| Plan Review Notes For Permit 05080522 |
| Permit Number |
05080522 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-09-28 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 05080522 | | | ADD: 8057 CRANES POINT WAY | | | CONT: DANIEL ELECTRIC | | | TEL: (561)848-9495 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2ND REVIEW | | | ACTION: DENIED | | | 1) GENERATOR SLAB & ANCHOR REQUIREMENT | | | PLEASE PROVIDE SIZE OF GENERATOR(WXL), | | | PLUS PROVIDE PLANS WITH THE INFORMATION | | | DEPICTING HOLD DOWN BRACKETS, TYPE OF | | | FASTENER, AND THE MINIMUM EDGE DISTANCE | | | THE DEVICE REQUIRES WITHOUT LOAD | | | REDUCTION. | | | | | | 2) SECOND, PROVIDE INFORMATION ON THE | | | SLAB, THICKNESS, WIDTH AND LENGTH, IF | | | WIREMESH, FIBER MESH OR IF STEEL REBAR | | | WILL BE USED. | | | DISCREPANCY IN INFORMATION, PAGES | | | FROM DANIEL ELECTRIC, AND INFORMATION ON | | | SURVEY DO NOT MATCH THE GENERATOR SIZE, | | | NO INFORMATION ON THE HOLD DOWN DEVICES | | | OR SLAB SIZE. | | | | | | 3) THE NEW SLAB AND HOLD DOWN DETAILS: | | | 104.2.1* ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA | | | SHALL BEAR THE NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR THE DESIGN. | | | | | | 4) PAGES SUBMITTED CORRELATE INTO (2) | | | SETS OF PLANS. | | | | | | | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | |
|