2005-08-15 00:00:00***** UNSAT ******
  
 1)NOTE: PLEASE SEE PERMIT APPLICATION IS
 FOR BLDG OF "POOL PAVILION" ONLY,
 HOWEVER PLANS SUBMITTED SHOWS , POOL
 EQUIPMENT, POOL PANEL ETC.
 PLEASE ONLY SUBMIT ELECTRICAL PERTAINING
 TO POOL PAVILION. PLEASE SEE "POOL "
 WILL BE UNDER SEPARATE PERMIT.
  
 2)NOTE: PLEASE SEE 225.31, A MEANS OF
 DISCONNECT WILL BE REQUIRED FOR CIRCUITS
 TO DETACHED STRUCTURE.
 **PLEASE SEE THIS MAY BE DONE BY MEANS
 OF SP/DP ETC SWITCHES.
  
 3)NOTE: PLEASE SEE 250.32 FOR GROUNDING
 AT DETACHED STRUCTURE.
  
 PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENTS FROM OTHER REVIEWER(S) WHICH
 MAY AFFECT ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE .
  