2005-10-14 00:00:00.PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE CALCULATED LOAD EXCEEDS THE
 GENERATOR OUTPUT.
  
 2} THE MAINS ARE NOT GROUPED.
  
 3} THERE IS NO GENERATOR DISCONNECT PER
 225.31. THE TOGGLE SWITCH IS NOT SERVICE
 RATED.
  
 4} THE FEEDER WIRE MUST COMPLY WITH
 445.13. 115% OF NAMEPLATE.
  