| 2006-03-01 00:00:00 | ************UNSAT **************** |
| | |
| | *** PLEASE SEE NEW ELECTRICAL PLANS ARE |
| | NOW BEING SUBMITTED WITH CHANGES TO |
| | PREVIOUS PLANS SUBMITTED. |
| | PLEASE SEE NOTES BELOW AS THERE HAVE |
| | BEEN MANY CHANGES. |
| | |
| | ************************************** |
| | |
| | 1)NOTE: PLEASE ONLY SUBMIT PLANS |
| | RELEVANT TO THE PERMIT APPLICATIONS |
| | SCOPE OF WORK. PLEASE SEE PERMIT |
| | APPLICATION IS FOR THE POOL PAVILION |
| | ONLY. |
| | PLEASE SEE PLANS NOW INDICATE A COMPLETE |
| | CHANGE IN THE "CLUBHOUSE" RISER DIAGRAM |
| | ETC. |
| | PLEASE SEE LOAD SUMMARY MENTIONS NEW |
| | PANEL "PP" TO BE LOCATED AT POOL |
| | PAVILION, HOWEVER PLANS DO NOT CORRELATE |
| | WITH THIS?? |
| | PLEASE SEE THIS LOAD SUMMARY NOW |
| | INDICATES MORE THAN ONE MAIN AND NONE OF |
| | THESE ARE GROUPED.230.72 ETC |
| | PLEASE SEE THAT ANY REVISIONS TO |
| | "CLUBHOUSE" NEED TO BE SUBMITTED UNDER |
| | THAT PERMIT. |
| | |
| | 2)NOTE: PLEASE SEE PLANS ARE STILL |
| | MISSING THE DISCONNECTING MEANS AT THE |
| | POOL PAVILION PER REQUIRED PER 225.31. |
| | ** PLEASE KNOW, THESE MAY BE SNAP |
| | SWITCHES IF SO |
| | DESIRED). |
| | |
| | 3)NOTE: PLEASE SEE GROUNDING AT POOL |
| | PAVILION (WHICH IS A DETACHED STRUCTURE) |
| | TO BE PER 250.32. |
| | |
| | 4)NOTE: PLEASE COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS FROM THESE SETS WHICH |
| | DO NOT HAVE TO DO WITH THIS PERMTI SCOPE |
| | OF WORK. PLEASE KNOW, THIS WILL HELP TO |
| | ALLEAVIATE ANY CONFUSION IN THE SCOPE OF |
| | WORK, PAPER, AND TO HELP IN EXPEDITING |
| | THIS PERMIT. |
| | |
| | 5)NOTE: PLEASE SEE NOTICE OF COMMENCMENT |
| | SUBMITTED HAS EXPIRED PER FS 713.13 |
| | PLEASE KNOW, A NEW RECORDED UPDATED NOC |
| | WILL BE REQUIRED BEFORE PICKING UP |
| | PERMIT. |
| | |
| | ** PLEASE SUBMIT THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |