Plan Review Notes
Plan Review Notes For Permit 05080524
Permit Number 05080524
Review Stop P
Sequence Number 1
Notes
Date Text
2005-08-11 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS, AND LICENSE NUMBER
 ON EACH SHEET. (SEE SHEET A-1)
 2. SHT A-1 GENERAL BLDG CODE ANALSYS
 READS FBC-2001, BUT PLANS WERE TO BE
 DESIGNED TO FBC-2004. PLEASE CLARIFY.
 3. SHT A-1 KITCHEN SPACE INDICATED IN
 MEANS OF EGRESS AND OCCUPANT LOAD
 SECTIONS OF CODE ANALSYS, BUT KITCHEN
 SPACE NOT FOUND ON PLANS. PLEASE
 INDICATE IF THE BREAKROOM IS THE SAME
 ROOM. SECTION 106.1.1.
 4. SHT A-1 BREAKROOM SINK BE ACCESSIBLE
 AND SHALL COMPLY WITH SECTION 11-4.24
 AND ALL SUBSECTIONS. PLEASE SUBMIT A
 DETAIL SHOWING THE FOLLOWING:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.5 CLEAR FLOOR SPACE. FORWARD
 APPROACH IS REQUIRED AND SHALL EXTEND A
 MAX. 19" UNDERNEATH THE SINK. CABINET
 DOORS ARE NOT APPROVED IN THE CLEAR
 FLOOR SPACE.
 E. 11-4.24.6 EXPOSED PIPES & SURFACES
 D. 11-4.24.7 FAUCETS
 5. SHT A-1 PER TABLE 403.1 2 DRINKING
 FOUNTAINS ARE REQUIRED. - INDICATE
 LOCATION OF FIXTURES AND SUBMIT A DETAIL
 SHOWING THE FOLLOWING:
 A. 11-4.15.2 SPOUT HEIGHT
 B. 11-4.15.3 SPOUT LOCTION
 C. 11-4.15.4 CONTROLS
 D. 11-4.15.5 CLEARANCES/CLEAR FLOOR
 SPACE.
 E. 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING.
 6. SHT A-1 ACCESSIBLE TOILET ROOM.
 SUBMIT A DETAIL SHOWING THE FOLLOWING:
 FOR W/C'S
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT
 C. 11-4.16.4 GRAB BARS
 D. 11-4.16.5 FLUSH CONTROLS
 E. 11-4.16.6 DISPENSERS
 FOR LAVS
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS
 E. 11-4.19.6 MIRRORS
 FOR TOILET ROOMS - SECTION 11-4.22 AND
 ALL SUBSECTIONS.
 7. AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE, AND SHALL BE THE SAME
 SIZE AS THE WATER SERVICE. TABLE
 603.1(D) AND SECTION 606.8.13.2
 8. SUBMIT A SANITARY RISER DIAGRAM
 SHOWING ALL PIPE SIZES, VENTS, TRAPS AND
 POINT OF CONNECTION. SECTION 106.3.5.1.3
 9. SUBMIT A WATER ISOMETRIC RISER
 DIAGRAM SHOWING ALL PIPE SIZES, VALVES,
 WATER HAMMER ARRESTORS IF REQUIRED BY
 SECTION 604.9, AND POINT OF CONNECTION.
 10. PER TABLE 403.1 A SERVICE SINK IS
 REQUIRED.
 11. PLEASE INDICATE THE AGES OF THE
 STUDENTS IN THE SCHOOL. REQUIREMENTS FOR
 DIFFERENT AGE GROUPS SHALL BE PER THE
 ACCESS BOARD RECOMMENDATIONS. (SEE
 BUILDING ELEMENTS FOR CHILDREN: ADAAG
 AMENDMENTS)
 WWW.ACCESS-BOARD.GOV/INDEXES/PUBSINDEX.
 HTM
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]