Date Text
2005-12-01 00:00:00******DENIED******
  
 TOWER #4
  
 1) FIRE HYDRANTS TO BE WET AND
 OPERATIONAL PRIOR TO, DURING AND AFTER
 CONSTRUCTION
  
 2) FOR REFERENCE, HIGHRISE IS DEFINED AS
 A BUILDING GREATER THAN 75' IN HEIGHT.
 SHT A-1.1.2
  
 3) PLEASE NOTE THAT THE FIRE PUMP IS
 SHOWN IN THE PARKING GARAGE THAT ISN'T
 PART OF THIS PHASE. ADDITIONAL
 INFORMATION REGARDING WHAT ARRANGEMENT
 BY THIS OFFICE HAS BEEN ACCEPTED IS
 REQUIRED. THE FIRE PUMP SHALL BE A
 MINIMUM OF 1250 GPM FOR A HIGHRISE
 BUILDING. PLEASE CONTACT THE BUREAU OF
 FIRE PREVENTION AT (561) 804-4724.
  
 4) BUILDING TO MEET APPLICABLE BUILDING
 CODES AND NFPA CHAPTER 11 REQUIREMENTS
 FOR HIGHRISE BUILDINGS.
  
 5) PLEASE VERIFY THAT NO COOKING WILL
 OCCUR IN THE CATERING KITCHEN.
  
 6) EXIT STAIRS ARE TO BE KEPT UP WITH
 CONSTRUCTION.
  
 7) NOTE REGARDING THE ADDRESS NUMBER IS
 ACKNOWLEDGED. PLEASE ILLUSTRATE ON
 ELEVATION SHEETS FOR FUTURE REFERENCE
 AND FURTHER PLAN REVIEW.
  
 8) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENT FOR HANDRAILS AND GUARDS
  
 9) KNOX BOXES WILL BE REQUIRED.
  
 10) PLEASE INDICATE THE OCCUPANT LOAD
 CALCULATIONS FOR THE HOME THEATER AND
 FITTNESS CENTER.
  
 11) PLEASE PROVIDE THE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS IE
 CLASS A,B OR C.
  
 12) TACTILE SIGNAGE IS REQUIRED AT EXIT
 DOORS.
  
 13) PLEASE INDICATE IF ELEVATORS ARE
 STRETCHER ACCESSIBLE.
  
 14) SIGNS ARE REQUIRED IN STAIRWELLS
 INDICATING TOP, BOTTOM, FLOOR NUMBER AND
 ROOF ACCESS.
  
 15) WARNING SIGNS ARE REQUIRED IN
 ELEVATOR LOBBIES.
  
 16) IN ACCORDANCE WITH LOCAL
 REQUIREMENTS, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM WHEN
 ACTIVATED.
  
 17) FIRE ALARM SYSTEM TO BE CLASS A,
 STYLE D OR FULLY ADDRESSABLE.
  
 18) AS INDICATED ON PLANS, SEPARATE SHOP
 DRAWINGS AND PERMITS ARE REQUIRED FOR
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS.
  
 19) UL CERTIFICATION TO BE PROVIDED AT
 THE TIME OF THE FIRE ALARM ACCEPTANCE
 TEST.
  
 20) IN ADDITION TO ELECTRONIC SWITCHES,
 DOUBLE CHECK DETECTOR ASSEMBLY TO BE
 SECURED WITH LOCK AND CHAIN.
  
 21) HYDRAULIC CALCULATIONS WILL BE
 REQUIRED WHEN APPLYING FOR THE FIRE
 SPRINKLER PERMIT.
  
 22) FDV ON STANDPIPE SHALL BE 2 1/2" TO
 1 1/2" REDUCER WITH CHAIN.
  
 23) TEMPORARY STANDPIPES ARE REQUIRED
 WHEN THE BUILDING REACHED 3 STORIES OR
 30" IN HEIGHT.
  
 24) NO FIRE SPRINKLER COVERAGE NOTED TO
 COVERED WALKWAYS AND PORTE COCHERE.
  
 25) PLANS DON'T SHOW ANY EXIT SIGNS OR
 EMERGENCY LIGHTING FACILITIES IN COMMON
 AREA MEANS OF EGRESS. PLEASE SHOW ON
 ELECRICAL AND LIFE SAFETY SHTS.
  
 26) FIRE ALARM SYSTEM TO MEET THE
 SURVIVABILITY REQUIREMENTS IN ACCORDANCE
 WITH NFPA 72.
  
 27) THE ANTICIPATED STACK EFFECT NOTE
 WORDING SHALL BE ADDED TO THE MECHANICAL
 SHTS.
  
 28) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 29) ELEVATORS TO COMPLY WITH BUILDING
 AND FIRE CODES AND ASME/ANSI A 17.1.
  
 30) FIRE SPRINKLER COVERAGE DOESN'T
 EXTEND TO ELEC/PHONE ROOMS.
  
 31) NO CUTTING OR WELDING TO OCCUR
 WITHOUT APPROVAL OF FIRE PREVENTION
 BUREAU AND COMPLIANCE WITH NFPA 51B.
  
 32) EMERGENCY LIGHTING IS NOT SHOWN IN
 ELEC/PHONE ROOMS ON UPPER FLOORS.
  
 33) A MINIMUM OF (2) FIRE DEPARTMENT
 CONNECTIONS ARE REQUIRED ON HIGHRISE
 BUILDINGS.
  
  
 34) FIRE PUMP SHALL MEET THE
 REQUIREMENTS OF NFPA 20 AND MANUFACTURER
 SPEC SHEETS REQUIRED.
  
 35) ALL SHAFTS LARGE ENOUGH FOR PERSONS
 TO FALL INTO MUST BE MARKED SHAFTWAY IN
 6" LETTERS.
  
 36) LOCKING KNOX BOX CAPS ARE REQUIRED
 ON THE FIRE DEPARTMENT CONNECTIONS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  