| 2005-09-08 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | COMMENTS FROM PREVIOUS REVIEW: |
| | |
| | 1.)FLORIDA STATE OR LOCAL PRODUCT |
| | APPROVALS REQUIRED FAC9B72.ALSO SUBMIT |
| | BACKUP DOCUMENTATION SUCH AS |
| | INSTALLATION INSTRUCTIONS AND EVALUATION |
| | REPORT.THE DOCUMENTS SUBMITTED ARE NOT |
| | LEGIBLE. |
| | |
| | THE COPIES YOU SHOWED ME WERE LEGIBLE. |
| | THESE ARE NOT.YOU HAD FLORIDA STATE |
| | APPROVALS IN OUR MEETING; THEY ARE NOT |
| | IN THIS PACKAGE.I ATTEMPTED TO LOOK IT |
| | UP ONLINE FOR YOU BUT THIS COMPANY HAS |
| | TOO MANY DIFFERENT PRODUCTS FOR ME TO |
| | EASILY DETERMINE WHICH ONE YOU ARE |
| | USING.WWW.FLORIDABUILDING.ORG |
| | |
| | 2.)PROVIDE MEAN ROOF HEIGHT OF THE |
| | BUILDING.DESIGN PRESSURES FOR A HIGH |
| | RISE (OVER 60')ARE REQUIRED TO BE |
| | DETERMINED BY AN ENGINEER, FBC1606.1.1. |
| | DOCUMENTS PREPARED BY AN |
| | ENGINEER AND SUBMITTED FOR PUBLIC RECORD |
| | ARE TO BE SIGNED SEALED ORIGINALS |
| | FAC61G15-23.002. |
| | |
| | THIS NEEDS TO BE ADDRESSED ON THE PLAN |
| | OR PERMIT APPLICATION. |
| | |
| | NEW COMMENTS: |
| | |
| | 3.)ONLY TWO SHEETS WERE PROVIDED.THE |
| | PRODUCT INFORMATION PROVIDED WERE FOR |
| | FACE MOUNT (WALL) INSTALLING INTO |
| | CONCRETE, HOLLOW BLOCK OR WOOD WALL. |
| | YOUR APPLICATION IS INTO A SLAB AT THE |
| | BOTTOM AND IT IS NOT CLEAR WHAT YOU ARE |
| | ANCHORING INTO ABOVE.THIS APPLICATION |
| | IS NOT IN THE SHEETS PROVIDED.THE |
| | SHEET SPECIFYING MINIMUM EDGE DISTANCE |
| | IS NOT IN THE TWO ILLEGIBLE SHEETS |
| | SUBMITTED. |
| | |
| | 4.)PROVIDE A LETTER FROM THE HOA |
| | GIVING PERMISSION FOR THIS WORK TO BE |
| | DONE. |
| | |
| | 5.)PROVIDE STRUCTURAL DETAILS FOR THE |
| | CONDITIONS FOR INSTALLATION; DIMENSIONS |
| | FOR SLAB BELOW AND BALCONY ABOVE.SEE |
| | GENERAL NOTE #5 ON THE PAPERWORK YOU |
| | PROVIDED IN REGARDS TO ENGINEERING BEING |
| | REQUIRED. |
| | |
| | NOTE - NOT ENOUGH INFORMATION PROVIDED |
| | TO DETERMINE CODE COMPLIANCE |
| | |