| 2005-08-10 00:00:00 | ******** UNSAT ********* |
| | |
| | 1)NOTE: PLEASE SHOW CIRCUITING FOR |
| | EM/EXT LTS PER 700.12E THE BRANCH |
| | CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL |
| | BE THE SAME BRANCH CIRCUIT AS THAT |
| | SERVING THE NORMAL LIGHTING IN THE AREA |
| | AND CONNECTED AHEAD OF ANY LOCAL |
| | SWITCHES. |
| | |
| | 2)NOTE: PLEASE SHOW LIGHTING LAYOUT FOR |
| | MEANS OF EGRESS ON PLANS. |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE CORRRELATE ELECTRICAL |
| | CONNECTIONS FOR NEW TRAILER/PORTABLE |
| | CLASSROOM. |
| | PLEASE SHOW WHICH LOCATION THIS WILL BE |
| | FED FROM. TWO PLANS SHOWING TWO |
| | DIFFERENT FEEDS WERE SUBMITTED. |
| | PLEASE PROVIDE LOAD CALCUALTIONS FOR |
| | EXISTING SERVICE. THIS SHALL INCLUDE ALL |
| | NEW LOADS TO BE ADDED ALONG WITH |
| | EXSITING |
| | LOADS.220.3,220.10,220.11,220.13 ETC. |
| | 215.5 |
| | PLEASE BE SURE ALL CONTINUOUS LOADS ARE |
| | SHOWN AT 125% ALONG WITH LARGEST MOTOR |
| | LOADS. |
| | 215.3,230.42 ETC |
| | |
| | 4)NOTE: PLEASE SHOW LOCATIONS OF ALL |
| | ELECTRICAL PANELS ON PLANS. |
| | PLEASE SEE THAT ANY ELECTRICAL PANELS ON |
| | INTERIOR/BATH ROOM SHALL BE EQUIPED WITH |
| | A LOCKING TYPE ELECTRICAL PANEL COVER. |
| | |
| | 5)NOTE: ALL LIGHTING FIXTURES AT EXIST |
| | DISCHANGE AND MEANS OF EGREES TO THE |
| | OUTSIDE OF BLDG SHALL BE IN WORKING |
| | ORDER. |
| | LS101 14.2.8, 7-8 |
| | THIS IS ONLY A NOTE FOR ALL FIXTURES TO |
| | COMPLY AT JOBSITE. |
| | |
| | 6)NOTE: PLEASE SEE 2002 NEC 210.8B3 FOR |
| | KITCHENS IN OTHER THAN DWELLING UNITS |
| | WHICH REQUIRES ALL 15- AND 20-AMPERE, |
| | 125-VOLT RECEPTACLES IN NONDWELLING-TYPE |
| | KITCHENS TO BE GFCI PROTECTED. THIS |
| | REQUIREMENT APPLIES TO EACH AND EVERY |
| | 15- AND 20-AMPERE, 125-VOLT KITCHEN |
| | RECEPTACLE, WHETHER OR NOT THE |
| | RECEPTACLE SERVES COUNTERTOP APPLIANCES. |
| | |
| | PLEASE SEE OTHER POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |