| 2005-08-11 00:00:00 | DENIED:REVIEWED UNDER 2004 FBC |
| | NO MECHANICAL PLANS OR ANALYSIS |
| | SUBMITTED FOR REVIEW.PLEASE PROVIDE |
| | THE FOLLOWING INFORMATION. |
| | |
| | 1.PLEASE INDICATE EXISTING HVAC & |
| | EXHAUST SYSTEMS IN ACCORDANCE WITH 2004 |
| | FBC(M)401.3.PLEASE NOTE, CORRIDORS |
| | SHALL NOT BE USED AS RETURN AIR PLENUMS |
| | PER 2004 FBC 423.15.2. |
| | |
| | 2.PROVIDE EQUIPMENT SCHEDULE (NEW OR |
| | EXISTING). |
| | |
| | 3.INDICATE ANY NEW WORK OR |
| | MODIFICATIONS TO DUCT & GRILLE LAYOUT. |
| | |
| | 4.PLANS DO NOT INDICATE FIRE RATING OF |
| | WALLS, PARTITIONS OR SEPARATION |
| | REQUIREMENTS.PLEASE PROVIDE DETAILS |
| | FOR PENETRATIONS. |
| | |
| | 5.PROVIDE OUTSIDE AIR CALCULATIONS PER |
| | 2004 FBC(M) TABLE 403.3. |
| | |
| | 6.BATHROOM EXHAUST SHALL BE A MINIMUM |
| | OF 50 CFM PER WATER CLOSET OR URINAL. |
| | BATHROOMSSHALL BE CONTINUOUSLY |
| | VENTILATED DURING OCCUPANCYOR COMPLY |
| | WITH THE EXCEPTION UNDER 2004 FBC |
| | 423.15.4. |
| | |
| | 7.PLEASE NOTE PLAN INDICATES THE |
| | GENERAL BUILDING CODE ANALYSIS IS UNDER |
| | THE 2001 FBC NOT THE 2004 FBC IN WHICH |
| | THE PERMIT APPLICATION INDICATES. |
| | PLEASE CLARIFY. |
| | |