| Plan Review Notes For Permit 05080658 |
| Permit Number |
05080658 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-15 00:00:00 | **** UNSAT ****** | | | | | | PLEASE SEE PLANS ARE COMING BACK FOR | | | PLUYMB COMMENTS, PLEASE MAKE THE BELOW | | | CORRECTIONS AT THIS TIME. | | | | | | 1)NOTE: PLEASE SEE 2002NEC 210.8B3, | | | WHICHREQUIRES ALL 15- AND 20-AMPERE, | | | 125-VOLT RECEPTACLES IN NONDWELLING-TYPE | | | KITCHENS TO BE GFCI PROTECTED. THIS | | | REQUIREMENT APPLIES TO EACH AND EVERY | | | 15- AND 20-AMPERE, 125-VOLT KITCHEN | | | RECEPTACLE, WHETHER OR NOT THE | | | RECEPTACLE SERVES COUNTERTOP APPLIANCES. | | | | | | | | | 2)NOTE: PLEASE BE SURE ENIGINEER SIGNS | | | PLANS WITH LEGAL SIGNATURE AS IS ON | | | FILE. | | | SIGNATURE DOES NOT CORRELATE WITH FILE. | | | FS 471.025, FAC 61G15-16.002 | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|