| 2006-04-24 00:00:00 | ********* UNSAT ************* | | | | | | 1) NOTE: PLEASE CORRELATE SERVICE PANELS | | | FEEDERS ETC. | | | PLEASE SEE MDP IS NOW SHOWN AS 1-PHASE, | | | HOWEVER MCB IS SHOWN AS 3-POLE? | | | PLEASE SEE BRKRS FEEDING PANEL "PP" IS | | | SHOWN AS 2 POLE FROM MDP , YET PANEL | | | "PP" IS SHOWN AS CONTAINING A 3-POLE | | | MCB? | | | PLEASE SEE FEEDERS FROM MDP ARE SHOWN AS | | | 3-PHASE ON MDP AND SINGLE PHASE ON | | | RISER? | | | PLEASE CORRELATE ALL OF THE ABOVE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|