| Plan Review Notes For Permit 05080524 |
| Permit Number |
05080524 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-09-01 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1. SHT A-1 DETAIL 1 SINK DETAIL KNEE | | | CLEARANCE TO BE 27" NOT 47". SECTION | | | 11-4.24.3.DETAIL 2 LAV CLEARANCE TO BE | | | 29" NOT 47". SECTION 11-4.19.2. DETAIL 2 | | | THE FLUSH CONTROLS SHALL BE LOCATED ON | | | THE WIDE SIDE OF THE TOILET, (AWAY FROM | | | THE WALL). SECTION 11-4.16.5 | | | 2. SHT A-2 ONLY THE FIXTURES WITHIN THE | | | BATHROOM GROUPS SHALL CONNECT TO THE | | | WET-VENTED HORIZONTAL BRANCH DRAIN. ANY | | | ADDITIONAL FIXTURES SHALL DISCHARGE | | | DOWNSTREAM OF THE WET VENT. SECTION | | | 909.1 THE MOP SINK, THE DRINKING | | | FOUNTAIN, AND THE BREAKROOM SINK SHALL | | | CONNECT DOWNSTREAM OF THE BATHROOM | | | FIXTURES, NOT ON THE STACK WITH THE LAVS | | | ON THE SANITARY RISER DIAGRAMS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | |
|