| 2005-12-01 00:00:00 | ******DENIED****** |
| | |
| | TOWER #4 |
| | |
| | 1) FIRE HYDRANTS TO BE WET AND |
| | OPERATIONAL PRIOR TO, DURING AND AFTER |
| | CONSTRUCTION |
| | |
| | 2) FOR REFERENCE, HIGHRISE IS DEFINED AS |
| | A BUILDING GREATER THAN 75' IN HEIGHT. |
| | SHT A-1.1.2 |
| | |
| | 3) PLEASE NOTE THAT THE FIRE PUMP IS |
| | SHOWN IN THE PARKING GARAGE THAT ISN'T |
| | PART OF THIS PHASE. ADDITIONAL |
| | INFORMATION REGARDING WHAT ARRANGEMENT |
| | BY THIS OFFICE HAS BEEN ACCEPTED IS |
| | REQUIRED. THE FIRE PUMP SHALL BE A |
| | MINIMUM OF 1250 GPM FOR A HIGHRISE |
| | BUILDING. PLEASE CONTACT THE BUREAU OF |
| | FIRE PREVENTION AT (561) 804-4724. |
| | |
| | 4) BUILDING TO MEET APPLICABLE BUILDING |
| | CODES AND NFPA CHAPTER 11 REQUIREMENTS |
| | FOR HIGHRISE BUILDINGS. |
| | |
| | 5) PLEASE VERIFY THAT NO COOKING WILL |
| | OCCUR IN THE CATERING KITCHEN. |
| | |
| | 6) EXIT STAIRS ARE TO BE KEPT UP WITH |
| | CONSTRUCTION. |
| | |
| | 7) NOTE REGARDING THE ADDRESS NUMBER IS |
| | ACKNOWLEDGED. PLEASE ILLUSTRATE ON |
| | ELEVATION SHEETS FOR FUTURE REFERENCE |
| | AND FURTHER PLAN REVIEW. |
| | |
| | 8) PLEASE PROVIDE PRESCRIPTIVE STRENGTH |
| | REQUIREMENT FOR HANDRAILS AND GUARDS |
| | |
| | 9) KNOX BOXES WILL BE REQUIRED. |
| | |
| | 10) PLEASE INDICATE THE OCCUPANT LOAD |
| | CALCULATIONS FOR THE HOME THEATER AND |
| | FITTNESS CENTER. |
| | |
| | 11) PLEASE PROVIDE THE INTERIOR FINISH |
| | CLASSIFICATION FOR WALLS AND CEILINGS IE |
| | CLASS A,B OR C. |
| | |
| | 12) TACTILE SIGNAGE IS REQUIRED AT EXIT |
| | DOORS. |
| | |
| | 13) PLEASE INDICATE IF ELEVATORS ARE |
| | STRETCHER ACCESSIBLE. |
| | |
| | 14) SIGNS ARE REQUIRED IN STAIRWELLS |
| | INDICATING TOP, BOTTOM, FLOOR NUMBER AND |
| | ROOF ACCESS. |
| | |
| | 15) WARNING SIGNS ARE REQUIRED IN |
| | ELEVATOR LOBBIES. |
| | |
| | 16) IN ACCORDANCE WITH LOCAL |
| | REQUIREMENTS, DUCT SMOKE DETECTORS SHALL |
| | INITIATE A GENERAL FIRE ALARM WHEN |
| | ACTIVATED. |
| | |
| | 17) FIRE ALARM SYSTEM TO BE CLASS A, |
| | STYLE D OR FULLY ADDRESSABLE. |
| | |
| | 18) AS INDICATED ON PLANS, SEPARATE SHOP |
| | DRAWINGS AND PERMITS ARE REQUIRED FOR |
| | FIRE SPRINKLER AND FIRE ALARM SYSTEMS. |
| | |
| | 19) UL CERTIFICATION TO BE PROVIDED AT |
| | THE TIME OF THE FIRE ALARM ACCEPTANCE |
| | TEST. |
| | |
| | 20) IN ADDITION TO ELECTRONIC SWITCHES, |
| | DOUBLE CHECK DETECTOR ASSEMBLY TO BE |
| | SECURED WITH LOCK AND CHAIN. |
| | |
| | 21) HYDRAULIC CALCULATIONS WILL BE |
| | REQUIRED WHEN APPLYING FOR THE FIRE |
| | SPRINKLER PERMIT. |
| | |
| | 22) FDV ON STANDPIPE SHALL BE 2 1/2" TO |
| | 1 1/2" REDUCER WITH CHAIN. |
| | |
| | 23) TEMPORARY STANDPIPES ARE REQUIRED |
| | WHEN THE BUILDING REACHED 3 STORIES OR |
| | 30" IN HEIGHT. |
| | |
| | 24) NO FIRE SPRINKLER COVERAGE NOTED TO |
| | COVERED WALKWAYS AND PORTE COCHERE. |
| | |
| | 25) PLANS DON'T SHOW ANY EXIT SIGNS OR |
| | EMERGENCY LIGHTING FACILITIES IN COMMON |
| | AREA MEANS OF EGRESS. PLEASE SHOW ON |
| | ELECRICAL AND LIFE SAFETY SHTS. |
| | |
| | 26) FIRE ALARM SYSTEM TO MEET THE |
| | SURVIVABILITY REQUIREMENTS IN ACCORDANCE |
| | WITH NFPA 72. |
| | |
| | 27) THE ANTICIPATED STACK EFFECT NOTE |
| | WORDING SHALL BE ADDED TO THE MECHANICAL |
| | SHTS. |
| | |
| | 28) CONSTRUCTION, ALTERATION AND |
| | DEMOLITION TO COMPLY WITH NFPA 241. |
| | |
| | 29) ELEVATORS TO COMPLY WITH BUILDING |
| | AND FIRE CODES AND ASME/ANSI A 17.1. |
| | |
| | 30) FIRE SPRINKLER COVERAGE DOESN'T |
| | EXTEND TO ELEC/PHONE ROOMS. |
| | |
| | 31) NO CUTTING OR WELDING TO OCCUR |
| | WITHOUT APPROVAL OF FIRE PREVENTION |
| | BUREAU AND COMPLIANCE WITH NFPA 51B. |
| | |
| | 32) EMERGENCY LIGHTING IS NOT SHOWN IN |
| | ELEC/PHONE ROOMS ON UPPER FLOORS. |
| | |
| | 33) A MINIMUM OF (2) FIRE DEPARTMENT |
| | CONNECTIONS ARE REQUIRED ON HIGHRISE |
| | BUILDINGS. |
| | |
| | |
| | 34) FIRE PUMP SHALL MEET THE |
| | REQUIREMENTS OF NFPA 20 AND MANUFACTURER |
| | SPEC SHEETS REQUIRED. |
| | |
| | 35) ALL SHAFTS LARGE ENOUGH FOR PERSONS |
| | TO FALL INTO MUST BE MARKED SHAFTWAY IN |
| | 6" LETTERS. |
| | |
| | 36) LOCKING KNOX BOX CAPS ARE REQUIRED |
| | ON THE FIRE DEPARTMENT CONNECTIONS. |
| | |
| | |
| | MIKE WENNERGREN, CAPTAIN/WPBFR |
| | FIRE PLAN REVIEW (561) 805-6722 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |