| Plan Review Notes For Permit 05080656 |
| Permit Number |
05080656 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-10-14 00:00:00 | .PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE CALCULATED LOAD EXCEEDS THE | | | GENERATOR OUTPUT. | | | | | | 2} THE MAINS ARE NOT GROUPED. | | | | | | 3} THERE IS NO GENERATOR DISCONNECT PER | | | 225.31. THE TOGGLE SWITCH IS NOT SERVICE | | | RATED. | | | | | | 4} THE FEEDER WIRE MUST COMPLY WITH | | | 445.13. 115% OF NAMEPLATE. | | | | | | I WILL BE OUT UNTILL 10/24, I HAVE | | | DISCUSSED THIS WITH DEWEY, IF YOU HAVE | | | QUESTIONS BEFORE I RETURN PLEASE CALL | | | HIM AT 805-6717. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|