Plan Review Notes
Plan Review Notes For Permit 05080675
Permit Number 05080675
Review Stop E
Sequence Number 1
Notes
Date Text
2005-09-29 00:00:00SAIL CLUB TOWER #4
  
 **** UNSAT ****
  
  
 1)NOTE: PLEASE SEE CODE REFERENCED ON
 PLANS LIST THE 1999 NEC. PLEASE KNOW, AS
 OF JULY 1ST 2003, THE STATE ADOPTE DTHE
 2002 NEC.
 PLEASE ALSO SEE WE ARE UNDER THE 2003
 NFPA-101 AND 2002 NFPA-72
 PLEASE ADJUST.
  
 2)NOTE: PLEASE SEE BLDG /FIRE REVIEW
 COMMENTS FOR STAIR TOWER EXITING WHICH
 WILL AFFECT ELECTRICAL LAYOUT.
 EXITS BACK INTO HALL WAY AREAS IN FRONT
 OF UNITS.
 PLEASE ALSO SEE POSSIBLE NOTES FOR
 EXITING OUTSIDE TRASH ROOM.
 PLEASE SEE BLDG REVIEW FOR STAIR TOWER
 #2 AND SWING OF DOOR AND PATH OF EGREES
 TRAVEL.
  
 3)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULES.
 PLEASE SEE SOME AREAS WHICH ELECTRICAL
 FIXTURES SEEM TO BE MISSINGTHIS.
 PLEASE ALSO SEE CIRCUITING FOR UNITS.
 PLEASE KNOW, A "TYPICAL" UNIT LAYOUT MAY
 BE PROVIDED, HOWEVER A LAYOUT WOULD BE
 REQUIRED FOR EACH UNIT TYPE, INCLUDING
 STUDIO UNIT.
 CIRCUITING FOR SOME UNITS/ITEMS CAN NOT
 BE VERIFIED AT THIS TIME.
  
 4)NOTE: PLEASE PROVIDE PHOTO-METRICS FOR
 STAIR TOWERS ON NORMAL PWR AND STAND-BY.
 ALONG WITH WALK AREAS.
 PLEASE SEE STAIR TOWERS UNDER NORMAL PWR
 SHALL MEET A MIN OF 10FT CANDLES. PLEASE
 SEE ARES FOR HALLS ETC ARE PERMITTED TO
 BE LESS. .
 PLEASE SEE NFPA-101 7.8.1.3,7.9.2.1
  
 5)NOTE:
 PLEASE KNOW, BATTERY BACK FIXTURES WILL
 BE REQUIRED AT EVERY OTHER LEVEL(MIN).
 PLEASE SEE LS 101 WHICH MENTIONS THE
 TRIPPING/THROW OF A SINGLE BRKR SAHLL
 NOT LEAVE ANY EGRESS AREA IN TOTAL
 DARKNESS. PLEASE CALL ELECTRICAL PLAN
 REVIEW AND FIRE MARSHALS OFFICE TO GO
 OVER OPTIONS PERMITTED.
 A BATTERY BACK-UP FIXTURE AT EVERY OTHER
 LEVEL WILL SATISFY FIRE MARSHAL'S OFFICE
 AND AHJ.
 PLEASE BE SURE TO MEET THE MIN OF 1
 FT/CANDLE UNDER EM.
 PLEASE BE SURE TO SEE PREVIOUS NOTE #4
 FOR LIGHTING LEVELS.(MIN)
  
 6)NOTE: PLEASE PROVIDE BATTERY BACK-UP
 FIXTURES IN MAIN ELECTRICAL RMS AND
 ELEVATOR ROOM(S), GENERATOR AND FIRE
 PUMP ROOM. PLEASE ALSO PROVIDE
 CIRCUITING FOR THESE
 RMS.
  
 7)NOTE: PLEASE PROVIDE CURB DETAIL FOR
 BUS-DUCT RISER AND FLOOR PENATRATIONS.
 368.6
  
 8)NOTE: PLEASE PROVIDE NOTES ON RISER
 AND ELECTRICAL ROOM SHEETS FOR
 REQUIREMENTS OF 110.26 FOR PANIC
 HARDWARE AND DOOR SWINGS.
 PLEASE SEE MIN CLEARENCE PER 110.26
 PLEASE ALSO SEE MIN DOOR OPENING 6' WITH
 SINGLE ACCESS FOR EWUIPMENT MORE THAN
 1200 A'S AND OVER 6' WIDE.
  
 9)NOTE: PLEASE SEE RISER INDICATES ALL
 BUS-DUCT FROM FPL VAULT TO MAIN
 ELECTRICAL ROOM AS OVER-HEAD. PLEASE SEE
 230.70, 230.6, NO MORE THAN 8' OF
 UNPROTECTED CONDUCTORS/ OR BUS DUCT
 PERMITTED "INSIDE THE BLDG.
 PLEASE SEE ROUTING OF BUS-DUCT APPEARS
 TO SHOW INSTALLATION INSIDE CONDO
 UNITS??
 PLEASE PROVIDE LAYOUT, REVISE TO
 UNDER-GROUND FEEDERS OR OTHER ACCEPTABLE
 MEANS.
  
 10)NOTE: PLEASE PROVIDE INFORMATION ON
 BUS -DUCT RISER MAINS. APPEARS TO SHOW
 THESE AS "SHUNT-TRIP" AND NOT CONTAINING
 A MANUAL MEANS OF DISCONNECT LOCATED ON
 THE OUTSIDE OF THE EQUIPMENT. PLEASE SEE
 MAIN PANEL SCHEDULE(S), THESE DO NOT
 SEEM TO INDICATE A MCB.
 230.76,230.79
  
 11)NOTE: PLEASE SEE GARAGE PLANS FOR
 FIRE PUMP RM AND GEN RM ARE SHOWN BLANK?
  
 12)NOTE: PLEASE PROVIDE SPECIFIC
 INFORMATION ON BUS-DUCT, PLEASE SEE AN
 ALUM EQUIPMENT GROUNDING CONDUCTOR/
 MATERIAL IS NOT PERMITED.
 310.2. LOCAL AMENDMENTS.
  
 13)NOTE: PLEASE SUBMIT ALL MANUFACTURE
 SPECS AND CUT SHEETS FOR GENERATOR, ATS,
 FIRE PUMP AND FIRE PUMP CONTROLLER.
 PLEASE ALSO SUBMIT THE SAME FOR ANYSUB
 BASE FUEL TANK.
 PLEASE KNOW, DUE TO THE INFORMATION NOT
 BEING SUBMITTED AT THIS TIME, REVIEW FOR
 SOME ITEMS FOR CODE COMPLIANCE CAN NOT
 BE DONE.
 UNABLE TO VERIFY CODE COMPLIANCE FOR
 MANY ITEMS UNDER NFPA, 20,70,101,110
 ETC.
 SOME INFORMATION IS "APECIFIED" ON PLANS
 FOR TOWER #4, HOWEVER, TOWER #3 SHOULD
 REFLECT THE SAME INFORMATION. ALL
 MANUFACTURE CUTS/SPECS ARE STILL
 REQUIRED.
  
 14)NOTE: PLEASE SEE ELECTRICAL RISER
 DIAGRAM DOES CONTAININFORMATION
 FOR FIRE PUMP, YET NOT FIRE PUMP
 CONTROLLER,
 SERVICE, SIZING, LOCKED ROTOR SETTINGS
 ETC.
 PLEASE COMPLETE.
 ENCASEMENT IN CONCRETE, OUTSIDE THE
 BLDGS, ETC
  
 15)NOTE: PLEASE SEE AREA FOR GARAGE
 CONTAINING THE LOCATION OF FIRE PUMP AND
 GENERATOR WILL BE REQUIRED TO BE
 SUBITTED FOR PERMIT AND REVIEW.
 PLEASE SEE LOCATIONS FOR FIRE
 SEPARATIONS, ACCESS, LIGHTING, ETC CAN
 NOT BE REVIEWED AT THIS TIME.
  
 16)NOTE: PLEASE SEE A PANEL SCHEDULE FOR
 A PANELH12B IS SUBMITTED, HOWEVER THIS
 PANEL COULD NTO BELOCATED ON RISER
 DIAGRAM??
 PLEASE CORRELATE.
  
 17)NOTE: PLEASE PROVIDE DISCONNECTING
 MEANS FOR ALL A/C EQUIPMENT AT ROOF TOP
 LEVEL. A"TYPICAL" DETAIL MAY BE GIVEN
 FOR THESE.440.11
 PLEASE SHOW A "TYPICAL DETAIL SHOWING
 MOUNTING ETC.
  
 PLEASE CORRELATE ALL A/ KW RATINGS AND
 LOADS WITH MECHANICNAL PLANS . (KW
 RATINGS ETC).
  
 18)NOTE: PLEASE SEE FIRE REVIEW NOTES
 ALSO: PLEASE PROVIDE A LAYOUT FOR
 CENTRAL STATION RM(FIRE COMMAND RM)
 SHOWING ALL DEVICES/ PANELS/ STATUS
 PANELS ETC.
 PLEASE LIST ALL ITEMS AS SPECIFIED IN
 NFPA- 101 11.8.5,
  
 19)NOTE: PLEASE SEE RECEPTS MISSING PER
 210.52
 SEE REDLINED PLANS.
  
 20)NOTE: PLEASE CALRIFY THE "P" LOCATED
 NEXT TO SMOKE DETECTORS?
 THIS CORRELATING SYMBOL COULD NOT BE
 LOCATED ON PLANS.
  
 21)NOTE: PLEASE VERIFY CIRCUITING OF
 LAUNDRY RM/ WASHER CIRCUIT.
 PLEASE SEE 210.11C2,210.52F,220.16
 PLEASE ALSO SEE MIN 1500VA.
 PLEASE VERIFY LOAD FOR WASHER.
  
 22)NOTE:PLEASE PROVIDE NOTE ON PLANS
 FOR SMOKE DETECTOR PLACEMENT PER
 REQUIREMENTS NFPA -72 11.8.3.5.
  
 23): PLEASE PROVIDE NOTE FOR ALL
 ELECTRICAL DEVICES TO BE INSTALLED PER
 FAIR HOUSING ACT REGULATIONS, (FHAR) 24
 CFR 100.205
  
 24)NOTE: PLEASE SEE 210.52C1 FOR SOME
 MISSING KITCHEN COUNTERSPACE RECEPTS.
 PLEASE ALSO SEE COUNTERSPACE APPEARS TO
 SHOW A DEDICATED CIRCUIT (19) FOR
 MICROWAVE WHICH ALSO APPEARS TO BE THE
 RECEPT FOR KITCHEN COUNTERSPACE?
 IF THE MICROWAVE IS A DEDICATED RECEPT,
 THEN AN ADDTIONAL GFI WOULD BE REQUIRED.
 210.8A16.
  
 25)NOTE: PLEASE SEE A 70A BRKR IS BEING
 SHOWN FOR RANGE??
 PLEASE SEE 210.23,422.11B
 50A RANGE RECEPT, 50A BRKR MAX.
  
 26)NOTE: PLEASE SEE PANEL SCHEDULES SEEM
 TO SHOW "A" AND "C" PHASE FOR SINLGLE
 PHASE SERVICE AND UNITS??
 PLEASE CLARIFY / ADJSUT.
 215.5
  
 27)NOTE: PLEASE LABEL AND /OR CLARIFY
 "DINING" AREAS IN ALL UNITS.
 UNABLE TO VERIFY CIRCUITING AS DINING
 /LIVING ARE SEEMED TO BE COMBINED.'
 PLEASE SEE 210.52B1
  
 28)NOTE: PLEASE SEE 210.52D FOR SOME
 UNITS MISSING GFI'S WITH IN 3' OF LAV'S.
 PLEASE ALSO SEE A GFI MAY NOT PERMITTED
 ON THE OTHER SIDE OF A LAV TO MEET
 210.52D (3').
 GFI 'S MAY BE MOVED IN BETWEEN BOTH
 LAV'S OR AN ADDITIONALRECEPT MAY BE
 ADDED.
  
 29)NOTE: PLEASE SEE MISSING RECEPTS IN
 HALLWAY AREAS, 10' OR MORE OF CONTINUOUS
 WALL.
 210.52H.
  
 30)NOTE: PLEASE SEE RISER SEEMS TO
 INDICATE A POOL PANEL, HOWEVER NO OTHER
 INFORMATION WAS SUBMITTED AND PANEL
 COULD NOT LOCATED ON PLANS.
 LOADS ETC.
 215.5, 220
  
 31)NOTE: PLEASE VERIFY BATH CIRCUITS
 BEING SHOWN WITH ARC FAULT PROTECTION??
 210.8 REQUIRES GFI PROTECTION FOR BATHS
 AND 210.12 ARC FAULT PROTECTION FOR
 BEDROOM CIRCUITS?
 THIS IS ONLY A NOTE:
  
 32)NOTE: PLEASE PLACE NOTE ON "ROOF
 PLANS" WHICH WILL REQUIRE ALL LIGHTNING
 PROTECTION
  
  
 33)NOTE: PLEASE IDICATE ON PLANS/RISER
 IF GENERATOR WILL BE A "SEPARATELY
 DERIVED SYSTEM" OR A " NON SEPARATELY
 DERIVEDSYSTEM.
 IF SD, PLEASE INCLUDE GROUNDING
 ELECTRODE SYSTEM PER 250.30
  
 34)NOTE: PLEASE INDICATE IF PANELS EH2A-
 EH9A ARE FEED THRU LUGS OR DOES EACH
 PANEL CONTAIN OCP FOR EACH.?
 PLEASE ALSO SEE PANELS H5A-9, ETC.
 215.5
  
 35)NOTE: PLEASESEE PANELS EH2-EH9 ARE
 SHOWN ON RISER AND ESBA BEING FED W/
 225A OVER CURRENT PROTECTION, HOWEVER
 EACH OF THESE ARE SHOWN AS 125A ON PANEL
 SCHEDULE(S). PLEASE CORRELATE.
 215.5
  
 36) NOTE:PLEASE INDICATE IF EH2A- 9 ARE
 PANELS CONTAING "FEED-THRU" LUGS OR IS
 THERE OCP IN EACH OF THESE PANELS
 FEEDING THRU TO OTHER PANELS?
 215.5
  
 37)NOTE: PLEASE CLARIFY NOTES # 5 AND #6
 ON GROUNDING RISER?
 250.50
  
 38)NOTE: PLEASE SEE RISER INDICATES
 PANEL H12A FEEDING "ELEV PANEL" WITH
 CIRCUITS 20,22,24, HOWEVER PLEASE SEE
 PANEL H12A, DOES NOT SHOW ANY FEED TO
 "ELEVATOR PANEL".
 PLEASE CORRELATE.215.5
 PLEASE ALSO ADJUST LOAD CALCULATIONS FOR
 ADDITIONAL PANEL WHEN ADDED.
  
 39)NOTE: PLEASE SUBMIT "SPEC BOOKS' FOR
 REVIEW OF PROJECT.
 THESE WOULD CONTAIN JOBSITE SPECS.
  
 40)NOTE: PLEASE BE SURE ALL CONTINUOUS
 LOADS ARE SHOWN AT 125%.
 215.3,230.42 ETC.
  
 41)NOTE: PLEASE SEE MIN OCP FOR AHU HEAT
 TO BE 125%. 424.3B
 SHOWS 50A OCP.
  
 42)NOTE: PLEASE HAVE PANEL H2A INDICATE
 ALSO IF "FEED-THRU" LUGS.
  
 ** PLEASE SEE THAT NO PLANS, PERMIT
 APPLICATION ETC WAS SUBMITTED FOR GARAGE
 BLDGS.
  
 ** PLEASE KNOW, MANY OF THE ABOVE ITEMS
 ARE "REDLINED" AT LOCATIONS ON PLANS FOR
 NOTES.
  
 ** PLEASE KNOW, A RESPONSE LETTER IN
 TYPE WRITTEN FORM WILL HELP IN RESPONSES
 TO ELECTRICAL COMMENTS.
  
 ** PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO "REMOVE" ALL OLD
 VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO THE COMPLETED SETS
 FOR REVIEW AND STAMPING.
  
 ** PLEASE SEE BLDG REVIEW COMMENTS WHICH
 WILL REQUIRE ALL PRODUCT APPROVALS,
 SUBMITTALS ETC TO BE DETACHED FROM
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-09-28 00:00:00PLANS IN "F" STATUS, NOTES TO FOLLOW.
2005-09-11 00:00:00ONE ROLL IN ELECTRIC FOR REVIEW.
 REVIEWS IN PROGRESS .