Plan Review Notes
Plan Review Notes For Permit 05080524
Permit Number 05080524
Review Stop M
Sequence Number 4
Notes
Date Text
2005-09-15 00:00:00PROVISO:
 1.PER 2004 FBC TABLE 1016.1; OCCUPANCY
 EC INDICATES IN BUILDINGS PROTECTED
 THROUGHOUT BY AN APPROVED, SUPERVISED
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH SECTION 903, CORRIDORS ARE NOT
 REQUIRED TO HAVE FIRE RATED SO LONG AS
 SUCH WALLS FORM SMOKE PARTITIONS IN
 ACCORDANCE WITH THE FBC.PLEASE
 INDICATE SMOKE DAMPERS IN ACCORDANCE
 WITH 2004 FMC 607.3.2, SHOULD DUCT
 PENETRATE SMOKE CORRIDOR.
  
 2.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 REQUIRED PER 2004 FMC 606.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.