| 2005-09-07 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 11 |
| | |
| | FROM PREVIOUS REVIEW: |
| | 3. INDICATE THE CLEAR FLOOR SPACE AT THE |
| | LAVATORY AND THE WATER CLOSET. FBC |
| | 11-4.19.3 AND 11-4.16.2. - NOT ADDRESSED |
| | 9. MIRRORS MUST COMPLY WITH FBC |
| | 11-4.19.6. SHOWN AS 3'2" WHEN 3'4" IS |
| | REQUIRED. |
| | 10. 11-4.24.4 DEPTH. EACH SINK SHALL BE |
| | A MAXIMUM OF 6-1/2" DEEP. - NO RESPONSE. |
| | 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR |
| | FLOOR SPACE AT LEAST 30"X48" SHALL BE |
| | PROVIDED IN FRONT OF THE SINK TO ALLOW |
| | FORWARD APPROACH AND SHALL EXTEND A |
| | MAXIMUM OF 19" UNDERNEATH THE SINK. SEE |
| | FIG. 11-32. - NO RESPONSE NOTED. |
| | 11-4.24.6 EXPOSED PIPES & SURFACES. |
| | HOT WATER AND DRAIN PIPES EXPOSED UNDER |
| | SINKS SHALL BE INSULATED OR OTHERWISE |
| | CONFIGURED SO AS TO PROTECT AGAINST |
| | CONTACT. THERE SHALL BE NO SHARP OR |
| | ABRASIVE SURFACES UNDER SINKS. - NO |
| | RESPONSE NOTED. |
| | 11-4.24.7 FAUCETS. FAUCETS SHALL |
| | COMPLY WITH 11-4.27.4. LEVER-OPERATED, |
| | PUSH-TYPE, TOUCH-TYPE, OR ELECTRONICALLY |
| | CONTROLLED MENCHANISMS ARE ACCEPTABLE |
| | DESIGNS. - NO RESPONSE NOTED. |
| | |