| 2006-03-14 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | COMMENTS FROM PREVIOUS TWO REVIEWS: |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | THE NOC PROVIDED IS EXPIRED (OVER A YEAR |
| | OLD WITH NO OTHER EXPIRATION DATE |
| | SPECIFIED).THIS COMMENT DOES NOT |
| | PREVENT THE PERMIT FROM BEING ISSUED, |
| | BUT A CURRENT VALID NOC MUST BE PROVIDED |
| | PRIOR TO PERMIT PICKUP.FS713.13 |
| | |
| | 2.)(FIRST REVIEW COMMENT) PROVIDE A |
| | SITE PLAN SO THAT CODE COMPLIANCE CAN BE |
| | DETERMINED, FBC TABLE 600, FBC CHAPTER |
| | 11 (ACCESSIBLE ROUTE). |
| | |
| | (SECOND REVIEW COMMENT) THE LETTER |
| | STATING THAT THE SITE PLAN IS |
| | ON FILE WITH THE CITY IS ACKNOWLEDGED. |
| | HOWEVER, THIS PERMIT APPLICATION IS TO |
| | SHOW CODE COMPLIANCE.PROVIDE A SITE |
| | PLAN AS REQUESTED.SHOW DISTANCE TO |
| | ADJACENT BUILDINGS (IF ANY), ACCESSIBLE |
| | ROUTE (WIDTH AND SLOPE) SO THAT CODE |
| | COMPLIANCE CAN BE DETERMINED. |
| | |
| | THIRD REVIEW COMMENT - NOT PROPERLY |
| | ADDRESSED.TWO SITE PLANS WERE |
| | SUBMITTED.ONE IS AN REDUCED COPY OF A |
| | SITE PLAN PREPARED BY URBAN STUDIO |
| | DESIGN.THE OTHER FULL SIZE SHEET DOES |
| | NOT HAVE A TITLE BLOCK, AND IS NOT |
| | SIGNED AND SEALED.THE SITE PLAN MUST |
| | MUST BE A SIGNED, SEALED ORIGINAL |
| | FS481.306, FAC61G10-11.010 (LANDSCAPE |
| | ARCHITECT, SUBMITTED FOR PUBLIC RECORD). |
| | ALSO THE SITE PLAN DOES NOT SHOW THE |
| | REQUESTED INFORMATION TO DETERMINE CODE |
| | COMPLIANCE - SLOPE, SIDEWALK WIDTH, |
| | DISTANCE OF THIS STRUCTURE FROM OTHER |
| | STRUCTURES.FBC TABLE 600, FBC CHAPTER |
| | 11, FBC*104.3.1.1.THE NOTE THAT THE |
| | PLANS ARE ON FILE WITH THE CITY ARE |
| | AGAIN ACKNOWLEDGED, BUT THIS PERMIT |
| | PACKAGE IS TO SHOW CODE COMPLIANCE. |
| | |
| | A 4X PLAN REVIEW FEE HAS BEEN CHARGED, |
| | AND WILL BE CHARGED EVERY TIME THAT THIS |
| | PLAN IS RESUBMITTED WITHOUT ADDRESSING |
| | THE ABOVE CODE ISSUES RELATED TO |
| | ACCESSIBILITY AND FIRE RESISTANCE |
| | REQUIREMENTS. |