| Date |
Text |
| 2005-08-10 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05080524 |
| | ADD: 5800 CORPORATE WAY |
| | CONT:LTL BUILDERS |
| | TEL: (561)628-9753 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) PLANS INDICATE DESIGN TO FL BLDG CODE |
| | 2001, IT WAS AGREED ON THAT THE DESIGN |
| | CRITERIA WOULD BE TO THE FL 2004 CODE. |
| | THE 2004 CODE WILL PROVIDE THE DESIGNER |
| | GREATER LATITUDES IN SESIGN. |
| | |
| | 3) UNDER THE 2004 CODE REVISIT THE |
| | MINIMUM BLDG TYPE FOR DESIGN.TABLE 503. |
| | |
| | 4A) SEE 110.1.2* REQUIREMENTS FOR |
| | CERTIFICATE OF OCCUPANCY SEE ITEMS 1-12. |
| | |
| | 4B) NOTE ITEM# 10 ON THE REQUIREMENTS |
| | FOR C. O. "THE DESIGN OCCUPANT LOAD".!!! |
| | THIS LIMITATION UNDER 1004.1.1 WILL |
| | ALLOW THE DESIGNER TO "LIMIT THE DESIGN |
| | LOAD". UNDER THIS EDITION OF THE CODE |
| | SEE SECTION 1016.2 CORRIDOR WIDTHS, |
| | MINIMUM CORRIDOR WIDTH SHALL BE AS |
| | DETERMINED IN 1005.1 BUT NOT LESS THAN |
| | 44" SEE EXCEPTIONS (4) 72" IN GROUP "E" |
| | WITH A OCCUPANT LOAD GREATER THAN 100, |
| | THE CORRIDOR WIDTHCAN BE 44" IF THE |
| | DESIGNER LIMITS THE OCCUPANT LOAD UNDER |
| | 100, EVEN THOUGH THE TOTAL SHOWN ON THE |
| | PLAN IS GREATER THAN 100. CORRECT PLAN |
| | TO REFLECT THE NEW "DESIGN OCCUPANT |
| | LOAD". |
| | |
| | 4C) INDICATE COMPLIANCE WITH CORRIDORS |
| | WITH TABLE 1016.1 WITH FIRE SPRINKLERS |
| | FOR WALLS AND DOORS.SEE FOOTNOTE "C". |
| | |
| | 5)THE COPY ROOM DOOR WILL NOT MAKE THE |
| | ACCESSIBILITY REQUIREMENTS 11-4.13.6 |
| | REQUIRING THE 18" ON THE PULL SIDE OF |
| | LATCH. |
| | |
| | 6) PLANS INDICATE A STORAGE AREA THAT |
| | COMMUNICATES WITH THE EXIT ACCESS |
| | CORRIDOR, NO SEPERATION? |
| | |
| | 7) AIR MOVEMENT IN CORRIDORS 1016.4. |
| | PROVIDE COMPLIANCE WITH EXIT ACCESS |
| | CORRIDORS SHALL NOT SERVE AS SUPPLY, |
| | RETURN, EXHAUST RELIEF OR VENTILATION |
| | AIR DUCTS, SEE EXCEPTIONS. |
| | |
| | 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |