2005-10-06 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 COMMENTS FROM PREVIOUS TWO REVIEWS:
  
 1.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVALS REQUIRED FAC9B72.ALSO SUBMIT
 BACKUP DOCUMENTATION SUCH AS
 INSTALLATION INSTRUCTIONS AND EVALUATION
 REPORT.THE DOCUMENTS SUBMITTED ARE NOT
 LEGIBLE. (REVIEW 1)
  
 THE COPIES YOU SHOWED ME WERE LEGIBLE.
 THESE ARE NOT.YOU HAD FLORIDA STATE
 APPROVALS IN OUR MEETING; THEY ARE NOT
 IN THIS PACKAGE.I ATTEMPTED TO LOOK IT
 UP ONLINE FOR YOU BUT THIS COMPANY HAS
 TOO MANY DIFFERENT PRODUCTS FOR ME TO
 EASILY DETERMINE WHICH ONE YOU ARE
 USING.WWW.FLORIDABUILDING.ORG (REVIEW
 2)
  
 SAME ILLEGIBLE SHEET SUBMITTED WITHOUT
 PRODUCT APPROVAL.(REVIEW 3)
  
 2.)PROVIDE MEAN ROOF HEIGHT OF THE
 BUILDING.DESIGN PRESSURES FOR A HIGH
 RISE (OVER 60')ARE REQUIRED TO BE
 DETERMINED BY AN ENGINEER, FBC1606.1.1.
 DOCUMENTS PREPARED BY AN
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD
 ARE TO BE SIGNED SEALED ORIGINALS
 FAC61G15-23.002. (REVIEW 1)
  
 THIS NEEDS TO BE ADDRESSED ON THE PLAN
 OR PERMIT APPLICATION. (REVIEW 2)
  
 SAME COMMENTS STILL APPLY.THERE WAS A
 NOTE FROM THE CONTRACTOR, REFERRING TO
 THE WRONG UNIT, WITH THE MEAN ROOF
 HEIGHT AND A SPECIFICATION FOR
 INSTALLATION AND INSTALLATION
 CONDITIONS.THIS IS NOT ACCEPTABLE.
 THE CORRECTION REQUESTED FOR THE
 INFORMATION TO BE PUT ON THE PLAN OR ON
 THE APPLICATION. THE INSTALLATION IS TO
 BE IN ACCORDANCE WITH THE PRODUCT
 APPROVAL, WHICH WAS NOT PROVIDED(REVIEW
 3)
  
 NEW COMMENTS FROM SECOND REVIEW:
  
 3.)ONLY TWO SHEETS WERE PROVIDED.THE
 PRODUCT INFORMATION PROVIDED WERE FOR
 FACE MOUNT (WALL) INSTALLING INTO
 CONCRETE, HOLLOW BLOCK OR WOOD WALL.
 YOUR APPLICATION IS INTO A SLAB AT THE
 BOTTOM AND IT IS NOT CLEAR WHAT YOU ARE
 ANCHORING INTO ABOVE.THIS APPLICATION
 IS NOT IN THE SHEETS PROVIDED.THE
 SHEET SPECIFYING MINIMUM EDGE DISTANCE
 IS NOT IN THE TWO ILLEGIBLE SHEETS
 SUBMITTED. (SECOND REVIEW)
  
 THE PLAN SUBMITTED DOES NOT SHOW
 CONCRETE THICKNESS FOR EITHER THE SLAB
 OR THE BALCONY.ALL INFORMATION IS TO
 BE ON THE PLAN, NOT IN THE FORM OF A
 LETTER.THE NEW DRAWING IS FOR UNIT
 B307, NOT A103. IN OUR TELEPHONE
 CONVERSATION YOU STATED THAT THE PLAN
 B307 IS TO APPLY TO UNIT A103.THIS
 SHOULD BE CLEAR ON THE PLAN, BUT HOW CAN
 THE DETAIL AND CONCRETE THICKNESS BE THE
 SAME WHEN THE APPLICATIONS ARE
 DIFFERENT?THE DRAWING SHOWS ANCHORING
 INTO THE SLAB ABOVE, A WALL/RAILING AT
 THE BOTTOM.MY UNDERSTANDING IS THAT
 THE FIRST FLOOR IS TO BE INSTALLED
 ANCHORING INTO THE BALCONY ABOVE AND THE
 SLAB BELOW.THAT IS WHAT YOUR SECOND
 DRAWING SHOWS. (THIRD REVIEW)
  
 4.)ADDRESSED.
  
 5.)PROVIDE STRUCTURAL DETAILS FOR THE
 CONDITIONS FOR INSTALLATION; DIMENSIONS
 FOR SLAB BELOW AND BALCONY ABOVE.SEE
 GENERAL NOTE #5 ON THE PAPERWORK YOU
 PROVIDED IN REGARDS TO ENGINEERING BEING
 REQUIRED.
  
 NOT ADDRESSED.A DRAWING FOR UNIT B307
 WAS SUBMITTED INSTEAD OF A103.SEE
 COMMENT 3.
  
 NOTE - NOT ENOUGH INFORMATION PROVIDED
 TO DETERMINE CODE COMPLIANCE