Text |
| 2005-08-11 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. ENGINEERS SHALL LEGIBLY INDICATE |
| | THEIR NAME, ADDRESS, AND LICENSE NUMBER |
| | ON EACH SHEET. (SEE SHEET A-1) |
| | 2. SHT A-1 GENERAL BLDG CODE ANALSYS |
| | READS FBC-2001, BUT PLANS WERE TO BE |
| | DESIGNED TO FBC-2004. PLEASE CLARIFY. |
| | 3. SHT A-1 KITCHEN SPACE INDICATED IN |
| | MEANS OF EGRESS AND OCCUPANT LOAD |
| | SECTIONS OF CODE ANALSYS, BUT KITCHEN |
| | SPACE NOT FOUND ON PLANS. PLEASE |
| | INDICATE IF THE BREAKROOM IS THE SAME |
| | ROOM. SECTION 106.1.1. |
| | 4. SHT A-1 BREAKROOM SINK BE ACCESSIBLE |
| | AND SHALL COMPLY WITH SECTION 11-4.24 |
| | AND ALL SUBSECTIONS. PLEASE SUBMIT A |
| | DETAIL SHOWING THE FOLLOWING: |
| | A. 11-4.24.2 HEIGHT |
| | B. 11-4.24.3 KNEE CLEARANCE |
| | C. 11-4.24.4 SINK DEPTH |
| | D. 11-4.24.5 CLEAR FLOOR SPACE. FORWARD |
| | APPROACH IS REQUIRED AND SHALL EXTEND A |
| | MAX. 19" UNDERNEATH THE SINK. CABINET |
| | DOORS ARE NOT APPROVED IN THE CLEAR |
| | FLOOR SPACE. |
| | E. 11-4.24.6 EXPOSED PIPES & SURFACES |
| | D. 11-4.24.7 FAUCETS |
| | 5. SHT A-1 PER TABLE 403.1 2 DRINKING |
| | FOUNTAINS ARE REQUIRED. - INDICATE |
| | LOCATION OF FIXTURES AND SUBMIT A DETAIL |
| | SHOWING THE FOLLOWING: |
| | A. 11-4.15.2 SPOUT HEIGHT |
| | B. 11-4.15.3 SPOUT LOCTION |
| | C. 11-4.15.4 CONTROLS |
| | D. 11-4.15.5 CLEARANCES/CLEAR FLOOR |
| | SPACE. |
| | E. 11-4.1.3(10)(A) PROVISIONS FOR THOSE |
| | WHO HAVE DIFFICULTY BENDING OR STOOPING. |
| | 6. SHT A-1 ACCESSIBLE TOILET ROOM. |
| | SUBMIT A DETAIL SHOWING THE FOLLOWING: |
| | FOR W/C'S |
| | A. 11-4.16.2 CLEAR FLOOR SPACE |
| | B. 11-4.16.3 HEIGHT |
| | C. 11-4.16.4 GRAB BARS |
| | D. 11-4.16.5 FLUSH CONTROLS |
| | E. 11-4.16.6 DISPENSERS |
| | FOR LAVS |
| | A. 11-4.19.2 HEIGHT & CLEARANCES |
| | B. 11-4.19.3 CLEAR FLOOR SPACE |
| | C. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | D. 11-4.19.5 FAUCETS |
| | E. 11-4.19.6 MIRRORS |
| | FOR TOILET ROOMS - SECTION 11-4.22 AND |
| | ALL SUBSECTIONS. |
| | 7. AN RPZ BACKFLOW IS REQUIRED ON THE |
| | WATER SERVICE, AND SHALL BE THE SAME |
| | SIZE AS THE WATER SERVICE. TABLE |
| | 603.1(D) AND SECTION 606.8.13.2 |
| | 8. SUBMIT A SANITARY RISER DIAGRAM |
| | SHOWING ALL PIPE SIZES, VENTS, TRAPS AND |
| | POINT OF CONNECTION. SECTION 106.3.5.1.3 |
| | 9. SUBMIT A WATER ISOMETRIC RISER |
| | DIAGRAM SHOWING ALL PIPE SIZES, VALVES, |
| | WATER HAMMER ARRESTORS IF REQUIRED BY |
| | SECTION 604.9, AND POINT OF CONNECTION. |
| | 10. PER TABLE 403.1 A SERVICE SINK IS |
| | REQUIRED. |
| | 11. PLEASE INDICATE THE AGES OF THE |
| | STUDENTS IN THE SCHOOL. REQUIREMENTS FOR |
| | DIFFERENT AGE GROUPS SHALL BE PER THE |
| | ACCESS BOARD RECOMMENDATIONS. (SEE |
| | BUILDING ELEMENTS FOR CHILDREN: ADAAG |
| | AMENDMENTS) |
| | WWW.ACCESS-BOARD.GOV/INDEXES/PUBSINDEX. |
| | HTM |
| | |
| | |