| 2005-08-23 00:00:00 | FAILED: |
| | |
| | 1. SHEET 9, PLEASE NOTE THAT CURB RAMPS |
| | MUST BE DETAILED PER LATEST FDOT INDEX |
| | 304 WITH 2' DETECTABLE WARNING. |
| | 2. ORIGINAL APPROVED SITE PLAN BY THE |
| | PLANNING AND ZONING SHOWS A 8'TO 10'OF |
| | BICYCLE/ WALKWAY ALONG THE CLEAR LAKE, |
| | PLEASE VERIFY WITH THE ARCHITECTURAL |
| | PLANS. |
| | 3. PLEASE SUBMIT A COPY OF THE SFWMD |
| | PERMIT TO US AND ONE COPY TO THE PUBLIC |
| | UTILITIES AND ENGINEERING ATT; STEVE |
| | SARLEY. |
| | 4. SHEET 11, GARAGE DETENTION POND |
| | DETAILS, SHOW 60'PROPOSED UNDERDRAIN |
| | PIPE IN THIS AREA. |
| | 5. SHEET 6, PLEASE SHOW THE INVERTS |
| | N=13.5 AND S=13.5 FOR STRUCTURES D-OUT3 |
| | AND D-OUT2 RESPECTIVELY. |
| | 6. SHEET 10, OUTFALL STRUCTURE DETAIL, |
| | PLEASE VERIFY EL. 14.5 TOP OR BOTTOM OF |
| | THE DETENTIONS. |
| | 7. NOTE THAT A BACKFLOW PREVENTER FOR |
| | THE PROPOSED LIFT SATION IS REQUIRED, |
| | SHOULD BE SHOWN ON SHEETS 7 AND 15. |
| | 8. SHEET 7, PLEASE VERIFY 2" WS |
| | CONNECTION FOR THE TOWNHOUSE "A" |
| | 9 PLEASE NOTE THAT CIVIL PLANS MUST BE |
| | APPROVED BY THE PUBLIC UTILITIES AND |
| | ENGINEERING FOR ALL THE CONNECTIONS TO |
| | THE CITY SERVICES PRIOR TO GETTING |
| | APPROVAL FROM THE CONSTRUCTION SERVICES |
| | DEPT. |
| | IF ANY QUESTION PLEASE CONTACT 805-6723 |
| | MOHAMMAD R. AMINI |