| Plan Review Notes For Permit 05080675 |
| Permit Number |
05080675 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-06-13 00:00:00 | ***DENIED*** | | | | | | PLEASE NOTE THAT ARCHITECTUAL RESPONSE | | | LETTER WAS NOT FOUND WITH THIS | | | SUBMITTAL. THE FOLLOWING ADDRESSES | | | RESPONSE LETTER FROM KAMM CONSULTING. | | | | | | 1) OK | | | | | | 2) NOTE IS STILL ON PLANS. PLEASE | | | CORRECT OR REMOVE. | | | | | | 3) PLEASE INDICATE THE TOTAL BUILDING | | | COVEREAGE THAT IS EXPECTED BY A 1000 GPM | | | FIRE PUMP. | | | | | | 4) OK | | | | | | 5-15) NO ARCHITECT'S RESPONSE LETTER | | | FOUND. | | | | | | 16) OK | | | | | | 17) OK | | | | | | 18) OK | | | | | | 19) OK | | | | | | 20) NO MENTION OF LOCK AND CHAIN IN | | | ADDITION TO TAMPER SWITCHES. | | | | | | 21) HYDRAULIC CALCULATIONS WILL BE | | | REQUIRED AT THE TIME OF FIRE SPRINKLER | | | PERMITTING. | | | | | | 22) OK | | | | | | 23) OK | | | | | | 24) OK | | | | | | 25) OK | | | | | | 26) NO MENTION REGARDING SURVIVABILITY | | | REQUIREMENT ON FA0.1. | | | | | | 27) PLEASE NOTE THAT A HIGHRISE BUILDING | | | WITH ENCLOSED STAIRWELLS IS REQUIRED TO | | | HAVE STAIRWELL PRESSURIZATION. | | | | | | 28) NO RESPONSE LETTER. | | | | | | 31-36) NO RESPONSE LETTER FOUND. | | | | | | PLEASE NOTE THAT IT WOULD HELP EXPEDITE | | | THIS PROCESS IF RESPONSE LETTERS | | | INDICATING SHEET #'S ARE INCLUDED WITH | | | SUBMITTALS. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|