2005-08-10 00:00:00******DENIED******
  
 1) EXIT ACCESS CORRIDORS SHALL BE NOT
 LESS THAN 72" IN CLEAR WIDTH. NFPA 101,
 SECTION 14.2.3.2.
  
 2) IN ADDITION TO THE FBC, LIFE SAFETY
 TO COMPLY WITH NFPA 101, 2003 EDITION.
  
 3) PLEASE NOTE THAT MAXIMUM TRAVEL
 DISTANCE SHALL NOT EXCEED 200' IN
 EDUCATIONAL OCCUPANCIES PROTECTED
 THROUGHOUT WITH AN AUTOMATIC FIRE
 SPRINKLER SYSTEM.
  
 4) PANIC HARDWARE IS REQUIRED ON EXIT
 DOORS SERVING AREAS OF GREATER THAN 100
 PERSONS.
  
 5) PLEASE INDICATE THE SEPARATION
 REQUIREMENTS FOR CORRIDORS AND STORAGE
 ROOMS.
  
 6) PLEASE ILLUSTRATE THE MINIMUM
 INTERIOR FINISH CLASSIFICATION FOR WALLS
 AND CEILINGS.
  
 7) FIRE ALARM PERMIT HAS BEEN ISSUED.
 MONITORING SHALL BE UL CERTIFIED FOR
 CENTRAL STATION SERVICE.
  
 8) AN ADDRESS IS REQUIRED ON THE BUIDING
 TO BE AT LEAST 6" IN HEIGHT AND
 CONTRASTING TO THE BACKGROUND. PLEASE
 ADVISE IF EXISTING OR NEW.
  
 9) SEPARATE SHOP DRAWINGS AND PERMIT
 REQUIRED FOR FIRE SPRINKLER REMODEL.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 804-4756
 FIRE PLAN REVIEW (561) 805-6722