| Notes |
| Date |
Text |
| 2006-05-05 00:00:00 | DENIED: | | | COMMENTS ONE THROUGH FOUR FROM REVIEW | | | DATED 10-17-2005 WERE ADDRESSED. | | | | | | COMMENT #5: GAS APPLIANCES - PLAN SHEET | | | P5.1, INDICATES THE WATER HEATER, DRYER | | | & RANGE WILL BE GAS APPLLIANCES. | | | RESPONSE REFERS TO THE ARCHITECTURAL | | | PLANS FOR LOUVER ON THE DOOR. PLEASE | | | VERIFY THE FOLLOWING: | | | - UNITS 100- 500 THE DOOR FOR THE | | | LAUNDRY ROOM & CLOSET FOR THE AHU & | | | THE WATER HEATER. THE DOOR SCHEDULE | | | ON PLAN SHEET A7.1.1 SHOW SOLID DOORS | | | NOT LOUVERED DOORS. | | | | | | - PLAN SHEET M7.1 DETAIL 5 INDICATES | | | THE AHU IN A CLOSET WITH THE GAS | | | WATER HEATER.AS INDICATED ON THE | | | PLAN, THIS CLOSET SERVES AS A RETURN | | | AIR PLENUM.PER 2004 FMC 602.1, FUEL | | | FIRED APPLIANCES ARE NOT ALLOWED IN | | | THE RETURN AIR PLENUM. | | | | | | PLEASE NOTE, PER 2004 FMC 504.4, WHERE | | | DRYER INSTALLATION EXHAUST GREATER THAN | | | 200 CFM SHALL BE PROVIDED WITH MAKE-UP | | | AIR. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|