Plan Review Notes
Plan Review Notes For Permit 05080676
Permit Number 05080676
Review Stop M
Sequence Number 2
Notes
Date Text
2006-05-05 00:00:00DENIED:
 COMMENTS ONE THROUGH FOUR FROM REVIEW
 DATED 10-17-2005 WERE ADDRESSED.
  
 COMMENT #5: GAS APPLIANCES - PLAN SHEET
 P5.1, INDICATES THE WATER HEATER, DRYER
 & RANGE WILL BE GAS APPLLIANCES.
 RESPONSE REFERS TO THE ARCHITECTURAL
 PLANS FOR LOUVER ON THE DOOR. PLEASE
 VERIFY THE FOLLOWING:
 - UNITS 100- 500 THE DOOR FOR THE
 LAUNDRY ROOM & CLOSET FOR THE AHU &
 THE WATER HEATER. THE DOOR SCHEDULE
 ON PLAN SHEET A7.1.1 SHOW SOLID DOORS
 NOT LOUVERED DOORS.
  
 - PLAN SHEET M7.1 DETAIL 5 INDICATES
 THE AHU IN A CLOSET WITH THE GAS
 WATER HEATER.AS INDICATED ON THE
 PLAN, THIS CLOSET SERVES AS A RETURN
 AIR PLENUM.PER 2004 FMC 602.1, FUEL
 FIRED APPLIANCES ARE NOT ALLOWED IN
 THE RETURN AIR PLENUM.
  
 PLEASE NOTE, PER 2004 FMC 504.4, WHERE
 DRYER INSTALLATION EXHAUST GREATER THAN
 200 CFM SHALL BE PROVIDED WITH MAKE-UP
 AIR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.