| Plan Review Notes For Permit 05080524 |
| Permit Number |
05080524 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-10 00:00:00 | ******DENIED****** | | | | | | 1) EXIT ACCESS CORRIDORS SHALL BE NOT | | | LESS THAN 72" IN CLEAR WIDTH. NFPA 101, | | | SECTION 14.2.3.2. | | | | | | 2) IN ADDITION TO THE FBC, LIFE SAFETY | | | TO COMPLY WITH NFPA 101, 2003 EDITION. | | | | | | 3) PLEASE NOTE THAT MAXIMUM TRAVEL | | | DISTANCE SHALL NOT EXCEED 200' IN | | | EDUCATIONAL OCCUPANCIES PROTECTED | | | THROUGHOUT WITH AN AUTOMATIC FIRE | | | SPRINKLER SYSTEM. | | | | | | 4) PANIC HARDWARE IS REQUIRED ON EXIT | | | DOORS SERVING AREAS OF GREATER THAN 100 | | | PERSONS. | | | | | | 5) PLEASE INDICATE THE SEPARATION | | | REQUIREMENTS FOR CORRIDORS AND STORAGE | | | ROOMS. | | | | | | 6) PLEASE ILLUSTRATE THE MINIMUM | | | INTERIOR FINISH CLASSIFICATION FOR WALLS | | | AND CEILINGS. | | | | | | 7) FIRE ALARM PERMIT HAS BEEN ISSUED. | | | MONITORING SHALL BE UL CERTIFIED FOR | | | CENTRAL STATION SERVICE. | | | | | | 8) AN ADDRESS IS REQUIRED ON THE BUIDING | | | TO BE AT LEAST 6" IN HEIGHT AND | | | CONTRASTING TO THE BACKGROUND. PLEASE | | | ADVISE IF EXISTING OR NEW. | | | | | | 9) SEPARATE SHOP DRAWINGS AND PERMIT | | | REQUIRED FOR FIRE SPRINKLER REMODEL. | | | | | | | | | MIKE WENNERGREN, CAPTAIN | | | WPBFR(561) 804-4756 | | | FIRE PLAN REVIEW (561) 805-6722 |
|