| Plan Review Notes For Permit 05080560 |
| Permit Number |
05080560 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-15 00:00:00 | ***** UNSAT ****** | | | | | | 1)NOTE: PLEASE SEE PERMIT APPLICATION IS | | | FOR BLDG OF "POOL PAVILION" ONLY, | | | HOWEVER PLANS SUBMITTED SHOWS , POOL | | | EQUIPMENT, POOL PANEL ETC. | | | PLEASE ONLY SUBMIT ELECTRICAL PERTAINING | | | TO POOL PAVILION. PLEASE SEE "POOL " | | | WILL BE UNDER SEPARATE PERMIT. | | | | | | 2)NOTE: PLEASE SEE 225.31, A MEANS OF | | | DISCONNECT WILL BE REQUIRED FOR CIRCUITS | | | TO DETACHED STRUCTURE. | | | **PLEASE SEE THIS MAY BE DONE BY MEANS | | | OF SP/DP ETC SWITCHES. | | | | | | 3)NOTE: PLEASE SEE 250.32 FOR GROUNDING | | | AT DETACHED STRUCTURE. | | | | | | PLEASE BE SURE TO SEE ANY POSSIBLE | | | COMMENTS FROM OTHER REVIEWER(S) WHICH | | | MAY AFFECT ELECTRICAL PLANS. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE . | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|