Plan Review Notes For Permit 05080524
Permit Number 05080524
Review Stop M
Sequence Number 3
Notes
Date Text
2005-09-01 00:00:00DENIED: 2ND REQUEST
 COMMENT #1:OUTSIDE AIR CALCULATIONS
 WILL BE REQUIRED DUE TO THE CHANGE OF
 OCCUPANCY.OUTSIDE AIR CALCULATIONS
 SHALL BE BASED ON 2004 FBC(M) TABLE
 403.3.
  
 COMMENT #3:PROVIDE DUCT & GRILLE SIZE,
 MATERIAL, AND LAYOUT.
  
 NEW COMMENT:INDICATE ANY AND ALL FIRE
 DAMPERS.FIRE DAMPERS ARE REQUIRED ON
 DUCTS PENETRATING FIRE RATED PARTITIONS
 OR WALLS.INDICATE LOCATION OF FIRE
 DAMPERS IN ACCORDANCE WITH 2004
 FBC(M)607.
  