Plan Review Notes
Plan Review Notes For Permit 05080675
Permit Number 05080675
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2006-06-13 00:00:00***DENIED***
  
 PLEASE NOTE THAT ARCHITECTUAL RESPONSE
 LETTER WAS NOT FOUND WITH THIS
 SUBMITTAL. THE FOLLOWING ADDRESSES
 RESPONSE LETTER FROM KAMM CONSULTING.
  
 1) OK
  
 2) NOTE IS STILL ON PLANS. PLEASE
 CORRECT OR REMOVE.
  
 3) PLEASE INDICATE THE TOTAL BUILDING
 COVEREAGE THAT IS EXPECTED BY A 1000 GPM
 FIRE PUMP.
  
 4) OK
  
 5-15) NO ARCHITECT'S RESPONSE LETTER
 FOUND.
  
 16) OK
  
 17) OK
  
 18) OK
  
 19) OK
  
 20) NO MENTION OF LOCK AND CHAIN IN
 ADDITION TO TAMPER SWITCHES.
  
 21) HYDRAULIC CALCULATIONS WILL BE
 REQUIRED AT THE TIME OF FIRE SPRINKLER
 PERMITTING.
  
 22) OK
  
 23) OK
  
 24) OK
  
 25) OK
  
 26) NO MENTION REGARDING SURVIVABILITY
 REQUIREMENT ON FA0.1.
  
 27) PLEASE NOTE THAT A HIGHRISE BUILDING
 WITH ENCLOSED STAIRWELLS IS REQUIRED TO
 HAVE STAIRWELL PRESSURIZATION.
  
 28) NO RESPONSE LETTER.
  
 31-36) NO RESPONSE LETTER FOUND.
  
 PLEASE NOTE THAT IT WOULD HELP EXPEDITE
 THIS PROCESS IF RESPONSE LETTERS
 INDICATING SHEET #'S ARE INCLUDED WITH
 SUBMITTALS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  