| Plan Review Notes For Permit 05080654 |
| Permit Number |
05080654 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-15 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} CIRCUITS 22,24,26,27 & 28 IN PANEL | | | "A", CIRCUITS 29,30,33,34,35 AND 36 IN | | | PANEL "B" HAVE #14 WIRE ON A 20 AMP | | | BREAKER IN VIOLATION OF 310.16 AND | | | 240.4(D). | | | | | | 2} BATH RECEPTACLES MUST COMPLY WITH | | | 210.11(C)(3), 20 AMP(#12). INDICATE SAME | | | ON THE PANEL SCHEDULE. | | | | | | 3} INDICATE THE LOCATION OF THE SERVICE | | | DISCONNECT ON THE PLAN. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|