| Plan Review Notes For Permit 05080524 |
| Permit Number |
05080524 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-08-19 00:00:00 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | | | | FROM PREVIOUS REVIEW: | | | 4. THE BREAK ROOM SINK SHALL BE | | | ACCESSIBLE. NEW SINK NOTED. PLEASE | | | SUBMIT A DETAIL SHOWING THE FOLLOWING: | | | B. 11-4.24.3 KNEE CLEARANCE | | | C. 11-4.24.4 SINK DEPTH | | | E. 11-4.24.6 EXPOSED PIPES & SURFACES | | | D. 11-4.24.7 FAUCETS | | | 5. FOR DRINKING FOUNTAINS: | | | C. 11-4.15.4 CONTROLS | | | 6. FOR W/C'S | | | D. 11-4.16.5 FLUSH CONTROLS | | | FOR LAVS | | | C. 11-4.19.4 EXPOSED PIPES & SURFACES | | | D. 11-4.19.5 FAUCETS | | | 8. SUBMIT A SANITARY RISER DIAGRAM | | | SHOWING ALL PIPE SIZES, VENTS, TRAPS, | | | AND POINTS OF CONNECTION. SECTION | | | 106.3.5.1.3. | | | 9. SUBMIT A WATER ISOMETRIC RISER | | | DIAGRAM SHOWING ALL PIPE SIZES, VALVES, | | | WATER HAMMER ARRESTORS IF REQUIRED BY | | | SECTION 604.9, AND POINTS OF CONNTECTION | | | . | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|