Plan Review Notes
Plan Review Notes For Permit 05080524
Permit Number 05080524
Review Stop P
Sequence Number 3
Notes
Date Text
2005-09-01 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1. SHT A-1 DETAIL 1 SINK DETAIL KNEE
 CLEARANCE TO BE 27" NOT 47". SECTION
 11-4.24.3.DETAIL 2 LAV CLEARANCE TO BE
 29" NOT 47". SECTION 11-4.19.2. DETAIL 2
 THE FLUSH CONTROLS SHALL BE LOCATED ON
 THE WIDE SIDE OF THE TOILET, (AWAY FROM
 THE WALL). SECTION 11-4.16.5
 2. SHT A-2 ONLY THE FIXTURES WITHIN THE
 BATHROOM GROUPS SHALL CONNECT TO THE
 WET-VENTED HORIZONTAL BRANCH DRAIN. ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT. SECTION
 909.1 THE MOP SINK, THE DRINKING
 FOUNTAIN, AND THE BREAKROOM SINK SHALL
 CONNECT DOWNSTREAM OF THE BATHROOM
 FIXTURES, NOT ON THE STACK WITH THE LAVS
 ON THE SANITARY RISER DIAGRAMS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  