| Date |
Text |
| 2005-09-11 00:00:00 | IN ELECTRIC FOR REVIEW. |
| | REVIEWS IN PROGRESS . |
| | ********** UNSAT ************ |
| | |
| | SAIL CLUB |
| | TOWNHOUSE(CONDO) BLDG #7 |
| | |
| | 1)NOTE: PLEASESEE BLDG REVIEW COMMENTS |
| | ETC AS THIS BUILDING IS NOT A FEE SIMPLE |
| | "TOWNHOUSE" . PLEASE SEE THE ELECTRICAL |
| | SERVICES ARE SET UP FOR EACH UNIT TO |
| | CONTAIN AN INDIVIDUAL SERVICE FROM FPL. |
| | PLEASE SEE THIS BLDG IS A |
| | MULTI-FAMILY/CONDO UNIT AND WILL REQUIRE |
| | ONE ELECTRICAL SERVICE WITH ALL METERS |
| | AND MAINS CONTAINED IN ONE LOCATION. |
| | 230.70,230.72. |
| | PLEASE SEE IF THESE DO BECOME "FEE |
| | SIMPLE" TOWNHOUSE UNITS, PLEASE INDICATE |
| | DISCONNECTS AS SHOWN ON RISER, ON PLANS |
| | NEXT TO METERS. |
| | IT IS ALSO THE UNDERSTANDING FROM |
| | ZONING, MR JOHN ROACH, A RE-PLAT WOULD |
| | BE REQUIRED IF UNITS GO TO "FEE SIMPLE" |
| | TOWNHOUSE UNITS. |
| | |
| | 2)NOTE: PLEASE COMPLETE CIRCUITING ON |
| | PLANS FOR ALL UNITS AND CORRELATE WITH |
| | PANEL SCHEDULES. |
| | PLEASE SEE IF EVERY UNIT IS IDENTICAL, A |
| | TYPICAL UNIT LAYOUT MAY BE USED. |
| | (SOME ARE NOT THE SAME). |
| | |
| | 3)NOTE: PLEASE SEE PLANS REFERENCE THE |
| | 1999 NEC. PLEASE SEE AS OF JULY 7TH,2003 |
| | THE STATE ADOPTED THE 2002 NEC. |
| | |
| | 4)NOTE: PLEASE SEE 210.52D WHICH |
| | REQUIRES THE BATH RM GFI RECEPT TO BE |
| | LOCATED WITHIN 3' OF SINK/LAV EDGE. |
| | CROSSING OVER ONE SINK TO THE OTHER IS |
| | NOT PERMITTED. PLEASE ADD AN ADDITIONAL |
| | GFI RECEPT OR MOVE THE ONE SHOWN TO THE |
| | CENTER OF BOTH. |
| | PLEASE ALSO SEE BATH CIRCUIT IS ALOS |
| | INDICATED AS BEING ARC FAULT? |
| | THIS IS ONLY A NOTE. |
| | |
| | 5)NOTE: PLEASE SEE DINING RM RECEPTS MAY |
| | BE ON ONE OR MORE OF THE SAMLL |
| | APPLICANCE CIRCUITS, HOWEVER THEY MAY |
| | NOT SHARE WITH OTHER LOCATIONS. PLEASE |
| | SEE THESE ARE ALSO SHOWN TO LIVING RM. |
| | 210.52B, 210.11C1 |
| | PLEASE SEE THIS IS ALSO SHOWN ON ARC |
| | FAULT PROTECTED CIRCUIT? THIS IS OK, AND |
| | ONLY A NOTE. |
| | |
| | 6)NOTE: PLEASE SEE 210.52F, 210.11C2, |
| | 220.16WHICH REQUIRES THE MIN OF 1500 |
| | VA FOR THE LAUNDRY/WASHER CIRCUIT. |
| | (1.2 SHOWN). |
| | |
| | 7)NOTE: PLEASE SEE PANEL INDICATES "A" |
| | AND "C" PHASES? PLEASE CLARIFY AS |
| | SERVICE IS SHOWN AS SINGLE PHASE. A&B) |
| | |
| | 8)NOTE: PLEASE SEE CIRCUIT 19 ALONG |
| | KITCHEN COUNTERSPACE IS SHOWN AS A |
| | DEDICATED RECEPT FOR MICROWAVE(GFI), IF |
| | THIS INDEED A DEDICATED RECEPT, PLEASE |
| | SEE 210.52C1 WHICH WOULD REQUIRE AND |
| | ADDITIONAL GFI RECEPT TO SERVE KITCHEN |
| | COUNTERSPACE. |
| | |
| | 9)NOTE: PLEASE ALSO SEE REDLINED PLANS |
| | FOR ADDITIONAL MISSING KITCHEN |
| | COUNTERSPACE RECEPTS MISSING PER |
| | 210.52C1, USEING SCALE ON PLANS AS |
| | SHOWN. |
| | |
| | 10)NOTE: PLEASE SEE REDLINED PLANS FOR |
| | SOME MISSING RECEPTS PER 210.52 |
| | PLEASE SEE WALL SPACE AT STAIRS, WALL |
| | SPACE IN "E" UNIT. |
| | |
| | 11)NOTE: PLEASE CLARIFY AND ADJUST OCP |
| | SHOWN FOR RANGE. PANEL SCHEDULE |
| | INDICATES A 70A 2P BRKR FOR WHAT WOULD |
| | BE A 50A RECEPT FOR RANGE. |
| | PLEASE SEE 406.2B, 210.21B3,4 |
| | |
| | PLEASE SEE DUE TO THE COMMENTS IN NOTE |
| | #1 AND THE CHANGES IN ELECTRICAL |
| | SERVICE, REVIEW FOR MAIN ELECTRICAL |
| | SERVICE SHALL BE DONE UNDER NEXT REVIEW. |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | **************************************** |
| | PLEASE COMPLETELY REMOVE ALL OLD/ VOIDED |
| | |
| | SHEET FROM SETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STMAPING. |
| | ONE COPY OF ALL OLD/VOIDED SHEETS SHOULD |
| | BE ATTACHED TO EACH OTHER TO COMPOSE OF |
| | ONE SET OF VOIDED SHEETS ONLY AND WILL |
| | BE SUBMITTED ALONG WITH NEW SETS FOR |
| | REFERENCE. |
| | ************************************** |
| | |
| | PLEASE SEE BLDG REVIEW COMMENTS WITH |
| | RESPECT TO PRODUCT NOA'S ATTACHED TO |
| | PLANS. |
| | PLEASE ALSO SEE COMMENTS WITH REPECT TO |
| | PRODUCT APPROVALS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |