| Plan Review Notes For Permit 05080522 |
| Permit Number |
05080522 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-24 00:00:00 | MECH. PLAN REVIEW: | | | PROVISO: | | | 1. GENERATOR MANF. RECOMBINATION FOR | | | SERVICE CLERANCE / VENELATION IN | | | FEET/INCHES IN ALL DIRECTIONS MUST ACCM. | | | GENERATOR PERMIT APP.NEC 70110.3 B. | | | | | | 2. GENERATOR EXHAUST MUST BE TEN FEET | | | AWAY FROM BUILDING OPENINGS, AND EXHAUST | | | MUST BE DIRECTED AWAY FROM BUILDING. | | | AND BE TEN FEET FROM PROPETY LINE. | | | 2001 FBC/M 804.3.3 TERMINATION | | | 2001 FBC/MSECTION 9158.2.3.2 | | | EXHAUST SYSTEM TERMINATION. | | | | | | 3. LP/NAT GAS REQUIRES PERMIT, FROM | | | LICENSED GAS CONTRACTOR. | | | | | | PAT RAFTER 561/805/6728 OR 805/6719 | | | PATTY KRAUSS. | | | | | | PLEASE CALL IF THEAR ANY QUESTIONS. |
|