| Plan Review Notes For Permit 05080676 |
| Permit Number |
05080676 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-10-19 00:00:00 | 1ST FIRE REVIEW | | | ACTION: DENIED | | | | | | 1) NOTE ONLY: THE POOL DECK THAT'S NOT | | | PART OF THIS PERMIT ( PHASE I TOWN HOUSE | | | #7 ) IT APPEARS THAT IT HAVE ONLY ONE | | | EXIT FROM THE DECK ( TWO EXITS ARE | | | REQUIRED ). | | | | | | 2) IN ADDITION TO THE HEIGHT REQUIREMENT | | | THE ADDRESS NUMBERS SHALL CONTRAST TO | | | THE BACKGROUND. SHEET TH-7 A1.1.2. | | | | | | 3) ABC MULTI-PURPOSE RATED FIRE | | | EXTINGUISHERS ARE REQUIRED. | | | | | | 4) INTERIOR FINISH ON WALLS AND CEILINGS | | | OF OCCUPIED SPACES SHALL BE CLASS A, | | | CLASS B, OR CLASS C AS DEFINED IN | | | SECTION 10.2. | | | | | | 5) FIRE HYDRANTS SHALL BE WET PRIOR TO, | | | DURING AND AFTER CONSTRUCTION. | | | | | | 6) EMERGENCY VEHICLE ACCESS LANES SHALL | | | BE MAINTAINED AT A WIDTH OF AT LEAST | | | 20'. | | | | | | 7) SHALL COMPLY WITH NFPA 101 LIFE | | | SAFETY CODE, 2003 EDITION AND NFPA 1 | | | UNIFORM FIRE CODE, 2003 EDITION. | | | | | | | | | NATE MCCRAY, ASSISTANT FIRE MARSHAL | | | 561-804-4754 |
|