| Plan Review Notes For Permit 05080507 |
| Permit Number |
05080507 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-09-07 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | FROM PREVIOUS REVIEW: | | | 1. SEE NOTES DATED 8-9-5 RMCDONALD | | | RE: HANDICAP REST ROOM DETAIL "A" | | | SHOW THE FOLLOWING: | | | FOR W/C'S: | | | 11-4.16.2 CLEAR FLOOR SPACE | | | 11-4.16.3 HEIGHT | | | 11-4.16.4 GRAB BARS | | | 11-4.16.5 FLUSH CONTROLS | | | 11-4.16.6 DISPENSERS | | | FOR LAV'S: | | | 11-4.19.2 HEIGHT & CLEARANCES | | | 11-4.19.3 CLEAR FLOOR SPACE | | | 11-4.19.4 EXPOSED PIPES & SURFACES | | | 11-4.19.5 FAUCETS | | | 11-4.19.6 MIRRORS | | | FOR TOILET ROOMS: | | | 11-4.22.3 UNOBSTRUCTED TURNING AREA | | | 2. 104.6.5 BUILDING PERMIT VALUATION OF | | | $1500.00 APPEARS TO BE UNDER ESTIMATED | | | ON THE APPLICATION. THE PERMIT WILL BE | | | DENIED UNLESS THE APPLICATION CAN SHOW A | | | BONAFIDE SIGNED CONTRACT. - ALTHOUGH THE | | | APPLICATION WAS INCREASED TO $2500.00, | | | NO CONTRACT SUBMITTED. | | | 3. SECTION 104.3.1.1 (104.2) DRAWINGS | | | AND SPECIFICATIONS: | | | SUBMIT DRAIN, WASTE AND VENT ISOMETRIC | | | AND A WATER PIPING ISOMETRIC. SHOW ALL | | | PIPE SIZES, TYPE OF MATERIAL, VALVES, | | | TRAPS AND POINTS OF CONNECTION. | | | ***************NEW COMMENT************* | | | 1B. PER TABLE 403.1 A DRINKING FOUNTAIN | | | IS REQUIRED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|