Plan Review Notes
Plan Review Notes For Permit 05080560
Permit Number 05080560
Review Stop E
Sequence Number 3
Notes
Date Text
2006-03-01 00:00:00************UNSAT ****************
  
 *** PLEASE SEE NEW ELECTRICAL PLANS ARE
 NOW BEING SUBMITTED WITH CHANGES TO
 PREVIOUS PLANS SUBMITTED.
 PLEASE SEE NOTES BELOW AS THERE HAVE
 BEEN MANY CHANGES.
  
 **************************************
  
 1)NOTE: PLEASE ONLY SUBMIT PLANS
 RELEVANT TO THE PERMIT APPLICATIONS
 SCOPE OF WORK. PLEASE SEE PERMIT
 APPLICATION IS FOR THE POOL PAVILION
 ONLY.
 PLEASE SEE PLANS NOW INDICATE A COMPLETE
 CHANGE IN THE "CLUBHOUSE" RISER DIAGRAM
 ETC.
 PLEASE SEE LOAD SUMMARY MENTIONS NEW
 PANEL "PP" TO BE LOCATED AT POOL
 PAVILION, HOWEVER PLANS DO NOT CORRELATE
 WITH THIS??
 PLEASE SEE THIS LOAD SUMMARY NOW
 INDICATES MORE THAN ONE MAIN AND NONE OF
 THESE ARE GROUPED.230.72 ETC
 PLEASE SEE THAT ANY REVISIONS TO
 "CLUBHOUSE" NEED TO BE SUBMITTED UNDER
 THAT PERMIT.
  
 2)NOTE: PLEASE SEE PLANS ARE STILL
 MISSING THE DISCONNECTING MEANS AT THE
 POOL PAVILION PER REQUIRED PER 225.31.
 ** PLEASE KNOW, THESE MAY BE SNAP
 SWITCHES IF SO
 DESIRED).
  
 3)NOTE: PLEASE SEE GROUNDING AT POOL
 PAVILION (WHICH IS A DETACHED STRUCTURE)
 TO BE PER 250.32.
  
 4)NOTE: PLEASE COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS FROM THESE SETS WHICH
 DO NOT HAVE TO DO WITH THIS PERMTI SCOPE
 OF WORK. PLEASE KNOW, THIS WILL HELP TO
 ALLEAVIATE ANY CONFUSION IN THE SCOPE OF
 WORK, PAPER, AND TO HELP IN EXPEDITING
 THIS PERMIT.
  
 5)NOTE: PLEASE SEE NOTICE OF COMMENCMENT
 SUBMITTED HAS EXPIRED PER FS 713.13
 PLEASE KNOW, A NEW RECORDED UPDATED NOC
 WILL BE REQUIRED BEFORE PICKING UP
 PERMIT.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]