| Plan Review Notes For Permit 05080656 |
| Permit Number |
05080656 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-30 00:00:00 | MECH. PLAN REVIEW: | | | | | | 1. PLAN MUST INDICATE ANY BUILDING | | | OPENING, WINDOWS/DOOR/ROOF VENTS. | | | GENERATOR EXHAUST MUST BE TEN FEET | | | AWAY FROM ANY BUILDING OPENINGS, AND TEN | | | FEET AWAY FROM ADJACENT BUILDING | | | OPENINGS. | | | 2001 FBC/M 804.3.3 TERMINATION. | | | 2001 FBC SECTION 915 REQUIREMENT OF | | | NFPA 37 8.2.3.2 EXHAUST SYSTEM | | | TERMINATION. | | | | | | 2. LP GAS REQUIRE LICENSE | | | GAS CONTRACTOR AND MUST SUBMIT GAS | | | PIPING DRAWING WITH GAS PERMIT APP. | | | | | | 3. GENERATOR MANF. RECOMATIONS FOR | | | SERVICE CLEARANCE/VENELATION IN | | | FEET/INCHES IN ALL DIRECTIONS MUST ACCM. | | | GENERATOR PERMIT APP. NEC 70 110.3 B . | | | | | | PAT RAFTER 561/805/6728 OR 805/6719 | | | PATTY KRAUSS. | | | | | | PLEASE CALL IF THEAR ANY QUESTIONS. |
|