| Plan Review Notes For Permit 05080524 |
| Permit Number |
05080524 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-09-01 00:00:00 | DENIED: 2ND REQUEST | | | COMMENT #1:OUTSIDE AIR CALCULATIONS | | | WILL BE REQUIRED DUE TO THE CHANGE OF | | | OCCUPANCY.OUTSIDE AIR CALCULATIONS | | | SHALL BE BASED ON 2004 FBC(M) TABLE | | | 403.3. | | | | | | COMMENT #3:PROVIDE DUCT & GRILLE SIZE, | | | MATERIAL, AND LAYOUT. | | | | | | NEW COMMENT:INDICATE ANY AND ALL FIRE | | | DAMPERS.FIRE DAMPERS ARE REQUIRED ON | | | DUCTS PENETRATING FIRE RATED PARTITIONS | | | OR WALLS.INDICATE LOCATION OF FIRE | | | DAMPERS IN ACCORDANCE WITH 2004 | | | FBC(M)607. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|