| Plan Review Notes For Permit 05080524 |
| Permit Number |
05080524 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2005-09-15 00:00:00 | PROVISO: | | | 1.PER 2004 FBC TABLE 1016.1; OCCUPANCY | | | EC INDICATES IN BUILDINGS PROTECTED | | | THROUGHOUT BY AN APPROVED, SUPERVISED | | | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE | | | WITH SECTION 903, CORRIDORS ARE NOT | | | REQUIRED TO HAVE FIRE RATED SO LONG AS | | | SUCH WALLS FORM SMOKE PARTITIONS IN | | | ACCORDANCE WITH THE FBC.PLEASE | | | INDICATE SMOKE DAMPERS IN ACCORDANCE | | | WITH 2004 FMC 607.3.2, SHOULD DUCT | | | PENETRATE SMOKE CORRIDOR. | | | | | | 2.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | REQUIRED PER 2004 FMC 606.2.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|