Plan Review Notes
Plan Review Notes For Permit 05080675
Permit Number 05080675
Review Stop G
Sequence Number 1
Notes
Date Text
2006-05-12 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 FROM PLUMBING REVIEW:
  
 27. THE FOLLOWING INFORMATION REQUIRED
 FOR THE GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. CUT SECTIONS NOT SHOWN
 AND MOST RISERS NOT SHOWN.
 ***RESPONSE NOTED, BUT LENGTHS OF CUT
 SECTIONS NOT SHOWN.
  
 C. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 ***RESPONSE NOTED, BUT CALCULATIONS FOR
 CLOTHES DRYER ROOMS NOT SUBMITTED.
  
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ***RESPONSE NOTED, BUT NO MANUF. SHEETS
 SUBMITTED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 ***RESPONSE NOTED, BUT VOIDED SHEETS NOT
 REMOVED.
  