Plan Review Notes
Plan Review Notes For Permit 05080560
Permit Number 05080560
Review Stop E
Sequence Number 4
Notes
Date Text
2006-04-24 00:00:00********* UNSAT *************
  
 1) NOTE: PLEASE CORRELATE SERVICE PANELS
 FEEDERS ETC.
 PLEASE SEE MDP IS NOW SHOWN AS 1-PHASE,
 HOWEVER MCB IS SHOWN AS 3-POLE?
 PLEASE SEE BRKRS FEEDING PANEL "PP" IS
 SHOWN AS 2 POLE FROM MDP , YET PANEL
 "PP" IS SHOWN AS CONTAINING A 3-POLE
 MCB?
 PLEASE SEE FEEDERS FROM MDP ARE SHOWN AS
 3-PHASE ON MDP AND SINGLE PHASE ON
 RISER?
 PLEASE CORRELATE ALL OF THE ABOVE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]