Plan Review Notes
Plan Review Notes For Permit 05080676
Permit Number 05080676
Review Stop B
Sequence Number 1
Notes
Date Text
2005-10-05 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05080676
 ADD: 719 EXECUTIVE CENTER DR
 (TOWNHOUSE #7)
 CONT: THE WEITZ CO.
 TEL: (561)686-5511
 CELL:(954)675-4302
  
 ARCHITECT: ACI ARCHITECRTURALGROUP
 PAUL M. TWITTY
 TEL:(561)832-5599
 STRUC ENGINEER: ONM&J
 PHILLIP RIZZO
 TEL:(561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE
 ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) 105.8* PROVIDE NOC RECORDED WITH THE
 CLERK OF COURT BEFORE A PERMIT CAN BE
 ISSUED.
  
 3A)109.3.7*THIS PARTICUAL TYPE OF
 BUILDING WILL REQUIRE A SPECIAL
 INSPECTOR, FOR THE MID RISE AND HIGH
 RISE A THRESHOLD INSPECTOR SHALL BE
 REQUIRED, WILL THIS BE THE SAME PERSON
 OR WILL THERE BE TWO INDIVIDUALS?
 FORMS WILL NEED TO BE FILLED OUT FOR THE
 SPECIAL INSPECTOR, CONTACT HAROLD
 PISKURA, INSPECTION SERVICES MANAGER @
 (561)805-6711 TO SEET UP AN APPOINTMENT.
 3B) SINCE THERE WILL BE A ON SITE
 INSPECTOR (3)
  
  
 4) 106.3.3* PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 SHALL BE REVIEWED AND APPROVED IN
 WRITTING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR " JURISDICTIONAL
 APPROVAL", (LOCAL PRODUCT APPROVAL).
  
 5) SITE PLAN NEEDS TO BE SUBMITTED TO
 ADDRESSING PERSONEL JOHN HIGGINS FOR
 ADDRESSING AS WELL AS NEW PLAT MAP FOR
 THE COMBINATION OF LOTS. JOHN HIGGINS
 CONTACT NUMBER IS (561)822-1239.
  
 6) THE TERM TOWNHOUSE TO DESCRIBE THIS
 TYPE OF BUILDING RAISES CONCERNS:
 6A) THE DEFINITION USED UNDER THE 2004
 FL BLDG CODE IS LOCATED UNDER 705.4.1.1.
 WHICH REQUIRES ZERO CLEARENCE FROM
 PROPERTY LINES. REMOVE THIS TERM FROM
 ALL DOCUMENTS SUBMITTED FOR PERMITTING.
  
 6B) THERE IS A DISCREPANCY IN THE PLANS
 SINCE THE BOUNDRY SURVEY FOR PARCEL# 7,
 ONLY INDICATES 2 LOTS PARCEL 1&2. FOR
 TOWNHOUSES EACH UNIT WILL REQUIRE
 INDIVIDUAL PROPERTY CONTROL NUMBERS
 WITH ASSOCIATED PROPERTY LINE.
 6C) THE SURVEY DOES SHOW 2 SEPERATE LOTS
 WHICH APPEAR TO CUT THROUGH BULDING "B"
 AND BUILDING "C". A UNITY OF TITLE SHALL
 BE REQUIRED, TABLE 601 AND 602.
 6D) THERE IS ANOTHER DISCREPANCY IN HOW
 THE BUILDINGS ARE DESCIBED. PLANS
 INDICATE BUILDINGS A-G, WHEEEREAS THE
 APPLICATION DESCIPTION IS
 "TOWNHOUSE # 7".
  
 7) ENERGY COMPLIANCE FORMS:
 7A) REMOVE THE WORDING "TOWNHOMES"
 7B) UPDATE FORM TO FORM 600A-04
 7C) LINE# 3 CORRECT FROM SINGLE FAMILY
 TO MULTI-FAMILY
 7D) CHECK THE CLIMATE ZONE BOX FOR PALM
 BEACH COUNTY.
  
 8) GEOTECHNICAL REPORT THAT WORK WAS
 PREFORMED BY ARDAMAN NEEDS TO BE AN
 ORIGINAL WITH SIGNATURE AND RAISED SEAL.
 PLANS, SPECIFICATIONS,REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 9A) SHEET A5.1.2 WALL SECTIONS DO NOT
 INDICATE WHAT TYPE OF TERMITE TREATMENT
 FOR SOILS WILL BE USED, SEE 1816.1.
 9B) THIS SAME SHEET INDICATES THE USE OF
 A VAPOR BARRIER, MUST BE A MINIMUM OF 6
 MIL TO BE USED WITH CHEMICALLY TREATED
 TERMITE TREATMENT FOR SOILS BENEATH
 SLAB.1806.1.4.
 9C) 1816.1.6 IF SOIL TREATMENT IS USED
 FOR SUBTERRANEAN TERMITE PREVENTION,
 CHEMICAL SOIL TREATMENT SHALL BE APPLIED
 UNDER ALL EXTERIOR CONCRETE OR GRADE
 WITHIN 1 FT OF THE PRIMARY STRUCTURE
 SIDEWALLS.
  
 10) SHEET A6.1.1:
 10A) THE WALL SECTIONS DO NOT INDICATE
 COMPLIANCE WITH ATTIC VENTILATION
 REQUIREMENTS FOUND IN 1203.2.
 PLEASE INDICATE COMPLIANCE.
 10B) THE DETAILS LISTED 1-3 ARE VARIOUS
 CUT SECTIONS THROUGH THE ROOF
 SHEATHING, IN THE 3 DETAILS THE
 PLANS REVEAL 2 TYPES OF MATERIALS
 TO BE INSTALLED AND 3 THICKNESSES.
 PLEASE CORRECT ALL DETAILS TO THE
 SAME MATERIAL & THICKNESS.
 10C) WHERE THE DETAIL #1 ABOVE DECLARED
 USING A HIGH DENSITY 1/2"
 SUBSTRATE. TABLE 2304.7(5) FOOTNOTE
 (D) LIMITS THE USE OF ROOF
 SHEATHING TO 19/32" WOOD STRUCTURAL
 PANELS IN WIND REGIONS OF 110 -
 140MPH, EXPOSURE B.
 10D) DETAILS 8&9 INDICATE THE USE IT
 APPEARS TO BE A TYPE-O "AND" THE
 SOFFIT DETAILS APEAR TO HAVE (2)
 LAYERS OF COMPLETE INSTALLATION,
 THE AND MAYBE SHOULD HAVE BEEN A
 "OR".(2004 FBC) 106.1.1*
 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE & EXTENT OF THE
 WORK PROPOSED & SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND REVELENT LAWS,
 ORDINANCES, AND RULES AND
 REGULATIONS AS DETERMINED BY THE
 BUILDING OFFICIAL.
 10E) DETAIL# 6 EXT WALL AND FLOOR TRUSS
 MISSING THE FIRESTOPPING SEPERATING
 VERTICAL & HORIZONTAL AREAS.717.2.3
 DETAIL# 11 MISSING FIRE STOPPING AT
 TOP OF WALL TO ROOF TRUSSES.
 10F) DETAIL # 17 INDICATES THE USE OF
 A MUD DOWN ROOF TILE SYSTEM. PROVIDE
 A FL STATE APPROVAL COVERSHEET WITH
 THE ASSOCIATED NOA REPORT. ALSO
 PROVIDE THE TYPE OF UNDERLAYMENT TO
 BE USSED.
  
 11) SHEET A4.1.1:
 11A) PLANS DO NOT REFLECT THE
 REQUIREMENTS FOR DRAFTSTOPPING, SEE
 SECTIONS: 717.3.2 FOR FLOOR/ CEILING
 ASSEMBLIES & 717.4 FOR IN ATTICS.
 NOTE THE SLEEPING UNIT SEPERATION.
 11B) MISSING INFORMATION ON THE ATTIC
 ACCESS REQUIEMENTS 1209.2.
  
 12A)SHEET A4.1.1 TH-7 THE SECOND FLOOR
 BEDROOM# 2 WINDOWS LABELED "D" ARE
  
 EMERGENCY EGRESS WINDOWS REQUIRING
 5.7 SQ FT CLEAR OPENING OF VENT
 OPENING 1025.2.
 121B) THE WINDOW WIDTHS AND HEIGHTS ON
 THE A4.1.1 DO NOT MATCH THE WINDOW
 HEIGHTS LISTED IN THE NOA SUBMITTED.
 12C) A4.1.1 NOR A4.2.1. DO NOT INDICATE
 THE USEOF LARGE MISSLE TESTED
 GLAZING IN THE WINDOWS OR DOORS.
 12D) NOTE FOR THE 3 BEDROOM UNIT THE
 EGRESS WINDOWS CURRENTLY WORK BUT
 WHEN THEY ARE RESIZED TO THE
 MANUFACTURERS SIZES THEY MAY NOT
 MAKE THE 5.7 SQ FT.1
  
 13) P2.1.1 CONDENSATE DRAINS:
 1503.6 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 14A) S-1.7 SLAB ON GRADE PROVIDE NOTE
 FOR: FL BLDG 1911.2(EXEPTION# 2)
 CONCRETE SLABS ON GRADE CONTAINING
 6X6/ W1.4XW1.4 WELDED WIRE
 REINFORCEMENT FABRIC LOCATED IN THE
 MIDDLE TO THE UPPER 1/3RD OF THE SLAB
 SHALL BE SUP- PORTED BY APPROVED
 MATERIALS OR SUPPORTS AT SPACING NOT
 TO EXCEED 3 FT OR IN ACCORDANCE WITH
 MANUFACTURER'S SPEC.
 14B) THE 2ND FLOOR FRAMING PLAN LOOKS AS
  
 IF THERE IS A COLUMN IN EACH OF THE
 UNITS BUT THERE IS NO DESIGNATION?
  
 15A) S-2 ROOF/ WIND LOAD SCHEDULE, THE
 DIAGRAPMS INDICATE A GABLE ROOF WITH
 0-10 DEGREES, ALTHOUGH THE SCHEDULE
 IS FOR 10-30 DEGREES, DELETE THE
 DIAGRAPM THAT WILL NOT BE USED IN THE
  
 ROOF SCHEDULE.
 15B) S-2 ROOF/ WIND LOAD SCHEDULE;
 NOTE# 1 CHANGE TO 2004 FL BLDG CODE.
  
 16) S-2 TYPICAL WOOD BUCK DETAIL NOTE
 INDICATES 2001 FL BLDG CODE, CORRECT.
  
 17A) S-2 TRUSS ANCHOR "E" LOAD TO BE
 REDUCED TO 11,150.
 17B) FASTENERS "K& L" INDICATE SEE
 DETAIL THIS SHEET, WHERE?
  
 18) S-4.7 PROVIDE EXPLANATION AS TO WHY
 THE INTERIOR ZONE CONTINUES TO WITHIN
 1'-6" OF THE CORNERS? SEE REAR AND SIDE
 ELEVATIONS, WHAT HAPPENED TO THE END
 ZONES? SEE 1609.6.3, ALSO FIGURE 1606.6B
 SEE WIND DIRECTION RANGE (A) AND (2A).
  
 19) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
  
 20) PRODUCT APPROVALS SUBMITED ARE ONLY
 ONE SET, THE APPROVALS SUBMITTED HAVE
 REPORTS FOR BOTH LARGE AND REPORTS FOR
 SMALL MISSLE IMPACT GLAZING. GLAZED
 OPENINGS ZERO -30 FT REQUIRE LARGE
 MISSLE IMPACT GLAZING, OR SHUTTERS.
 SINCE THIS IS CONDOS AND A LARGE PROJECT
 IF SHUTTERS ARE TO BE USED APPROVAL FROM
 THE BUILDING OFFIICAL WILL BE REQUIRED.
 SEE THE BUILDING OFFICIALS
 INTERPRETATION OF CODE. SEE QUESTION 13
 & 14 OF INTERPRETATION OF STANDARDS.
 ****************************
 (13) RECOGNIZING SUCH CONCERNS AS
 ABSENTEE OWNERS, OR CASES WHERE LONGER
 TIME & EFFORT IS NECESSARY TO SECURE
 SHUTTERS ON LARGE OR MULTI-STORY
 BUILDINGS, WHAT MEASURES ARE BEING
 RECOMMENDED OR IMPLEMENTED TO ENSURE
 THAT COMPLETE INSTALLATION OR SECURING
 IS DONE SUFFICIENTLY IN ADVANCE OF THE
 HURRICANE EVENT?
 (13) ANSWER: IN MATTERS CONCERNING
 PUBLIC SAFETY, HEALTH, AND THE GENERAL
 WELFARE NOT SPECIFICALLY ADDRESSED IN
 THE CODE SECTION 104.1* FLORIDA BUILDING
 CODE, 2004 EDITION, PROVIDES THE ABILITY
 FOR THE BUILDING OFFICIAL TO IMPLEMENT
 REQUIREMENTS FOR ENSURING STABILITY,
 STRENGTH, AND PROPER OPERATION OF
 EXISTING & NEW BUILDINGS.
 IN ORDER TO ASSURE THE SECURING OF
 SHUTTERS ON LARGE OR MULTI-STORY
 BUILDING, OR MULTIPLE BUILDINGS ON THE
 SAME PROPERTY, PRE-STORM PREPARATION
 PLANS MUST BE SUBMITTED BY THE PROPERTY
 OWNERS OR MANAGING AGENTS FOR REVIEW BY
 THE CONSTRUCTION SERVICES DEPARTMENT.
 ANY SUCH PLAN SHALL INCLUDE, AT A
 MINIMUM, ON-SITE LOCATION OF SHUTTERS,
 PARTY RESPONSIBLE FOR SECURING THE
 SHUTTERS (SAID PARTIES MUST BE LOCATED
 WITHIN PALM BEACH COUNTY), TOTAL NUMBER
 OF OPENINGS TO BE PROTECTED AND TOTAL
 TIME REQUIRED TO SECURE ALL OPENINGS.
 PROTECTION OF OPENINGS SHALL BE
 ACCOMPLISHED WITHIN TWELVE (12) HOURS OR
 LESS OF THE OFFICIAL NOTIFICATION BY THE
 NATIONAL WEATHER SERVICE OF A HURRICANE
 WATCH.
 PROVISIONS IN THE BUILDING CODES
 (AND THIS STANDARD) ARE NOT INTENDED TO
 PROHIBIT THE USE OF ALTERNATIVE
 MATERIALS AND METHODS, AND ALLOW THE
 BUILDING OFFICIAL TO REVIEW AND APPROVE
 ANY ALTERNATE DEEMED EQUIVALENT IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE
 RESISTANCE, DURABILITY AND SAFETY
 PRESCRIBED BY CODE. BASED UPON THIS CODE
 PROVISION, ACCEPTANCE OF ALTERNATE
 MATERIALS AND METHODS MAY BE APPROVED ON
 A CASE-BY-CASE BASIS AND SHALL REQUIRE
 SUFFICIENT EVIDENCE OR PROOF TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING
 THE ALTERNATE.
  
 (14)ARE REMOVABLE STORM PANELS
 APPROPRIATE FOR USE ON VERY LARGE, MID
 OR HIGH-RISE STRUCTURES?
 (14) ANSWERS: NO, EXCEPT ON THE
 GROUND FLOOR. ON COMMERCIAL AND
 MULTI-UNIT RESIDENTIAL STRUCTURES, ABOVE
 THE FIRST LEVEL, IMPACT RESISTANT
 GLAZING OR PERMANENTLY AFFIXED
 PROTECTIVE DEVICES SHALL BE INSTALLED.
 PERMANENTLY AFFIXED PROTECTIVE DEVICES
 SHALL REQUIRE THE WRITTEN APPROVAL OF
 THE BUILDING OFFICIAL.
 **************************
  
  
 21) FL BLD CODE 1609.6.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A)FRONT ENTRY DOOR
 B) LOUVER DOOR
 C) TRUSS ANCHORS
 D) STORM SHUTTERS
 E) ROOFING ASSEMBLIES
  
 22) THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
 _X__ WRONG REPORT.
 _X__ CONTRACTOR DID NOT PROVIDE THE MEAN
 ROOF HEIGHT.
 _X__ CONTRACTOR DID NOT INDICATE THE
 ROOF PITCH.
 _X__ TYPE OF UNDERLAYMENT TO BE USED.
 _X__ TYPE OF TILE TO BE USED.
 _X__ TYPE OF FASTENING SYSTEM.
 _X__ REPORT SUBMITTED TO SMALL TO READ.
  
 23) BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO.,THE PERMIT PLANS STAMPED BY
 THEM AND THE RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026