2005-08-22 00:00:00DENIED:
 PLEASE ADDRESS COMMENTS DATED 8-11-05,
 ALSO PER OUR MEETING.
  
 1.OUTSIDE AIR CALCULATIONS WILLBE
 REQUIRED DUE TO THE CHANGE IN OCCUPANCY.
  
 2.PLEASE ANNOTATE EXISTING EQUIPMENT
 ON PLAN.
  
 3.PLAN INDICATES "NEW CLASSROOMS",
 PLEASE INDICATE ANY NEW DUCTWORK.
 PLEASE ANNOTATE IF NO MODIFICATIONS TO
 THE DUCT ARE REQUIRED.PLEASE NOTE,
 RETURN AIR REQUIRED FROM ALL ROOMS
 SEPARATED FROM THE CENTRAL RETURN BY A
 DOOR (2004 FBC(M)601.4).SHOULD RETURN
 BE A PLENUM, NO COMBUSTIBLES ALLOWED IN
 A RETURN AIR PLENUM PER 2004 FBC(M)
 602.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.