Plan Review Notes
Plan Review Notes For Permit 05080676
Permit Number 05080676
Review Stop E
Sequence Number 1
Notes
Date Text
2005-09-11 00:00:00IN ELECTRIC FOR REVIEW.
 REVIEWS IN PROGRESS .
 ********** UNSAT ************
  
 SAIL CLUB
 TOWNHOUSE(CONDO) BLDG #7
  
 1)NOTE: PLEASESEE BLDG REVIEW COMMENTS
 ETC AS THIS BUILDING IS NOT A FEE SIMPLE
 "TOWNHOUSE" . PLEASE SEE THE ELECTRICAL
 SERVICES ARE SET UP FOR EACH UNIT TO
 CONTAIN AN INDIVIDUAL SERVICE FROM FPL.
 PLEASE SEE THIS BLDG IS A
 MULTI-FAMILY/CONDO UNIT AND WILL REQUIRE
 ONE ELECTRICAL SERVICE WITH ALL METERS
 AND MAINS CONTAINED IN ONE LOCATION.
 230.70,230.72.
 PLEASE SEE IF THESE DO BECOME "FEE
 SIMPLE" TOWNHOUSE UNITS, PLEASE INDICATE
 DISCONNECTS AS SHOWN ON RISER, ON PLANS
 NEXT TO METERS.
 IT IS ALSO THE UNDERSTANDING FROM
 ZONING, MR JOHN ROACH, A RE-PLAT WOULD
 BE REQUIRED IF UNITS GO TO "FEE SIMPLE"
 TOWNHOUSE UNITS.
  
 2)NOTE: PLEASE COMPLETE CIRCUITING ON
 PLANS FOR ALL UNITS AND CORRELATE WITH
 PANEL SCHEDULES.
 PLEASE SEE IF EVERY UNIT IS IDENTICAL, A
 TYPICAL UNIT LAYOUT MAY BE USED.
 (SOME ARE NOT THE SAME).
  
 3)NOTE: PLEASE SEE PLANS REFERENCE THE
 1999 NEC. PLEASE SEE AS OF JULY 7TH,2003
 THE STATE ADOPTED THE 2002 NEC.
  
 4)NOTE: PLEASE SEE 210.52D WHICH
 REQUIRES THE BATH RM GFI RECEPT TO BE
 LOCATED WITHIN 3' OF SINK/LAV EDGE.
 CROSSING OVER ONE SINK TO THE OTHER IS
 NOT PERMITTED. PLEASE ADD AN ADDITIONAL
 GFI RECEPT OR MOVE THE ONE SHOWN TO THE
 CENTER OF BOTH.
 PLEASE ALSO SEE BATH CIRCUIT IS ALOS
 INDICATED AS BEING ARC FAULT?
 THIS IS ONLY A NOTE.
  
 5)NOTE: PLEASE SEE DINING RM RECEPTS MAY
 BE ON ONE OR MORE OF THE SAMLL
 APPLICANCE CIRCUITS, HOWEVER THEY MAY
 NOT SHARE WITH OTHER LOCATIONS. PLEASE
 SEE THESE ARE ALSO SHOWN TO LIVING RM.
 210.52B, 210.11C1
 PLEASE SEE THIS IS ALSO SHOWN ON ARC
 FAULT PROTECTED CIRCUIT? THIS IS OK, AND
 ONLY A NOTE.
  
 6)NOTE: PLEASE SEE 210.52F, 210.11C2,
 220.16WHICH REQUIRES THE MIN OF 1500
 VA FOR THE LAUNDRY/WASHER CIRCUIT.
 (1.2 SHOWN).
  
 7)NOTE: PLEASE SEE PANEL INDICATES "A"
 AND "C" PHASES? PLEASE CLARIFY AS
 SERVICE IS SHOWN AS SINGLE PHASE. A&B)
  
 8)NOTE: PLEASE SEE CIRCUIT 19 ALONG
 KITCHEN COUNTERSPACE IS SHOWN AS A
 DEDICATED RECEPT FOR MICROWAVE(GFI), IF
 THIS INDEED A DEDICATED RECEPT, PLEASE
 SEE 210.52C1 WHICH WOULD REQUIRE AND
 ADDITIONAL GFI RECEPT TO SERVE KITCHEN
 COUNTERSPACE.
  
 9)NOTE: PLEASE ALSO SEE REDLINED PLANS
 FOR ADDITIONAL MISSING KITCHEN
 COUNTERSPACE RECEPTS MISSING PER
 210.52C1, USEING SCALE ON PLANS AS
 SHOWN.
  
 10)NOTE: PLEASE SEE REDLINED PLANS FOR
 SOME MISSING RECEPTS PER 210.52
 PLEASE SEE WALL SPACE AT STAIRS, WALL
 SPACE IN "E" UNIT.
  
 11)NOTE: PLEASE CLARIFY AND ADJUST OCP
 SHOWN FOR RANGE. PANEL SCHEDULE
 INDICATES A 70A 2P BRKR FOR WHAT WOULD
 BE A 50A RECEPT FOR RANGE.
 PLEASE SEE 406.2B, 210.21B3,4
  
 PLEASE SEE DUE TO THE COMMENTS IN NOTE
 #1 AND THE CHANGES IN ELECTRICAL
 SERVICE, REVIEW FOR MAIN ELECTRICAL
 SERVICE SHALL BE DONE UNDER NEXT REVIEW.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ****************************************
 PLEASE COMPLETELY REMOVE ALL OLD/ VOIDED
  
 SHEET FROM SETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STMAPING.
 ONE COPY OF ALL OLD/VOIDED SHEETS SHOULD
 BE ATTACHED TO EACH OTHER TO COMPOSE OF
 ONE SET OF VOIDED SHEETS ONLY AND WILL
 BE SUBMITTED ALONG WITH NEW SETS FOR
 REFERENCE.
 **************************************
  
 PLEASE SEE BLDG REVIEW COMMENTS WITH
 RESPECT TO PRODUCT NOA'S ATTACHED TO
 PLANS.
 PLEASE ALSO SEE COMMENTS WITH REPECT TO
 PRODUCT APPROVALS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved