| Notes |
| Date |
Text |
| 2005-08-22 00:00:00 | DENIED: | | | PLEASE ADDRESS COMMENTS DATED 8-11-05, | | | ALSO PER OUR MEETING. | | | | | | 1.OUTSIDE AIR CALCULATIONS WILLBE | | | REQUIRED DUE TO THE CHANGE IN OCCUPANCY. | | | | | | 2.PLEASE ANNOTATE EXISTING EQUIPMENT | | | ON PLAN. | | | | | | 3.PLAN INDICATES "NEW CLASSROOMS", | | | PLEASE INDICATE ANY NEW DUCTWORK. | | | PLEASE ANNOTATE IF NO MODIFICATIONS TO | | | THE DUCT ARE REQUIRED.PLEASE NOTE, | | | RETURN AIR REQUIRED FROM ALL ROOMS | | | SEPARATED FROM THE CENTRAL RETURN BY A | | | DOOR (2004 FBC(M)601.4).SHOULD RETURN | | | BE A PLENUM, NO COMBUSTIBLES ALLOWED IN | | | A RETURN AIR PLENUM PER 2004 FBC(M) | | | 602.2.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|