2001 CODE.
 PER SHT LT-2 CODE SUMMARY BUILDING HAS
 BEEN DESIGNED ACCORDING TO FBC-2004.
 PLEASE CORRELATE PLUMBING SHEETS WITH
 CODE SUMMARY SHEET.
 ***RESPONSE NOTED, BUT PLUMBING NOTES 1
 & 24 HAVE NOT BEEN CHANGED. ALSO SEE
 WATER HEATER DETAIL & GENERAL NOTES (2)
 UNDER PLUMBING FIXTURE SCHEDULE FOR
 REFERENCES TO FBC-2001 CODE.
  
 5. SHT P5.1 WATER RISER ISO. WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR
 THE FIXTURE IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING AS SHOWN. (SEE SHT P0.1
 PLUMBING NOTE 13 AND W/M CONNECTION
 DETAIL). PDI-WH 201 AND MANUF.
 INSTALLATION INSTRUCTIONS. - WATER
 HAMMER ARRESTORS REQUIRED AT REF. AND
 DISHWASHER BOTH UNIT TYPES. SECTION
 604.9.
 ***RESPONSE NOTED, BUT THERE ARE NO
 WATER HAMMER ARRESTORS AT THE REF.
  
 9. SHT P5.1 THE FOLLOWING INFORMATION IS
 REQUIREMENTS FOR GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ***RESPONSE NOTED, BUT THE LENGHTS OF
 CUT SECTIONS IS NOT SHOWN.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 ***RESPONSE NOTED, BUT PIPE MATERIAL NOT
 FOUND ON ISOMETRIC.
  
 I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ***RESPONSE NOTED, BUT MANUF. SHEETS NOT
 SUBMITTED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 ***NO RESPONSE NOTED, VOIDED SHEETS TO
 BE REMOVED FROM SETS OF PLANS.
  
 **************NEW COMMENTS**************
  
 1B. SHT P5.1 WATER RISER DIAGRAMS.
 SHUTOFF VALVES SHALL BE INSTALLED ON THE
 WATER SUPPLY PIPE TO EACH SILLCOCK.
 SECTION 606.2(2).
  
 2B. SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL & FS 553.80(2)(B).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]