| 2005-09-14 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT. |
| | |
| | 2- IMPACT FEES PAID RECEIPT SUBMITTED |
| | PR#05040709 DOESN'T MATCH PR# STAMPED ON |
| | PLANS. REVISE AS REQUIRED. |
| | |
| | 3- ENERGY CALCS ARE GETTING THE CEILING |
| | FAN CREDIT. THEREFORE, NEED TO SPECIFY |
| | CEILING FAN SIZES IN THE ELECTRICAL |
| | PLAN, INCLUDING FANS REQUIRED IN THE |
| | GREAT ROOM. SEE TABLE 6-6 CHAPTER 13 FBC |
| | |
| | 4- ROOF FRAMING PLAN NEEDS TO BE REVISED |
| | AT ENTRY PORCH AREA. CONCRETE BM DOESN'T |
| | EXTEND ALL THE WAY BACK TO THE FOYER. |
| | ALSO, REVISE THE KNEEWALL AT THE LEFT |
| | HAND SIDE OF THE ROOF. IT'S NOT CONCRETE |
| | BEAM. SEE PLANS AND REVISE FRAMING PLAN |
| | AS REQUIRED AND SPECIFY CORRESPONDING |
| | CONNECTOR. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 5- TRUSS ANCHOR SCHEDULE: REVISE NUMBER |
| | OF NAILS FOR HUS26. SEE 2005 CATALOGUE. |
| | |
| | 6- PROVIDE PRODUCT APPROVAL FOR: |
| | A)INSWING 1HR FIRE RATED DOOR AS SHOWN |
| | AT ATRIUM.PRODUCT APPROVAL SUBMITTED IS |
| | FOR "OUTSWING" APPLICATION. |
| | |
| | B) WINDOW MULLION SPECIED @ GREAT RM |
| | FIXED WINDOWS. |
| | |
| | C) 12'-0" SLIDING GLASS DOORS. |
| | |
| | 7- SPECIFY MULLION SIZE AND ANCHORS FOR |
| | FIXED WINDOWS AT GREAT ROOM. . SIZE |
| | SPECIFIED ON WINDOW SCHEDULE DOESN'T |
| | MEET THE CALCULATED DESIGN PRESSURES. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT (561)805-6712. |