Plan Review Notes
Plan Review Notes For Permit 05080675
Permit Number 05080675
Review Stop P
Sequence Number 2
Notes
Date Text
2006-05-12 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
  
 1. ALL PLANS DESIGNED BY A PROFESSIONAL
 ARCHITECT OR ENGINEER, THEN ALL SHEETS
 SHALL BE SIGNED, SEALED & DATED AS
 REQUIRED BY FS. SECTION 106.1.
 ***RESPONSE NOTED, BUT SEE BOUNDRY
 SURVEY, SHTS PP1 OF 9 THRU PP9 OF 9,
 SHTS LA-POOL-1 THRU LA-POOL-4, AND SHTS
 LA-FW-1 THRU LA-FW-6.
  
 2. INFORMATIONAL ONLY.
  
 3. SHT T-4 A2.4.1 SUBMIT CALCULATIONS
 FOR PRIMARY AND SECONDARY ROOF DRAINS.
 SHOW THE SQUARE FOOTAGE FOR EACH AREA &
 SHOW 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS ALONG WITH THE AREA
 OF ROOF THAT DRAINS ONTO THE ROOF FROM
 ABOVE FOR EACH AREA IN CALCLATIONS.
 SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS.
 ***RESPONSE NOTED, BUT THE AREAS FROM
 ROOFS ABOVE HAVE NOT BEEN ADDRESSED FOR
 THE MECHANICAL RM ROOF, THE HIP ROOFS,
 THE OCTAGON ROOF, OR THE STAIRWELL ROOF.
  
 4. SHTS T-4 A4.1.1 THRU T-4 A4.1.10
 UNITS A, B, C, D, E, H, F, G & K SHALL
 COMPLY WITH REQUIREMENTS 1 THRU 7 OF THE
 FHA-98 DESIGN MANUAL. INDICATE
 SPECIFICATION "A" OR "B" FOR EACH UNIT.
 SHOW THE W/C OPENING, (MINIMUM 33"),
 SHOW THE W/C AT 18" OFF THE WALL TO THE
 CENTER OF THE FIXTURE WHERE APPLICABLE,
 AND 18" MINIMUM OFF AN ADJACENT FIXTURE.
 SEE PAGES 6.7 7.43 & 7.44. - SHOW CLEAR
 FLOOR SPACE FOR ALL USABLE FIXTURES. -
 SUBMIT A DETAIL FOR BACKING FOR W/C'S,
 TUBS, SHOWERS ECT. PER REQUIREMENT 6. -
 CLEAR FLOOR SPACE FOR SHOWERS SHALL BE
 PARALLEL TO SHOWER & FLUSH WITH CONTROL
 WALL. INDICATE CONTROL WALL ON UNIT
 FLOOR PLAN. (SEE PAGE 7.56).
 ***NO RESPONSE FROM ARCHITECT, NOT
 ADDRESSED.
  
 5. SHT T-4 A4.1.11 MEN'S & WOMEN'S
 TOILET ROOMS SHALL COMPLY WITH SECTIONS
 11-4.16, 11-4.19 & 11-4.22 WITH ALL
 SUBSECTIONS. SUBMIT A DETAIL SHOWING
 COMPLIANCE.
 ***NO RESPONSE FROM THE ARCHITECT, NOT
 ADDRESSED.
  
 6. SUBMIT CALCULATIONS FOR ALL
 AMENITITES AREAS FOR MINIMUM FACILITIES
 PER TABLES 1004.2 (BLDG) AND 403.1
 (PLMG). SHOW THE SQUARE FOOTAGE FOR ALL
 COMMON USE AREAS ALONG WITH THE
 OCCUPANCY LOAD OF EACH AREA. INDICATE
 THE LOCATION OF THE SANITARY FACILITIES
 FOR THE POOL AREA.
 ***NO RESPONSE FROM THE ARCHITECT, NOT
 ADDRESSED.
  
 7. SHT T-4 A7.1.1 FLOORS AND WALLS IN
 TOILET ROOM SHALL BE NONABSORBENT PER
 SECTIONS 1210.1 & 1210.2. PLEASE
 INDICATE HOW THIS WILL BE ACCOMPLISHED
 WITH EXPOSED CONCRETE, GYP. BOARD AND NO
 BASE AS SHOWN IN GROUND LEVEL ROOM
 FINISH SCHEDULE.
 ***NO RESPONSE FROM THE ARCHITECT, NOT
 ADDRESSED.
  
 8. SHT T-4 A4.11 SINK IN CATERING
 KITCHEN SHALL COMPLY WITH SECTION
 11-4.24 AND ALL SUBSECTIONS. PROVIDE A
 DETAIL.
 ***NO RESPONSE FROM THE ARCHITECT, NOT
 ADDRESSED.
  
 9. SHT T-4 A6.1.1 DETAIL #4 TRASH CHUTE
 WATER SUPPLY SHALL HAVE BACKFLOW
 PROTECTION. INDICATE THE METHOD OF
 BACKFLOW PROTECTION REQUIRED IN SECTION
 608 AND TABLE 608.1.
 ***RESPONSE NOTED, BUT NO BACKFLOW
 SHOWN.
  
 10. SHT T-4 A6.1.3 DETAIL #10 ROOF DRAIN
 DETAIL, INDICATE MEASUREMENT FROM THE
 ROOF TO THE TOP OF THE SECONDARY ROOF
 DRAIN PIPI, (EMERGENCY OVERFLOW PIPE).
 ***NO RESPONSE FROM THE ARCHITECT, NOT
 ADDRESSED.
  
 11. SHT T-4 A8.1.1 SHOW THE BACKING FOR
 THE W/C'S PER FHA DESIGN MANUAL PAGES
 6.3 & 6.4. SHOW BACKING FOR THE TUBS PER
 PAGE 6.9.
 ***NO RESPONSE FROM THE ARCHITECT, NOT
 ADDRESSED.
  
 12. SHT P0.1 PLUMBING NOTES #1 & #24
 REFER TO FBC-2001, CODE ADOPTED FOR THIS
 JOB IS FBC-2004. PLEASE CHANGE REFERENCE
 ***RESPONSED NOTED, BUT PLUMBING NOTE
 #24 HAS NOT BEEN CHANGED.
  
 14. SHT P2.1 MANY FITTINGS CONNECTING
 BRANCH LINES TO BLDG. SANT. DRAIN ARE
 NOT SHOWN TO GUIDE SEWAGE AND WASTE IN
 THE DIRECTION OF FLOW. SECTION 706.3. -
 IDENTIFY THE RISER BETWEEN ROOMS B110 &
 B110.
 ***RESPONSE NOTED, BUT THIS HAS NOT BEEN
 ADDRESSED.
  
 16. SHT P2.4 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS. (SEE
 COMMENT #3).
 ***RESPONSE NOTED, BUT SEE COMMENT #3
 FOR REQUIREMENTS FOR ROOFS THAT DRAIN
 ONTO ROOF FROM ABOVE.
  
 18. SHT P3.3 2ND SHEET WITH 2ND, 4TH -
 12TH FLOORS. NO 3RD FLOOR SUBMITTED.
 PLEASE CLARIFY.
 ***RESPONSE NOTED, BUT NO CHANGE SEEN.
  
 21. SHTS P5.1 & P5.2 SUBMIT SOVENT
 DESIGN MANUAL FOR THE SOVENT SYSTEM. THE
 SOVENT SYSTEM SHALL BE APPROVED. SECTION
 106.1.1.
 ***RESPONSE NOTED, BUT THIS SYSTEM IS
 NOT APPROVED. NO TESTING AND APPROVAL OF
 FITTINGS.
  
 22. SHT P5.3 BLDG DRAIN ISOMETRIC RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN.
 THE ISOMETRIC IS REVERSE FROM THE FLOOR
 PLAN. THE BLDG. DRAIN IS SHOWN AS
 EXITING THE BLDG. BETWEEN S/1 & S/2 ON
 THE FLOOR PLAN. SHOW ALL GROUND FLOOR
 FIXTURE PIPING ON THE ISOMETRIC WITH ALL
 PIPE SIZES AND VENTING. SECTION
 104.3.1.1.
 ***RESPONSE NOTED, BUT THE RISER DIAGRAM
 STILL DOES NOT REFLECT THE FLOOR PLAN IN
 MANY AREAS. CHECK ALL PIPE SIZES AGAINST
 TABLE 710.1(1). - FLOOR DRAINS MISSING,
 UNIDENTIFIED FIXTURE DOWNSTREAM OF RISER
 S/63 NOT SHOWN. (SEE RED LINE
 CORRECTIONS ON ONE SET OF PLUMBING
 SHEETS).
  
 23. SHT P5.3 SHOW DFU'S AS THEY
 ACCUMULATE IN THE SYSTEM. TABLE 710.1(1)
 ***RESPONSE NOTED, BUT SOME FIXTURES
 MISSING AND ADDITION DOWNSTREAM OF RISER
 S/49 NEEDS TO BE RECHECKED. FLOOR DRAINS
 PER TABLE 709.2.
  
 27. THE FOLLOWING INFORMATION REQUIRED
 FOR THE GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. CUT SECTIONS NOT SHOWN
 AND MOST RISERS NOT SHOWN.
 ***RESPONSE NOTED, BUT LENGTHS OF CUT
 SECTIONS NOT SHOWN.
  
 C. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 ***RESPONSE NOTED, BUT CALCULATIONS FOR
 CLOTHES DRYER ROOMS NOT SUBMITTED.
  
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ***RESPONSE NOTED, BUT NO MANUF. SHEETS
 SUBMITTED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 ***RESPONSE NOTED, BUT VOIDED SHEETS NOT
 REMOVED.
  
 **************NEW COMMENTS**************
  
 1B. SHTS T-4 A8.1.2 THRU T-4 A8.1.8
 SHOWN ON THE INDEX OF DRAWINGS HAVE NOT
 BEEN SUBMITTED. PLEASE CLARIFY. SECTION
 106.1.1.
  
 2B. SHTS P2.4 & P7.1 STORM RISERS 6 & 10
 SF DOES NOT REFLECT SF ON ROOF PLAN NOR
 ON BLDG. STORM DRAIN ISOMETRIC. PLEASE
 CORRELATE RISERS WITH ROOF PLANS AND
 STORM DRAIN ISOMETRIC. SECTION 106.1.1.
  
 3B. SHTS P5.1 & P5.2 BASE OF STACKS DO
 NOT REFLECT REQUIREMENTS OF SOVENT
 DESIGN MANUAL. FIRST FLOOR FIXTURES DO
 NOT CONNECT TO VERTICLE STACK UNDER THE
 DEAERATOR REQUIREMENT FOR THE PRL LINE
 IS NOT CORRECT.
  
 4B. SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL & FS 553.80(2)(B).
  
 REVIEW BY KEN STEVENS