| 2005-08-23 00:00:00 | | | | PLEASE NOTE THAT LOAD CALCS INDICATE A | | | 2000VA WATER HEATER,SEE 220.18 AND THE | | | RANGE MUSTBE IN COMPLIANCE WITH 220.19. | | | | | | SEE 700.5 FOR LOADS @ 100%. THE GENERAL | | | LIGHTING LOAD MAY USE THE DEMAND FROM | | | TABLE 220.11. | | | | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|