2005-10-17 00:00:00PERMIT: 05080675
 ADD: 719 EXECUTIVE CENTER DR
 (TOWER# 4)
 CONT: THE WEITZ CO.
 TEL: (561)686-5511
 CELL:(954)675-4302
  
 ARCHITECT: ACI ARCHITECRTURALGROUP
 PAUL M. TWITTY
 TEL:(561)832-5599
 STRUC ENGINEER: ONM&J
 PHILLIP RIZZO
 TEL:(561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE
 ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) 105.8* PROVIDE NOC RECORDED WITH THE
 CLERK OF COURT BEFORE A PERMIT CAN BE
 ISSUED.
  
 3A)109.3.7*THIS PARTICUAL TYPE OF
 BUILDING WILL REQUIRE A THRESHOLD
 INSPECTOR.FORMS WILL NEED TO BE FILED
 OUT FOR THE THRESHOLD INSPECTOR, CONTACT
 HAROLD PISKURA, INSPECTION SERVICES
 MANAGER @ (561)805-6711 TO SEET UP AN
 APPOINTMENT.
  
 3B) 109.3.6.1* THE ENFORCING AGENCY
 SHALL REQUIRE A SPECIAL INSPECTOR TO
 PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A
 STRUCTURAL INSPECTION PLAN PREPARED BY
 THE ENGINEER OR ARCHITECT OF RECORD.
 THE STRUCTURAL INSPECTION PLAN MUST BE
 SUBMITTED TO THE ENFORCINGAGENCY PRIOR
 TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD
 BUILDING.THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLANS IS TO PROVIDE SPECIFIC
 INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 3C) 109.3.6.4.4.105.13.4.4 ALL PLANS FOR
 THE BUILDING WHICH ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S OR
 ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND
 THE APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTES.
  
 3D) NOTE: SINCE THIS BUILDING WILL BE A
 THRESHOLD STRUCTURE SUBMIT (3) OF ALL
 DOCUMENTS FOR REVIEW.
  
 4) 106.3.3* PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 SHALL BE REVIEWED AND APPROVED IN
 WRITTING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR " JURISDICTIONAL
 APPROVAL", (LOCAL PRODUCT APPROVAL).
  
 5) SITE PLAN NEEDS TO BE SUBMITTED TO
 ADDRESSING PERSONEL JOHN HIGGINS FOR
 ADDRESSING AS WELL AS NEW PLAT MAP FOR
 THE COMBINATION OF LOTS. JOHN HIGGINS
 CONTACT NUMBER IS (561)822-1239.
  
 6) THE SURVEY DOES SHOW 2 SEPERATE LOTS
 WHICH APPEAR TO CUT THROUGH BULDING "B"
 AND BUILDING "C". A UNITY OF TITLE SHALL
 BE REQUIRED, TABLE 601 AND 602.
  
 7) SHEET A-1.1.2 BUILDING DATA FOR
 TOWER#4 INDICATES 107 UNITS WHERE AS THE
 SAME SHEET THE SITE PLAN INDICATES 108,
 CORRECT DESCRIPANCY.
  
 8) GEOTECHNICAL REPORT THAT WORK WAS
 PREFORMED BY ARDAMAN NEEDS TO BE AN
 ORIGINAL WITH SIGNATURE AND RAISED SEAL.
 PLANS, SPECIFICATIONS,REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 9) 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS
 CODE SHALL BE PERMORMED IN A MANNER SO
 AS NOT TO ADVERSLY IMPACT THE CONDITION
 OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE
 PROPERTY OWNER.THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE,
 WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS.
 NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORICSURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGNCOMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED
 SITES.ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENET, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS,
 DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN
 EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCELL SHALL AS A PERMIT
 CONDITION, PROVIDE A PROFESSIONALY
 PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 10)109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM
 HIGHWINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 11) SHEET T-4 A2.1.1
 11A) STAIR TOWER # 2, DOOR A/130 SWINGS
 THE WRONG WAY,SEE 1008.1.2.
  
 11B) ELEVATORS, PLEASE INDICATE THAT THE
 ELEVATORS CAN ACCOMODATE AMBULANCE
 STRETCHERS. 3002.4.
  
 12)SHEET T-4 A2.1.1 FAIR HOUSING/
 ACCESIBLITY
 12A)PLANS DO NOT PROVIDE AN ACCESSIBLE
 PATH TO THE BUS STOP. THE SIDEWALK STOPS
 SHORT OF BUS STOP BENCH. THERE IS NO
 PEDESTRIAN CROSSWALK CONNECTING THE
 SIDEWALKS TO PUBLIC TRANS PORTATION.
  
 12B) PROVIDE HOW THE HANDICAPPED
 ACCESSIBLE PATH (SIDEWALKS) WILL BE
 MAINTAINED DURING THE PHASING, PROVIDE A
 SITE PLAN INDICATING ACCESSIBLITY TO THE
  
 PUBLIC WAY.
  
 12C) PORTE COCHERE: THE PLANS DO NOT
 INDICATE THERE IS A ACCESSIBLE LOADING
 ZONE UNDER THE PORTE COCHERE. FAIR
 HOUSING ANSI 4.6
  
 12D) PROVIDE SIGNAGE FOR HANDICAPPED
 PARKING, AND VAN ACCESSIBLE PARKING.
  
 12E) PLANS DO NOT INDICATE REACH RANGES
 FOR THE COMMON USE MAIL BOXES.
  
 12F) THERE IS NO KITCHEN DETAILS
 INDICATING AN ACCESSIBLE SINK WITH
 FORWARD APPOARCH.
  
 12G) THE INDIVIDUAL UNITS WITH ENTRYS
 WITH 45 DEGREE WALLS MISSING THE
 REQUIRED 18" ON THE PULL SIDE OF DOOR.
 SEE ANSI 4.13.6, ONLY REQUIED ON THE
 EXTERIOR SIDE.
 THE UNIT ENTRY DOORS WITH 45 DEGREE
 WALLS ADJACENT TO THE FFRONT ENTRY DOOR
 DO NOT MEET THE FAIR HOUSING GUIDELINE
 FOR AN ACCESSIBLE FRONT ENTRY, SEE
 ANSI 4.13FOR THE EXTERIOR SIDE LATCH
 SIDE OF DOOR ONLY.
  
 12H) IN BOTH STAIR TOWER 1 & 2 THE ARROW
 INDICATING DIRECTION OF TRAVEL IS
 BACKWARDS. WHEN CORRECTED THE PROBLEM
 WITH REDUCED VERTICAL CLEARENCE UNDER
 THE STAIRS WILL BE APPEARENT. ANSI 117.1
 SECTION 307.4 REQUIRING EITHER A
 GUARDRAIL OR OTHER BARRIER WHERE THE
 VERTICAL HEIGHT IS REDUCED LESS THAN
 80".
  
 13) STAIR TOWER# 2 DOOR A/130 IS
 SWINGING THE WRONG WAY, SEE 1008.1.2
  
 14) SHEET A2.1.1/ A2.1.3
 STAIR TOWER# 1& STAIR TOWER# 2 IN BOTH
 CASES ONCE THE STAIR TOWER DOOR OPENS
 LEAVES THE OCCUPANTS WITHIN THE CONFINES
 OF THE BUILDING. THE DOORS AND WINDOWS
 ON THE OPPOSITE WALL ARE NOT RATED. THE
 LIFE SAFETY PLAN INDICATES IN BOTH CASES
 A SINGLE MEANS OF EGRESS.
 SEE 1013.5.1. THIS SECTION IS FOR
 BALCONIES, THE SAME CONCERNS ABOUT
 EGRESS APPLIES THAT THE OPENINGS WOULD
 REQUIRE OPENING PROTECTIVES.
  
 15) SHEET T-4 A2.2.1.
 15A) THE 2ND FLOOR AND HIGHER FLOORS
 HAVE THE SAME PROBLEM WITH NOT HAVING AN
 ELEVATOR LOBBY. THE AREA THAT SURROUNDS
 THE ELEVATORS AND IS ENCLOSED NOT
 MEETING THE DIFINITION OF AN OPEN
 BALCONY (SEE 1013.5.2) AND WILL BE
 CONSIDERED AS A CORRIDOR REQUIRING
 A 1HR RATING SEE TABLE 1016.1.
  
 15B) ELEVATOR LOBBIES SHALL MEET THE
 REQUIREMENTS OF 707.1.14.1.THE LOBBY
 SHALL SEPERATE THE ELEVATOR FROM THE
 CORRIDOR BY FIRE PARTITIONS AND THE
 REQUIRED OPENING PPROTECTION.
  
 15C) UNIT A, UNIT B, UNIT C, UNIT E,
 UNIT I, UNIT B AND UNIT A ARE EITHER
 TOTALLY WITHIN A CORRIDOR OR PARTIALLY
 WITHIN A CORRIDOR REQUIRING RATED
 OPENING PROTECTIVES SEE TABLE 1016.1.
  
 15D) NOTE IF WINDOWS REQUIRES FIRE RATED
 GLASS, AS FAR AS I'M AWARE NO
 MANUFACTURER MAKES FIRE RATED AND LARGE
 MISSLE IMPACT RATED GLAZING!!!! SEE
 THE BUILDING OFFICIALS INTERPRETATION ON
  
 LARGE OR HIGH RISE BUILDINGS AS FAR AS
 SHUTTERS VS LARGE OR SMALL MISSLE RATED
 GLASS.
 *************************
 QUESTION# 13) RECOGNIZING SUCH CONCERNS
 AS ABSENTEE OWNERS, OR CASES WHERE
 LONGER TIME AND EFFORT IS NECESSARY TO
 SECURE SHUTTERS ON LARGE OR MULTI-STORY
 BUILDINGS, WHAT MEASURES ARE BEING
 RECOMMENDED OR IMPLEMENTED TO ENSURE
 THAT COMPLETE INSTALLATION OR SECURING
 IS DONE SUFFICIENTLY IN ADVANCE OF THE
 HURRICANE EVENT?
  
 IN MATTERS FLORIDA BUILDING CODE, 2004
 EDITION, PROVIDES THE ABILITY FOR THE
 BUILDING OFFICIAL TO IMPLEMENT
 REQUIREMENTS FOR ENSURING STABILITY,
 STRENGTH, AND PROPER OPERATION OF
 EXISTING BUILDINGS.
  
 IN ORDER TO ASSURE THE SECURING OF
 SHUTTERS ON LARGE OR MULTI-STORY
 BUILDING, OR MULTIPLE BUILDINGS ON THE
 SAME PROPERTY, PRE-STORM PREPARATION
 PLANS MUST BE SUBMITTED BY THE PROPERTY
 OWNERS OR MANAGING AGENTS FOR REVIEW BY
 THE CONSTRUCTION SERVICES DEPARTMENT.
 ANY SUCH PLAN SHALL INCLUDE, AT A
 MINIMUM, ON-SITE LOCATION OF SHUTTERS,
 PARTY RESPONSIBLE FOR SECURING THE
 SHUTTERS (SAID PARTIES MUST BE LOCATED
 WITHIN PALM BEACH COUNTY), TOTAL NUMBER
 OF OPENINGS TO BE PROTECTED AND TOTAL
 TIME REQUIRED TO SECURE ALL OPENINGS.
 PROTECTION OF OPENINGS SHALL BE
 ACCOMPLISHED WITHIN TWELVE (12) HOURS OR
 LESS OF THE OFFICIAL NOTIFICATION BY THE
 NATIONAL WEATHER SERVICE OF A HURRICANE
 WATCH.
  
 PROVISIONS IN THE BUILDING CODES (AND
 THIS STANDARD) ARE NOT INTENDED TO
 PROHIBIT THE USE OF ALTERNATIVE
 MATERIALS AND METHODS, AND ALLOW THE
 BUILDING OFFICIAL TO REVIEW AND APPROVE
 ANY ALTERNATE DEEMED EQUIVALENT IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE
 RESISTANCE, DURABILITY AND SAFETY
 PRESCRIBED BY CODE. BASED UPON THIS CODE
 PROVISION, ACCEPTANCE OF ALTERNATE
 MATERIALS AND METHODS MAY BE APPROVED ON
 A CASE-BY-CASE BASIS AND SHALL REQUIRE
 SUFFICIENT EVIDENCE OR PROOF TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING
 THE ALTERNATE.
  
 QUESTION# 14) ARE REMOVABLE STORM PANELS
 APPROPRIATE FOR USE ON VERY LARGE, MID
 OR HIGH-RISE STRUCTURES?
  
 NO, EXCEPT ON THE GROUND FLOOR. ON
 COMMERCIAL AND MULTI-UNIT RESIDENTIAL
 STRUCTURES, ABOVE THE FIRST LEVEL,
 IMPACT RESISTANT GLAZING OR PERMANENTLY
 AFFIXED PROTECTIVE DEVICES SHALL BE
 INSTALLED. PERMANENTLY AFFIXED
 PROTECTIVE DEVICES SHALL REQUIRE THE
 WRITTEN APPROVAL OF THE BUILDING
 OFFICIAL.
  
 16)T-4 A.2.2.3 CODE REVIEW FOR HIGH RISE
 BLDG DOES NOT INDICATE AS TO WHICH CODE
 THIS BUILDING WAS DESIGNED TO.
  
 17)SHEET T4-A2.4.1:
 17A) THIS PLAN HAS THE TERM "WALL
 ANCHOR" PLEASE EXPLAIN?
  
 17B) TERM E.O.S. EMERGENCY OVERFLOW
 SCUPPER DOES NOT INDICATE ANY SECTIONS
 THROUGH NOR GIVE SIZES, ADDITIONAL
 INFORMATION REQUIRED.
  
 17C) ROOF TOP MECHANICAL UNITS AS SHOWN
 ON A6.1.3 DETAIL 8 INDICATES A MINIMUM
 OF 18" FROM ROOF, SEE TABLE 1509.7 FOR
 MINIMUM VERTICAL HEIGHTS.
  
 18) T-4 A.2.5.1-A2.5.3 ARE FOR AN AREAL
 COVERED WALKWAY . SHEET T-4 A.3.1.3,
 NOTE, THAT A SEPERATE PERMIT WILL BE
 SUBMITTED FOR CONSTRUCTION OF AREAL
 COVED WALKWAY. THESE PAGES WILL BE
 STRUCK "VOID" AND THE ASSOCIATED
 STRUCTURAL PAGES.
  
 19) SHEET T-4 A2.4.2 INDICATES 3 ATTIC
 AREAS NO USEAGE INDICATED. 1509.2 A
 PENTHOUSE, BULKHEAD OR ANY OTHER SIMILAR
 PROJECTION ABOVE THE ROOF SHALL NOT BE
 USSED FOR PURPOSES OTHER THAN SHELTERING
 OF MECHANICAL EQUIPMENT OR SHELTEROF
 VERTICAL SHAFT OPENINGS IN THE ROOF.
 PENT HOUSES USSED FOR PURPOSES OTHER
 THAN PERMITTED BY THIS SECTION SHALL
 CONFORM TO THE REQUIREMENTS OFTHIS CODE
 FOR AN ADDITIONAL STORY.
  
 20) THE ELEVATION SHEETS AND A6.1.1
 DEPICT DETAILS WITH CAST RESIN CORNICE
 AND BANDS ON THE EXTERIOR OF THE
 BUILDING. 1406.2.2 ARCHITECTURAL TRIM
 THAT EXCEEDS 40FT IN HEIGHT ABOVE GRADE
 PLANE SHALL BE CONSTRUCTED OF APPROVED
 NONCOMBUSTIBLE MATERIALS AND SHALL BE
 SECURED TO THE WALL WITH METAL OR OTHER
 APPROVED NONCOMBUSTIBLE BRACKETS.
  
 21)T-4A6.1.3 DETAIL# 11/ A5.1.3 BOTH SEC
 TIONS INDICATE USE OF R-30 INSULATION.
 THE INSULATION IS DEPICTED TO BE IN THE
 TOP CHORD OF THE METAL TRUSS. THE
 TRUSSES ARE CENTERED @ 48" O. C. HOW
 WILL THE INSULATION BE ATTACHEDAND TO
 WHAT?
  
 22) T-4 A6.1.3 DETAIL# 11 ALSO INDICATES
 THE USE OF INTEGRAL ROOF DECK PROVIDE
 ADDITIONAL INFORMATION.
  
 23) SAME DETAIL AS ABOVE WHAT SPANS CAN
 THE GALVANIZED METAL FURRING SPAN @ 12"
 O. C. PROVIDE THE PSF APPLIED LOAD, AND
 THICKNESS OF HI HAT IN MIL. SPANS TO BE
 TAKEN AS MULTIPLE SPANS?
  
 24) T-4 A7.2.1 THE DOOR SCHEDULE UNDER
 REMARKS HAS NO NOTATIONS, AS TO REQUIRED
 HARDWARE, SELF-CLOSING DOORS AND DROP
 SEALS PLEASE PROVIDE THIS ADDITIONAL
 INFORMATION.
  
 24A) 709.3 FIRE-RESISTANCE RATING. A1
 HOUR FIRE-RESISTANCE RATING IS REQUIRED
 FOR SMOKE BARRIERS.
  
 24B) 710.5.2 SMOKE AND DRAFT-CONTROL
 DOORS. WHERE REQUIRED ELSEWHERE IN THE
 CODE, DOORS IN SMOKE PARTITIONS SHALL BE
 TESTED IN ACCORDANCE WITH UL 1784 WITH
 AN ARTIFICIAL BOTTOM SEAL INSTALLED
 ACROSS THE FULL WIDTH OF THE BOTTOM OF
 THE DOOR ASSEMBLY.
  
 24C) DOOR A-129 STYLE"K" IS LOUVER THIS
 CORRIDOR TO BE 1HR RATED, CORRECT
  
 24D) DOOR 104,107, 110 & 112 FOR 2ND
 FLOOR & ABOVE WILL ALL REQUIRE RATED
 DOORS IN CORRIDOR.
  
 25) 1406.2.2 ARCHITECTURAL TRIM THAT
 EXCEEDS 40 FT IN HEIGHTABOVE GRADE
 SHALL BE CONSTRUCTED OF APPROVED
 NONCOMBUSTIBLE MATERIALS. SEE DEFINITION
 OF NON-COMBUSTIBLE MATERIAL.
  
 26) T-3 A5.1.5:
 26A) DETAILS SHOW A DROPPED CEILING OVER
 WALKWAYS WITH METAL FRAMING NO
 INDICATION AS TO THE ATTACHMENT TO THE
 DECK ABOVE, SPACING OF ATTACHMENET,
 GAUGE OR SIZE OF FRAMING OR SPACING OF
 FRAMING.
 26B) PLANS INDICATE THAT THE FINISH WILL
 BE A CEMENT PLASTER FINISH THIS MEANS A
 TRUE CEMENT PLASTER FINISH AND NOT EFIS?
 EFIS SYSTEMS INDICATE NOT TO BE USED ON
 HORIZONTAL SURFACES.
  
 27)FIRE SPRINKLER PLANS:
 27A)FS1.1 INDICATES THAT THERE IS NO
 FIRE PUMP LOCATED IN HIGHRISE TOWER# 3.
  
 403.8 & 911 BOTH DEAL WITH THE FIRE
 COMMAND CENTER WHICH REQUIRES BOTH A
 FIRE PUMP AND GENERATOR. FS.1 INDICATES
 A SHARED FIRE PUMP FOR THREE BUILDINGS,
 THE CODE ISN'T CLEAR AS TO IF THE FIRE
 PUMP CAN BE SHARED OF NOT. IN SPEAKING
 WITH THE FIRE REVIEWERS THIS MAY NOT BE
 AN ACCEPTABLE METHOD OR APPLICATION.
 THE PRESENT LOCATION OF THE FIRE PUMP IS
 IN A PARKING GARAGE THAT HASN'T EVEN
 APPLIED FOR A PERMIT. THE SECOND ISSUE
 WILL BE THE SIZE OF THE FIRE PUMP IF THE
 LOCATION IS ACCEPTED, PROVIDE THE
 DOCUMENTATION FOR THE SIZE OF THE FIRE
 PUMP REQUIRED FOR THE 3 BUILDINGS IT
 WILL SERVICE.
  
 28) T3 A2.1.1 DOESN'T INDICATE THE
 LOCATION OF THE EMERGENCY GENERATOR,
 403.10 A STANDBY POWER SYSTEM COMPLYING
 WITH 2702 SHALL BE PROVIDED FOR STANDBY
 POWER LOADS SPECIFIED IN SECTION
 403.10.2 AND ALSO NFPA 110 & 111.
  
 29) FS2.1 IS MISSING THE FIRE SPRINKLERS
 IN THE CORRIDORS THAT FRONT EACH UNIT.
 ALSO REMOVE THE LIGHTING SYMBLES THAT
 ARE LOCATED IN THE SAME CORRIDOR.
  
 30) SECTION 911.1 OF THE CODE DEALS WITH
 THE FIRE COMMAND CENTER AND THE
 ASSOCIATED SYSTEMS (15) THAT ARE
 REQUIRED FOR A HIGH RISE BUILDING.
 SUBMIT A LAYOUT OF THE FIRE COMMAND
 CENTER AND ALL FEATURES REQUIRED BY THE
 SECTION TO BE CONTAINED THEREIN SHALL BE
 SUBMITTED FOR APPROVAL PRIOR TO
 INSTALLATION.
  
 31)SHEET M2.5 HAS NO INDICATION OF A
 SMOKEPROOF EXIT ENCLOSURE, SEE 403.13
 ALSO SEE 1019.1.3 FOR REQUIRED
 VENTILATION, AND 909.20 FOR PRESSURIZED
 STAIRS.
  
 32)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  