Plan Review Notes
Plan Review Notes For Permit 05080524
Permit Number 05080524
Review Stop E
Sequence Number 1
Notes
Date Text
2005-08-10 00:00:00******** UNSAT *********
  
 1)NOTE: PLEASE SHOW CIRCUITING FOR
 EM/EXT LTS PER 700.12E THE BRANCH
 CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL
 BE THE SAME BRANCH CIRCUIT AS THAT
 SERVING THE NORMAL LIGHTING IN THE AREA
 AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES.
  
 2)NOTE: PLEASE SHOW LIGHTING LAYOUT FOR
 MEANS OF EGRESS ON PLANS.
 215.5
  
 3)NOTE: PLEASE CORRRELATE ELECTRICAL
 CONNECTIONS FOR NEW TRAILER/PORTABLE
 CLASSROOM.
 PLEASE SHOW WHICH LOCATION THIS WILL BE
 FED FROM. TWO PLANS SHOWING TWO
 DIFFERENT FEEDS WERE SUBMITTED.
 PLEASE PROVIDE LOAD CALCUALTIONS FOR
 EXISTING SERVICE. THIS SHALL INCLUDE ALL
 NEW LOADS TO BE ADDED ALONG WITH
 EXSITING
 LOADS.220.3,220.10,220.11,220.13 ETC.
 215.5
 PLEASE BE SURE ALL CONTINUOUS LOADS ARE
 SHOWN AT 125% ALONG WITH LARGEST MOTOR
 LOADS.
 215.3,230.42 ETC
  
 4)NOTE: PLEASE SHOW LOCATIONS OF ALL
 ELECTRICAL PANELS ON PLANS.
 PLEASE SEE THAT ANY ELECTRICAL PANELS ON
 INTERIOR/BATH ROOM SHALL BE EQUIPED WITH
 A LOCKING TYPE ELECTRICAL PANEL COVER.
  
 5)NOTE: ALL LIGHTING FIXTURES AT EXIST
 DISCHANGE AND MEANS OF EGREES TO THE
 OUTSIDE OF BLDG SHALL BE IN WORKING
 ORDER.
 LS101 14.2.8, 7-8
 THIS IS ONLY A NOTE FOR ALL FIXTURES TO
 COMPLY AT JOBSITE.
  
 6)NOTE: PLEASE SEE 2002 NEC 210.8B3 FOR
 KITCHENS IN OTHER THAN DWELLING UNITS
 WHICH REQUIRES ALL 15- AND 20-AMPERE,
 125-VOLT RECEPTACLES IN NONDWELLING-TYPE
 KITCHENS TO BE GFCI PROTECTED. THIS
 REQUIREMENT APPLIES TO EACH AND EVERY
 15- AND 20-AMPERE, 125-VOLT KITCHEN
 RECEPTACLE, WHETHER OR NOT THE
 RECEPTACLE SERVES COUNTERTOP APPLIANCES.
  
 PLEASE SEE OTHER POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved