| 2006-04-27 00:00:00 | IN ELEC FOR REVIEW. |
| | ***** UNSAT ***** |
| | |
| | PLEASE SEE MOST NOTES FROM PREVIOUS |
| | REVIEW WERE ADDRESSED, HOWEVER SOME |
| | NOTES REMAIN. |
| | PLEASE SEE A COUPLE OF NEW COMMENTS DUE |
| | TO CHANGES. |
| | PLEASE SEE NOTES BELOW ARE TAKEN |
| | DIRECTLY FROM PREVIOUS REVIEW. PLEASE |
| | ALSO SEE NOTES PERTAINING TO THE REMOVAL |
| | OF ALL OLDV/VOIDED SHEETS AS REQUESTED |
| | ON PREVIOUS REVIEW. |
| | |
| | |
| | SAIL CLUB |
| | TOWNHOUSE(CONDO) BLDG #7 |
| | |
| | 1)NOTE: OK. |
| | |
| | 2)NOTE: OK. |
| | |
| | 3)NOTE: NOTE #3, PLEASE SEE RESPONSE |
| | MENTIONS TO LATEST EDITION, HOWEVER, |
| | PLEASE STATE THE FOLLOWING CODES ON |
| | PLANS. |
| | 2002 NFPA-70, 2002 NFPA-72, 2003 |
| | NFPA-101. |
| | |
| | ** PREVIOUS NOTE** |
| | PLEASE SEE PLANS REFERENCE THE |
| | 1999 NEC. PLEASE SEE AS OF JULY 7TH,2003 |
| | THE STATE ADOPTED THE 2002 NEC. |
| | |
| | 4)NOTE: OK. |
| | |
| | 5)NOTE: OK. |
| | |
| | 6)NOTE: OK. |
| | |
| | 7)NOTE: NOTE #7 ? NO, PLEASE SEE PANEL |
| | SCHEDULE STILL SHOWS A AND C PHASE? |
| | PLEASE EXPLAIN THIS AS SERVICE IS BEING |
| | SHOWN AS SINGLE PHASE,IS THIS NOT A AND |
| | B? |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE PANEL INDICATES "A" |
| | AND "C" PHASES? PLEASE CLARIFY AS |
| | SERVICE IS SHOWN AS SINGLE PHASE. A&B) |
| | |
| | 8)NOTE: OK. |
| | |
| | 9)NOTE: OK. |
| | |
| | 10)NOTE:NOTE #13 NO, PLEASE SEE |
| | MISSING RECEPT ALONG WALL IN WHAT |
| | APPEARS TO BE LIVING RM 502? |
| | THIS IS REDLINED AT LOCATION. |
| | |
| | **PREVIOUS NOTE ** |
| | PLEASE SEE REDLINED PLANS FOR SOME |
| | MISSING RECEPTS PER 210.52 |
| | PLEASE SEE WALL SPACE AT STAIRS, WALL |
| | SPACE IN "E" UNIT. |
| | |
| | 11)NOTE:OK, HOWEVER ONLY RESPONSE |
| | LETTER MENTIONS A CHANGE TO A GAS RANGE |
| | AND PLANS ONLY CALL FOR A "RANGE" , IF |
| | GAS, PLEASE INDICATE ON SCHEDULE. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE CLARIFY AND ADJUST OCP SHOWN FOR |
| | RANGE. PANEL SCHEDULE INDICATES A 70A 2P |
| | BRKR FOR WHAT WOULD BE A 50A RECEPT FOR |
| | RANGE. |
| | PLEASE SEE 406.2B, 210.21B3,4 |
| | |
| | ************************************** |
| | NEW NOTES |
| | |
| | 12) NOTE: PLEASE SEE 250.66,250.50, |
| | 250.56,250.64(C) . |
| | PLEASE SEE THE MIN GEC SHALL BE SIZED |
| | PER 250.66, (1/0). PLEASE ALSO KNOW, |
| | THIS 1/0 SHALL BE CONTINUOUS TO FOOTER |
| | STEEL ETC. |
| | |
| | 13) NOTE: PLEASE CLARIFY THE NEW LAYOUT |
| | IN UNITS, WHERE WHAT APPEARS TO BE A |
| | WATER HEATER IN A NEW LAUNDRY/ |
| | CATV/PHONE RM. IDENTIFY EQUIPMENT SHOWN |
| | IN ROOM ON PLANS. |
| | |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | **************************************** |
| | PLEASE COMPLETELY REMOVE ALL OLD/ VOIDED |
| | SHEETS FROM SETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | ONE COPY OF ALL OLD/VOIDED SHEETS SHOULD |
| | BE ATTACHED TO EACH OTHER TO COMPOSE OF |
| | ONE SET OF VOIDED SHEETS ONLY AND WILL |
| | BE SUBMITTED ALONG WITH NEW SETS FOR |
| | REFERENCE. |
| | ************************************** |
| | |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |