2005-11-17 00:00:00DENIED:2004 FBC / TOWER 4
 1.PLANS SHEET M0.1, MECHANICAL NOTES
 REFERENCE 2001 FBC & STANDARDS THAT ARE
 APPLICABLE TO THIS SUBMITTAL.PLEASE
 REVISE.
  
 2.PLAN SHEET M2.1 DETAIL SECTION A-A,
 PLEASE ANNOTATE SUFFICIENT CLEARANCE FOR
 MAINTENANCE, SERVICE, & REPLACEMENT TO
 ALL EQUIPMENT INDCLUDING FIRE DAMPERS IS
 REQUIRED PER 2004 FMC 306.1.
  
 3.PLAN SHEET M2.1 KEY NOTE 11 'PROVIDE
 ACCESS PANELD FOR AHU.SEE ARCH PANELS
 FOR DETAILS.'THIS IS INDICATED IN THE
 MASTER BEDRM IN UNIT J104.PLEASE
 CLARIFY AHU LOCATION & WHAT AREA IT
 SERVES.PLEASE NOTE, ACCESS TO
 EQUIPMENT FOR THE COMMON AREAS SHALL NOT
 BE OBTAINED BY ENETERING A PRIVATE
 RESIDENCE.
  
 4.PLAN SHEET M2.1 EXHAUST DUCT FROM
 UNIT J THAT PENETRATES THE TENENANT
 SEPARATION WALL TO THE FITNESS CENTER &
 HOME THEATER AREAS SHALL COMPLY WITH
 2004 FMC 501.4, 504.2 & 603.3, FOR
 REQUIRED GAUGE OF GALVANIZED DUCT
 PENTETRATING RATED WALL/PARTITION.
  
 5.PLAN SHEET M2.2 DETAIL 1 DOES NOT
 INDICATE AUXILIARY DRAIN PAN.EQUIPMENT
 SCHEDULE (M6.1) INDICATES AUXILIARY
 DRAIN PAN W/FLOAT SWITCH.
  
 6.PLEASE NOTE THE AHU DETAIL 1 ON PLAN
 SHEET M2.2 INDICATES NO CEILING IN THE
 AHU CLOSET & THE DOOR IS TO HAVE
 'GASKET, SEALED'.PLAN SHEET M7.1
 DETAIL #2 (AHU) INDICATES R/A THROUGH
 LOUVERED DOOR, & NO DRAIN PAN.PLEASE
 CORRELATE PLANS.
  
 7.PLAN SHEET M2.2 DETAIL 2 SHOWS
 LAYOUT ABOVE THE CEILING.PLEASE NOTE
 DUCT SHALL HAVE ENOUGH CLEARANCE FOR
 ASSEMBLY, INSPECTION , CLEANING &
 MAINTENANCE PER 2004 FMC 603.1 &
 603.1.3.
  
 8.PLEASE PROVIDE COMBUSTION AIR
 CALCULATIONS (IF A CONFINED SPACE) FOR
 THE GAS DRYERS LOCATED IN THE LAUNDRY
 ROOM/CLOSET.2004 FMC CHAPTER 7.
  
 9.PLAN SHEET M2.5 KEY NOTE #4 'SEE
 ARCHITECTURAL PLANS FOR ACCESS TO UNDER
 FLOOR AREA.PLEASE CLARIFY THE
 ARCHITECTURAL PLAN SHEET THAT DETAILS
 THE ACCESS.
  
 10.PLAN SHEET M6.2 REFERENCES ASHRAE
 62-89, THIS SHOULD READ 62-01.
  
 11.PLAN SHEET M6.2 OUTSIDE AIR
 CALCULATIONS ARE GIVEN FOR COMMON AREAS
 ONLY.PLEASE PROVIDE CALCULATIONS FOR
 THE RESIDENT UNITS PER TABLE 403.3 AS
 REQUIRED FOR R-2 OCCUPANCIES.
  
 12.PLUMBING PLAN SHEET P6.4 INDICATES
 GAS APPLICANCES, SPECIFICALLY THE WATER
 HEATER.PLEASE CLARIFY VENTING A GAS
 WATER HEATER LOCATED IN AN AHU CLOSET.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  
  
  