| Plan Review Notes For Permit 05080524 |
| Permit Number |
05080524 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-08-18 00:00:00 | ******DENIED****** | | | | | | 1) PLEASE NOTE THAT THE PREVIOUS FIRE | | | REVIEW INDICATED THAT SEPARATE SHOP | | | DRAWINGS AND PERMIT FOR THE FIRE | | | SPRINKLER SYSTEM IS REQUIRED. FIRE | | | SPRINKLER DRAWINGS HAVE BEEN SUBMITTED | | | UNDER THE MASTER PERMIT. PLEASE HAVE | | | CALCULATION SHEETS INCLUDED WHEN | | | SUBMITTING FOR FIRE SPRINKLER REVIEW. | | | | | | 2) PLEASE INCLUDE EXISTING LOCATION OF | | | FDC AND DOUBLE DETECTOR CHECK ASSEMBLY | | | WHEN FIRE SPRINKLER PACKAGE IS | | | SUBMITTED. | | | | | | 3) PLEASE NOTE THAT PLANS ARE STILL | | | SHOWING EXIT ACCESS CORRIDOR WIDTH TO BE | | | LESS THAN THE MINIMUM REQUIREMENT OF 72" | | | IN ACCORDANCE WITH NFPA 101, SECTION | | | 14.2.3.2. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|