Plan Review Notes
Plan Review Notes For Permit 05080675
Permit Number 05080675
Review Stop E
Sequence Number 2
Notes
Date Text
2006-05-01 00:00:00************ UNSAT 2ND REVIEW *********
  
 ** PLEASE SEE NOTES FROM PREVIOUS REVIEW
 WHICH NEED TO BE ADDRESSED AND SOME NEW
 NOTES DUE TO CHANGES IN PLANS.
  
 ** PLEASE SEE NOTE BELOW ARE TAKEN
 DIRECTLY FROMPREVIOUS REVIEW AND ARE
 SO NOTED.
  
 **************************************
 PLEASE SEE NOTES AT THE END OF COMMENTS
 WITH RESPECT TO REMOVAL OF ALL
 OLD/VOIDED SHEETS.
 **************************************
  
  
 SAIL CLUB TOWER #4
  
  
  
  
 1)NOTE:NOTE #1 NO, PLEASE SEE PLANS
 STILL REFLECT AND NOTE THE 1999 NEC.
 PLEASE ALSO SEE REVISED ELECTRICAL PLANS
 ARE REQUIRED TO REFLECT THE CODES AND
 YEARS IN EFFECT FOR DESIGN.
  
 ** PREVIOUS NOTE **
 PLEASE SEE CODE REFERENCED ON PLANS LIST
 THE 1999 NEC. PLEASE KNOW, AS OF JULY
 1ST 2003, THE STATE ADOPTED THE 2002
 NEC.
 PLEASE ALSO SEE WE ARE UNDER THE 2003
 NFPA-101 AND 2002 NFPA-72
 PLEASE ADJUST.
  
 2)NOTE: NOTE #2, OK, HOWEVER PLEASE SEE
 ANYBLDG, FIRE REVIEW COMMENTS AS THEY
 MAY AFFECT DESIGN. PLEASE SEE NEW
 COMMENTS DUE TO CHNAGES AT FPL VAULT
 LOCATION.
  
 3)NOTE: NOTE #3 NO, PLEASE SEE AREAS
 WHERE SOME CIRCUTING IS STILL MISSING.
  
 ** PREVIOUS NOTE**
 PLEASE SHOW ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE SUBMITTED PANEL
 SCHEDULES.
 PLEASE SEE SOME AREAS WHICH ELECTRICAL
 FIXTURES SEEM TO BE MISSINGTHIS.
 PLEASE ALSO SEE CIRCUITING FOR UNITS.
 PLEASE KNOW, A "TYPICAL" UNIT LAYOUT MAY
 BE PROVIDED, HOWEVER A LAYOUT WOULD BE
 REQUIRED FOR EACH UNIT TYPE, INCLUDING
 STUDIO UNIT.
 CIRCUITING FOR SOME UNITS/ITEMS CAN NOT
 BE VERIFIED AT THIS TIME.
  
 4)NOTE: NOTE #4 NO, PLEASE SEE REPSONSE
 LETTER MENTIOSN TO SEE E 3.1, HOWEVER
 PLEASE SEETHIS SHEET ONLY SHOWS ONE
 AREA OF FIRST FLR COMMON AREA.
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE PHOTO-METRICS FOR
 STAIR TOWERS ON NORMAL PWR AND STAND-BY.
 ALONG WITH WALK AREAS.
 PLEASE SEE STAIR TOWERS UNDER NORMAL PWR
 SHALL MEET A MIN OF 10FT CANDLES. PLEASE
 SEE ARES FOR HALLS ETC ARE PERMITTED TO
 BE LESS. .
 PLEASE SEE NFPA-101 7.8.1.3,7.9.2.1
  
 5)NOTE: NOTE #5 NO, PLEASE KNOW, A
 BATTERY BACK UP FIXTURE OF SOME SORT
 WILL BE REQUIRED IN STAIR TOWERS AT A
 MIN OF EVERY OTHER LEVEL.
  
 ** PREVIOUS NOTE **
 PLEASE KNOW, BATTERY BACK FIXTURES WILL
 BE REQUIRED AT EVERY OTHER LEVEL(MIN).
 PLEASE SEE LS 101 WHICH MENTIONS THE
 TRIPPING/THROW OF A SINGLE BRKR SAHLL
 NOT LEAVE ANY EGRESS AREA IN TOTAL
 DARKNESS. PLEASE CALL ELECTRICAL PLAN
 REVIEW AND FIRE MARSHALS OFFICE TO GO
 OVER OPTIONS PERMITTED.
 A BATTERY BACK-UP FIXTURE AT EVERY OTHER
 LEVEL WILL SATISFY FIRE MARSHAL'S OFFICE
 AND AHJ.
 PLEASE BE SURE TO MEET THE MIN OF 1
 FT/CANDLE UNDER EM.
 PLEASE BE SURE TO SEE PREVIOUS NOTE #4
 FOR LIGHTING LEVELS.(MIN)
  
 6)NOTE: NOTE#6 NO, PLEASE SEE MOST
 FIXTURES WERE ADDED TO THESE ROOMS,
 HOWEVER PLEASE SEE ELEVATOR MACHINE ROOM
 WHICH WILL REQUIRE ARE BATTERY BACK
 FIXTURE OF SOME SORT.
 IT WAS NOTED, THAT LTS ARE ON EM
 CIRCUIT, HOWEVER A BATTERY BACK UP
 FIXTURE WILL BE REQUIRED.
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE BATTERY BACK-UP
 FIXTURES IN MAIN ELECTRICAL RMS AND
 ELEVATOR ROOM(S), GENERATOR AND FIRE
 PUMP ROOM. PLEASE ALSO PROVIDE
 CIRCUITING FOR THESE
 RMS.
  
 7)NOTE: NOTE #7 NO, RESPONSE MENITONS TO
 SEE E 5.1, HOWEVER NO DETAIL WAS SHOWN
 ON PLANS.
 PLEASE ALSO KNOW DETAILSHALL INCLUDE
 CURBING ALL FOUR SIDES.
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE CURB DETAIL FOR
 BUS-DUCT RISER AND FLOOR PENATRATIONS.
 368.6
  
 8)NOTE: NOTE #8, OK, HOWEVER PLEASE
 CONTINUE WITH NOTE FOR ALL MIN
 CLEARENCES PER 110.26 SHALL BE MET.
 NOTE FOR PANIC HARDWARE WAS ADDED WHICH
 WAS OK.
 NOTE WAS NOT ADDED FOR ALL.
  
 ** PREVIOUS NOTE **
 PLEASSE PROVIDE NOTE ON RISER AND
 ELECTRICAL ROOM SHEETS FOR REQUIREMENTS
 FOR 110.26 FOR PANIC HARDWARE AND DOOR
 SWINGS. PLEASE SEE MIN CLEARENCE PER
 110.26
 PLEASE ALSO SEE MIN DOOR OPENING 6' WITH
 SINGLE ACCESS FOR EQUIPMENT MORE THAN
 1200A'S AND OVER 6' WIDE.
  
  
 9)NOTE:NOTE # 9, OK, CHANGED TO
 FEEDERS FROM BUS-DUCT, HOWEVER PLEASE
 SEE NEW COMMENTS FOR VAULT AND FOR
 SIZING OF SEC'S.
  
 ** PREVIOUS NOTE **
 PLEASE SEE RISER INDICATES ALL
 BUS-DUCT FROM FPL VAULT TO MAIN
 ELECTRICAL ROOM AS OVER-HEAD. PLEASE SEE
 230.70, 230.6, NO MORE THAN 8' OF
 UNPROTECTED CONDUCTORS/ OR BUS DUCT
 PERMITTED "INSIDE THE BLDG.
 PLEASE SEE ROUTING OF BUS-DUCT APPEARS
 TO SHOW INSTALLATION INSIDE CONDO
 UNITS??
 PLEASE PROVIDE LAYOUT, REVISE TO
 UNDER-GROUND FEEDERS OR OTHER ACCEPTABLE
 MEANS.
  
 10)NOTE: NOTE #10, NO, ?? PLEASE SEE
 PLANS INDICATE THIS AS HAVING A 3-POLE
 MAIN, HOWEVER THERE IS NO INDICATION OF
 THE MANUAL MENAS OF DISCONNECT, LOCATED
 ON THE OUTSIDE. RESPONSE MENTIONS THIS
 WAS ADDRESSED IN A PREVIOUS REVISION,
 HOWEVER WE HAVE NOT SEEN ANY OTHER
 REVSIONS BEFORE THIS SUBMITTIAL. PLEASE
 SEE NEW NOTES FOR MAIN AS NOTED ON RISER
 "KEY NOTES"".
  
 ** PREVIOUS NOTES **
 PLEASE PROVIDE INFORMATION ON
 BUS -DUCT RISER MAINS. APPEARS TO SHOW
 THESE AS "SHUNT-TRIP" AND NOT CONTAINING
 A MANUAL MEANS OF DISCONNECT LOCATED ON
 THE OUTSIDE OF THE EQUIPMENT. PLEASE SEE
 MAIN PANEL SCHEDULE(S), THESE DO NOT
 SEEM TO INDICATE A MCB.
 230.76,230.79
  
 11)NOTE: NOTE #11, OK, HOWEVER SEE NOTES
 UNDER GARAGE PERMIT FOR ROOMS.
 PLEASE ALSO PROVIDE MIN LAYUOUT , AS
 THESE CAN BE REFERENCED UNDER A SEPARATE
 PERMIT. PLEASE SEE RESPONSE MENTIONS TO
 SEE REVISED 4.1, HOWEVER ONLY THE GEN RM
 SHOWS SOME SORT OF ELECTRICAL. PLEASE
 SEE MIN FT CNADLE FOR GEN RM SHAL BE 30
 FT CANDLES, WHICH IS NOTED UNDER GARAGE
 PERMIT.
 PLEASE ALSO KNOW, THESE AREAS WHERE THE
 GARAGE IS LOCATED SHALL BE 100% COMPLETE
 AND A CO MUST BE OBTAINED BEFORE
 ISSUANCE OF ANY TCO OR CO FOR TOWER
 BUILDINGS. THIS IS ONLY ANOTE AT THIS
 TIME TO HELP WITH THE PHASING OF THE
 PROJECT.
  
 ** PREVIOUS NOTE **
 PLEASE SEE GARAGE PLANS FOR FIRE PUMP
 RM AND GEN RM ARE SHOWN BLANK?
  
 12)NOTE: NOTE #12 NO, PLEASE SEE
 REPSONSE MENTIONS TO SEE E5.2, HOWEVER
 E5.2 DOES NOT REVISE INFORMATION ON
 BUS-DUCT? PLEASE CORRELATE WITH NOTES ON
 E0.1 AS NOTES SEEM TO CHNAGE ALL
 BUS-DUCT TO COPPER.
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE SPECIFIC INFORMATION ON
 BUS-DUCT, PLEASE SEE AN ALUM EQUIPMENT
 GROUNDING CONDUCTOR/ MATERIAL IS NOT
 PERMITED.
 310.2. LOCAL AMENDMENTS.
  
 13)NOTE: NOTE #13 NO, RESPONSE MENTIONS
 FOR CONTRACTOR TO SUBMIT, HOWEVER THIS
 WAS NOT DONE.
  
 ** PREVIOUS NOTE **
 PLEASE SUBMIT ALL MANUFACTURE SPECS AND
 CUT SHEETS FOR GENERATOR, ATS,
 FIRE PUMP AND FIRE PUMP CONTROLLER.
 PLEASE ALSO SUBMIT THE SAME FOR ANYSUB
 BASE FUEL TANK.
 PLEASE KNOW, DUE TO THE INFORMATION NOT
 BEING SUBMITTED AT THIS TIME, REVIEW FOR
 SOME ITEMS FOR CODE COMPLIANCE CAN NOT
 BE DONE.
 UNABLE TO VERIFY CODE COMPLIANCE FOR
 MANY ITEMS UNDER NFPA, 20,70,101,110
 ETC.
 SOME INFORMATION IS "APECIFIED" ON PLANS
 FOR TOWER #4, HOWEVER, TOWER #3 SHOULD
 REFLECT THE SAME INFORMATION. ALL
 MANUFACTURE CUTS/SPECS ARE STILL
 REQUIRED.
  
 14)NOTE:NOTE # 14 NO, SAME NOTE.
 RESPONSE MENTIONS TO SEE REVISED,
 HOWEVER COULD NOT LOCATE INFORMATION
 NEEDED.
  
 ** PREVIOUS NOTE **
 PLEASE SEE ELECTRICAL RISER DIAGRAM DOES
 CONTAININFORMATION FOR FIRE PUMP, YET
 NOT FIRE PUMP CONTROLLER,
 SERVICE, SIZING, LOCKED ROTOR SETTINGS
 ETC.
 PLEASE COMPLETE.
 ENCASEMENT IN CONCRETE, OUTSIDE THE
 BLDGS, ETC
  
 15)NOTE: NOTE #15 OK,SEE NOTE MENTIONED
 ABOVE.
  
 16)NOTE: NOTE #16, OK, HOWEVER PLEASE
 SEE NEW COMMENT FOR H12A.
  
 ** PREVIOUS NOTE **
 PLEASE SEE A PANEL SCHEDULE FOR A PANEL
 H12B IS SUBMITTED, HOWEVER THIS PANEL
 COULD NOT BE LOCATED ON RISER
 DIAGRAM??
 PLEASE CORRELATE.
  
 17)NOTE: NOTE #17 YES AND NO, PLEASE SEE
 THE FIRST PART OF THE NOTE REQUESTED A
 TYPICAL DISCONNECT DETAIL WHICH WAS
 DONE, HOWEVER PLEASE SEE HEAT FOR AHU'S
 FOR UNITS STILL DO NOT COORELATE. PLEASE
 ALSO SEE NOTE #41
  
 ** PREVIOUS NOTE **
 PART 2)
 PLEASE CORRELATE ALL A/C KW RATINGS AND
 LOADS WITH MECHANICAL PLANS. (KW RATINGS
 ETC. )
  
  
 18)NOTE:NOTE #18 NO, PLEASE RESPONSE
 MENTIONS TO SEEE5.1 FOR REVISED PLANS,
 HOWEVER 5.1DID NOT SHOW THIS? PLEASE
 SEE A ROOM LAYOUT ON3.1 WAS LOCATED,
 HOWEVER DID NOT SEEM TO CONTAIN ALL
 REQUIRED EQUIPMENT, PANELS ETC.
  
 ** PREVIOUS NOTE **
 PLEASE SEE FIRE REVIEW NOTES
 ALSO: PLEASE PROVIDE A LAYOUT FOR
 CENTRAL STATION RM(FIRE COMMAND RM)
 SHOWING ALL DEVICES/ PANELS/ STATUS
 PANELS ETC.
 PLEASE LIST ALL ITEMS AS SPECIFIED IN
 NFPA- 101 11.8.5,
  
 19)NOTE: PLEASE SEE MOST WERE CORRECTED,
 ONLY ONE OR TWO WERE MISSING OR LOCATED
 NOT TO SPACING, THESE CAN BE REDLINED ,
 HOWEVER IF REDLINES ARE VIEWED, PLEASE
 SEE POSSIBLE AREAS.
  
 ** PREVIOUS NOTE **
 PLEASE SEE RECEPTS MISSING PER
 210.52
 SEE REDLINED PLANS.
  
 20)NOTE:NOTE #20 OK.
  
 21)NOTE:NOTE #21 OK.
  
 22)NOTE: NOTE #22 NO, COULD NOT LOCATE
 NOTE. RESPONSE MENTIONS E0.1
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE NOTE ON PLANS FOR SMOKE
 DETECTOR PLACEMENT PER REQUIREMENTS NFPA
 -72 11.8.3.5.
  
 23) NOTE: NOTE #23 OK.:
  
 24) NOTE: NOTE #24 OK.
  
 25)NOTE: NOTE #25 OK, HOWEVER PLEASE SEE
 NEW NOTE. (MINOR CHANGE NEED FOR PANEL
 SCHEDULE.
  
 ** PREVIOUS NOTE **
 PLEASE SEE A 70A BRKR IS BEING SHOWN FOR
 RANGE?? PLEASE SEE 210.23,422.11B
 50A RANGE RECEPT, 50A BRKR MAX.
  
 26)NOTE: PLEASE SEE PANEL SCHEDULES SEEM
 TO SHOW "A" AND "C" PHASE FOR SINLGLE
 PHASE SERVICE AND UNITS??
 PLEASE CLARIFY / ADJSUT.
 215.5
  
 27)NOTE: NOTE #27 NO, PLEASE SEE MANY
 AREAS SHWON AS LIVING RM AND CIRCUITED
 FOR SMALL APPLIANCE. PLEASE SEE AREAS
 SEEM TO HAVE IDENTIFICATION SWITCHED.
  
 ** PREVIOUS NOTE **
 PLEASE LABEL AND /OR CLARIFY "DINING"
 AREAS IN ALL UNITS.
 UNABLE TO VERIFY CIRCUITING AS DINING
 /LIVING ARE SEEMED TO BE COMBINED.'
 PLEASE SEE 210.52B1
  
 28)NOTE:OK.
  
 29)NOTE: NOTE #29, NO, PLEASE SEE
 REDLINED PLANS AS SOME AREAS FOR HALLWAY
 WALLS.
  
 ** PREVIOUS NOTE **
 PLEASE SEE MISSING RECEPTS IN HALLWAY
 AREAS, 10' OR MORE OF CONTINUOUS
 WALL. 210.52H.
  
 30)NOTE: NOTE #30 NO, ? PLEASE SEE
 REPSONSE MENTIONS TO SEE REVISED 5.1,
 HOWEVER NO CHANGES COULD BE LOCATED TO
 PLANS.
 PLEASE ALSO SEE NO PANEL SCHEDULE ETC
 WAS SUBMITTED.?
  
 ** PREVIOUS NOTE **
 PLEASE SEE RISER SEEMS TO INDICATE A
 POOL PANEL, HOWEVER NO OTHER
 INFORMATION WAS SUBMITTED AND PANEL
 COULD NOT LOCATED ON PLANS.
 LOADS ETC.
 215.5, 220
  
 31)NOTE: OK, AS NOTED.
  
 32)NOTE: NOTE #32 NO, AS IT SEEMS NOTE
 WAS NOT COMPLETE. PLEASE SEE RESPONSE
 MENTIONS "LIGHTNING PROTECTION NOT
 REQUIRED", THIS IS TRUE AND NOTE WAS NOT
 TO REQUEST A LPS.
 PLEASE PLACE A NOTE ON "ROOF PLANS"
 WHICH STATES "ANY LIGHTNING PROTECTION
 SYSTEM INSTALLE SHALL MEET NFPA-780 AND
 SHALL BE UNDER A SEPARATE PERMIT."
 OR WORDS TO THAT AFFECT.
 SOMEHOW THE NOTE WAS NOT PRINTED AS
 TYPED?
  
 ** PREVIOUS NOTE **
 PLEASE PLACE NOTE ON "ROOF PLANS" WHICH
 WILL REQUIRE ALL LIGHTNING PROTECTION
  
  
 33)NOTE:OK.
  
 34)NOTE: OK.
  
 35)NOTE: OK.
  
 36) NOTE:OK
  
 37)NOTE: OK, HOWEVER SEE NEW NOTE.
  
 38)NOTE: OK.
  
 39)NOTE: NOTE: NO, PLEASE SEE RESPONSE
 MENTIONS TO SEE RISER E5.1? THIS COMMENT
 IS FOR JOBSITE SPEC BOOKS.
  
 ** PREVIOUS NOTE **
 PLEASE SUBMIT "SPEC BOOKS' FOR REVIEW OF
 PROJECT.
 THESE WOULD CONTAIN JOBSITE SPECS.
  
 40)NOTE:OK.
  
 41)NOTE:NOTE #41 NO, PLEASE SEE
 MECHNICAL PLANS AS NOTED ABOVE FOR KW
 RATINGS INDICATED.
 PLEASE SEE THIS COMMENT WAS FOR UNITS
 AND SOME IN HOUSE AREAS.
 YES, THE OCP WAS SHOWN CORRECT AT 125%
 ON ELECTRICAL PANEL SCHEDULE FOR THE KW
 HEAT WHICH WAS SHOWN. PLEASE KNOW, THE
 COMMENT WAS BASED ON KW AS INDICATED ON
 MECHANICAL PLANS AND NOTE #17.
  
 ** PREVIOUS NOTE **
 PLEASE SEE MIN OCP FOR AHU HEAT
 TO BE 125%. 424.3B
 SHOWS 50A OCP.
  
 42)NOTE: OK.
  
  
 ***************************************
 *************** NEW NOTES *************
  
 1) NOTE: PLEASE SEE "KEY NOTE" #8 WHICH
 NOW MENTIONS A 3000A MCB FOR BUS RISER
 "ML", HOWEVER SEC'S ARE ONLY RATED FOR
 2520A'S. PLEASE SEE 240.4C FOR DEVICES
 RATED OVER 800A'S.
 PLEASE ALSO CORRELATE AS BUS-DUCT RISER
 IS ONLY RATED @ 2500A'S.
 240.4,310.16 ETC.
 215.5
  
 2) NOTE: PLEASE SEE H12A, PLANS NOW SHOW
 H12B BEING FED FROM THIS, PLEASE
 INDICATE IF "FEED THRU LUGS" OR IF OCP
 AND FEEDERS ARE BEING INSTALLED.
 215.5
  
 3) NOTE: PLEASE INDICATE ON PANEL
 SCHEDULE ALL APPLIANCES AS GAS WHERE
 APPLICABLE. "GAS RNAGE", GAS WH" ETC.
  
 4) NOTE: PLEASE SEE A GORUNDING NOTE #19
 ON RISER AT GENERATOR MENTIONS TO SEE
 KEY NOTE FOR THIS, HOWEVER #19 ON KEY
 NOTES IS BLANK?
  
 5) NOTE: PLEASE SEE 7.1 AS THIS SEEM TO
 CONTAIN A "MISPRINT" FOR THE ATS IN THE
 MAIN ELECTRICAL ROOM. THIS IS SHOWN AS
 ATS-3, HOWEVER THIS IS TOWER #4.
  
 6) NOTE: PLEASE OBTAIN A LETTER OF
 APPROVAL FROM FPL ( MR. BILL HARTIGAN
 FOR APPROVAL AND CHANGE OF FPL VAULT AS
 SHOWN.
 PLEASE ALSO SEE NOTES FOR TOWER #3 FOR A
 SIMILAR COMMENT.
  
  
  
 ** PLEASE KNOW, MANY OF THE ABOVE ITEMS
 ARE "REDLINED" AT LOCATIONS ON PLANS FOR
 NOTES.
  
 ** PLEASE KNOW, A RESPONSE LETTER IN
 TYPE WRITTEN FORM WILL HELP IN RESPONSES
 TO ELECTRICAL COMMENTS.
  
 ** PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 ************************************
  
 ** PLEASE KNOW IT WAS REQUESTED ON
 PREVIOUS REVIEW BEFORE RESUBMITTING
 PLANS FOR ALL OLD/VOIDED SHEETS TO BE
 COMPLETELY REMOVED FROM SETS. PLEASE SEE
 THIS WAS NOT DONE AND ALL NEW SHEETS
 WERE INSERTED INTO NEW SETS. PLEASE
 KNOW, WE ONLY REQUIRE "ONE" COPY OF THE
 OLD REMOVED SHEETS. THESE SHOULD BE
 BUNDLED INTOONE SET AND SUBMITTED
 ALONG WITH THE THREE NEW REVISED SETS.
 PLEASE KNOW, THIS WILL EFFECT THE PLAN
 REVIEW PROCESS AND HELP TO EXPEDITE
 PROJECT.
  
 ***********************************
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
2006-04-28 00:00:00REVIEW IN PROGRESS.
2006-04-27 00:00:00IN ELEC FOR REVIEW.
 REVIEW TO CONTINUE ON 4/28