2005-10-17 00:00:00DENIED: TOWNHOUSE #7 - 2004 FBC
 1.PLAN SHEET M.01 MECHANICAL NOTE 1
 REFERENCES ASHRAE STANDARDS THAT ARE NOT
 CURRENT WITH WHAT IS LISTED IN THE 2004
 CODE.SHOULD READ ASHRAE 15-01, 34-01,
 62-01 NFPA AS FOLLOWS; 90A-02, 90B-02,
 91-00, 96-01.MECHANICAL NOTES ALSO
 REFERENCE THE 2001 FBC.
  
 2.SEE COMMENT #6(A) THROUGH (D) IN
 REGARDS TO THE CLASSIFICATION OF
 'TOWNHOUSE' AS INDICATED ON PLANS.
  
 3.UNITS 100 - THE SECOND FLOOR 16" X
 8" DUCT ACCORDING TO NOTE #1 IS AN 8" X
 8" DUCT UP TO GOOSENECK ON ROOF (TYPICAL
 OF ALL).ONE UNIT 300 IT ALSO INDICATES
 THIS AS BEING A 16" X 8" DUCT DOWN TO
 1ST FLOOR ACCORDING TO NOTE 3, PLEASE
 CLARIFY.
  
 4.RETURN AIR JUMPER'S TO THE MASTER
 SUITE SHALL BE INCREASED TO 1 1/2 TIMES
 THE TOTAL SUPPLY AIR INTO THE MASTER
 SUITE (INCLUDE AIR INTO MASTER BATH &
 CLOSET).2004 FMC 601.4 EXCEPTIONS 1 &
 3.
  
 5.PLEASE INDICATE ANY GAS APPLIANCES
 THAT MAY BE AN OPTION FOR INSTALLATION.
 PLEASE PROVIDE PERTINENT INFORMATION FOR
 COMBUSTION AIR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.