| Date |
Text |
| 2005-11-09 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FHA-98 DESIGN MANUAL |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SHTS LA-POOL-3 & LA-POOL-4 SEPARATE |
| | POOL PLANS & PERMIT ARE REQUIRED FOR |
| | EACH POOL. PLANS SHALL BE ROUTED TO THE |
| | PALM BEACH COUNTY HEALTH DEPT FOR REVIEW |
| | AND SHALL BE STAMPED PRIOR TO SUBMITTING |
| | TO CITY WPB FOR REVIEW. (MIN. 2 SETS OF |
| | PLANS). |
| | 2. ALL PLANS DESIGNED BY A PROFESSIONAL |
| | ARCHITECT OR ENGINEER, THEN ALL SHEETS |
| | SHALL BE SIGNED, SEALED, & DATED AS |
| | REQUIRED BY FLORIDA STATUTES. SECTION |
| | 106.1. |
| | 3. SHT P0.1 REFERENCES FBC-2001 CODE. |
| | PER SHT LT-2 CODE SUMMARY BUILDING HAS |
| | BEEN DESIGNED ACCORDING TO FBC-2004. |
| | PLEASE CORRELATE PLUMBING SHEETS WITH |
| | CODE SUMMARY SHEET. |
| | 4. SHT P5.1 SANITARY RISER ISO. |
| | CLEANOUTS FOR THE W/M SHALL BE INSTALLED |
| | 4' ABOVE THE FLOOR, AND A STANDPIPE IS |
| | REQUIRED FOR THE W/M. SECTIONS 708.9 AND |
| | 1002.1. |
| | 5. SHT P5.1 WATER RISER ISO. WATER |
| | HAMMER ARRESTORS SHALL BE LOCATED NEAR |
| | THE FIXTURE IN AN "EFFECTIVE RANGE" NOT |
| | IN THE CEILING AS SHOWN. (SEE SHT P0.1 |
| | PLUMBING NOTE 13 AND W/M CONNECTION |
| | DETAIL). PDI-WH 201 AND MANUF. |
| | INSTALLATION INSTRUCTIONS. - WATER |
| | HAMMER ARRESTORS REQUIRED AT REF. AND |
| | DISHWASHER BOTH UNIT TYPES. SECTION |
| | 604.9 |
| | 9. SHT P5.1 THE FOLLOWING INFORMATION IS |
| | REQUIREMENTS FOR GAS PERMIT: |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | C. TYPE OF GAS, (LP OR NATURAL) |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6 AND TABLES 402(1) THRU |
| | 402(33). |
| | E. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. |
| | F. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 506. |
| | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2 |
| | J. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | K. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND |
| | APPURTENANCES PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |