| 2005-10-17 00:00:00 | DENIED: TOWNHOUSE #7 - 2004 FBC |
| | 1.PLAN SHEET M.01 MECHANICAL NOTE 1 |
| | REFERENCES ASHRAE STANDARDS THAT ARE NOT |
| | CURRENT WITH WHAT IS LISTED IN THE 2004 |
| | CODE.SHOULD READ ASHRAE 15-01, 34-01, |
| | 62-01 NFPA AS FOLLOWS; 90A-02, 90B-02, |
| | 91-00, 96-01.MECHANICAL NOTES ALSO |
| | REFERENCE THE 2001 FBC. |
| | |
| | 2.SEE COMMENT #6(A) THROUGH (D) IN |
| | REGARDS TO THE CLASSIFICATION OF |
| | 'TOWNHOUSE' AS INDICATED ON PLANS. |
| | |
| | 3.UNITS 100 - THE SECOND FLOOR 16" X |
| | 8" DUCT ACCORDING TO NOTE #1 IS AN 8" X |
| | 8" DUCT UP TO GOOSENECK ON ROOF (TYPICAL |
| | OF ALL).ONE UNIT 300 IT ALSO INDICATES |
| | THIS AS BEING A 16" X 8" DUCT DOWN TO |
| | 1ST FLOOR ACCORDING TO NOTE 3, PLEASE |
| | CLARIFY. |
| | |
| | 4.RETURN AIR JUMPER'S TO THE MASTER |
| | SUITE SHALL BE INCREASED TO 1 1/2 TIMES |
| | THE TOTAL SUPPLY AIR INTO THE MASTER |
| | SUITE (INCLUDE AIR INTO MASTER BATH & |
| | CLOSET).2004 FMC 601.4 EXCEPTIONS 1 & |
| | 3. |
| | |
| | 5.PLEASE INDICATE ANY GAS APPLIANCES |
| | THAT MAY BE AN OPTION FOR INSTALLATION. |
| | PLEASE PROVIDE PERTINENT INFORMATION FOR |
| | COMBUSTION AIR. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |