Plan Review Notes
Plan Review Notes For Permit 05080676
Permit Number 05080676
Review Stop E
Sequence Number 2
Notes
Date Text
2006-04-27 00:00:00IN ELEC FOR REVIEW.
 ***** UNSAT *****
  
 PLEASE SEE MOST NOTES FROM PREVIOUS
 REVIEW WERE ADDRESSED, HOWEVER SOME
 NOTES REMAIN.
 PLEASE SEE A COUPLE OF NEW COMMENTS DUE
 TO CHANGES.
 PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW. PLEASE
 ALSO SEE NOTES PERTAINING TO THE REMOVAL
 OF ALL OLDV/VOIDED SHEETS AS REQUESTED
 ON PREVIOUS REVIEW.
  
  
 SAIL CLUB
 TOWNHOUSE(CONDO) BLDG #7
  
 1)NOTE: OK.
  
 2)NOTE: OK.
  
 3)NOTE: NOTE #3, PLEASE SEE RESPONSE
 MENTIONS TO LATEST EDITION, HOWEVER,
 PLEASE STATE THE FOLLOWING CODES ON
 PLANS.
 2002 NFPA-70, 2002 NFPA-72, 2003
 NFPA-101.
  
 ** PREVIOUS NOTE**
 PLEASE SEE PLANS REFERENCE THE
 1999 NEC. PLEASE SEE AS OF JULY 7TH,2003
 THE STATE ADOPTED THE 2002 NEC.
  
 4)NOTE: OK.
  
 5)NOTE: OK.
  
 6)NOTE: OK.
  
 7)NOTE: NOTE #7 ? NO, PLEASE SEE PANEL
 SCHEDULE STILL SHOWS A AND C PHASE?
 PLEASE EXPLAIN THIS AS SERVICE IS BEING
 SHOWN AS SINGLE PHASE,IS THIS NOT A AND
 B?
  
 ** PREVIOUS NOTE **
 PLEASE SEE PANEL INDICATES "A"
 AND "C" PHASES? PLEASE CLARIFY AS
 SERVICE IS SHOWN AS SINGLE PHASE. A&B)
  
 8)NOTE: OK.
  
 9)NOTE: OK.
  
 10)NOTE:NOTE #13 NO, PLEASE SEE
 MISSING RECEPT ALONG WALL IN WHAT
 APPEARS TO BE LIVING RM 502?
 THIS IS REDLINED AT LOCATION.
  
 **PREVIOUS NOTE **
 PLEASE SEE REDLINED PLANS FOR SOME
 MISSING RECEPTS PER 210.52
 PLEASE SEE WALL SPACE AT STAIRS, WALL
 SPACE IN "E" UNIT.
  
 11)NOTE:OK, HOWEVER ONLY RESPONSE
 LETTER MENTIONS A CHANGE TO A GAS RANGE
 AND PLANS ONLY CALL FOR A "RANGE" , IF
 GAS, PLEASE INDICATE ON SCHEDULE.
  
 ** PREVIOUS NOTE **
 PLEASE CLARIFY AND ADJUST OCP SHOWN FOR
 RANGE. PANEL SCHEDULE INDICATES A 70A 2P
 BRKR FOR WHAT WOULD BE A 50A RECEPT FOR
 RANGE.
 PLEASE SEE 406.2B, 210.21B3,4
  
 **************************************
 NEW NOTES
  
 12) NOTE: PLEASE SEE 250.66,250.50,
 250.56,250.64(C) .
 PLEASE SEE THE MIN GEC SHALL BE SIZED
 PER 250.66, (1/0). PLEASE ALSO KNOW,
 THIS 1/0 SHALL BE CONTINUOUS TO FOOTER
 STEEL ETC.
  
 13) NOTE: PLEASE CLARIFY THE NEW LAYOUT
 IN UNITS, WHERE WHAT APPEARS TO BE A
 WATER HEATER IN A NEW LAUNDRY/
 CATV/PHONE RM. IDENTIFY EQUIPMENT SHOWN
 IN ROOM ON PLANS.
  
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ****************************************
 PLEASE COMPLETELY REMOVE ALL OLD/ VOIDED
 SHEETS FROM SETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 ONE COPY OF ALL OLD/VOIDED SHEETS SHOULD
 BE ATTACHED TO EACH OTHER TO COMPOSE OF
 ONE SET OF VOIDED SHEETS ONLY AND WILL
 BE SUBMITTED ALONG WITH NEW SETS FOR
 REFERENCE.
 **************************************
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  