Plan Review Notes
Plan Review Notes For Permit 05080658
Permit Number 05080658
Review Stop P
Sequence Number 2
Notes
Date Text
2005-09-07 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 FROM PREVIOUS REVIEW:
 3. INDICATE THE CLEAR FLOOR SPACE AT THE
 LAVATORY AND THE WATER CLOSET. FBC
 11-4.19.3 AND 11-4.16.2. - NOT ADDRESSED
 9. MIRRORS MUST COMPLY WITH FBC
 11-4.19.6. SHOWN AS 3'2" WHEN 3'4" IS
 REQUIRED.
 10. 11-4.24.4 DEPTH. EACH SINK SHALL BE
 A MAXIMUM OF 6-1/2" DEEP. - NO RESPONSE.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR
 FLOOR SPACE AT LEAST 30"X48" SHALL BE
 PROVIDED IN FRONT OF THE SINK TO ALLOW
 FORWARD APPROACH AND SHALL EXTEND A
 MAXIMUM OF 19" UNDERNEATH THE SINK. SEE
 FIG. 11-32. - NO RESPONSE NOTED.
 11-4.24.6 EXPOSED PIPES & SURFACES.
 HOT WATER AND DRAIN PIPES EXPOSED UNDER
 SINKS SHALL BE INSULATED OR OTHERWISE
 CONFIGURED SO AS TO PROTECT AGAINST
 CONTACT. THERE SHALL BE NO SHARP OR
 ABRASIVE SURFACES UNDER SINKS. - NO
 RESPONSE NOTED.
 11-4.24.7 FAUCETS. FAUCETS SHALL
 COMPLY WITH 11-4.27.4. LEVER-OPERATED,
 PUSH-TYPE, TOUCH-TYPE, OR ELECTRONICALLY
 CONTROLLED MENCHANISMS ARE ACCEPTABLE
 DESIGNS. - NO RESPONSE NOTED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]