| Date |
Text |
| 2005-08-12 00:00:00 | DENIED |
| | |
| | 1) FBC 707.1 CONCEALED SPACES IN TYPES |
| | I, II AND IV CONSTRUCTION.COMBUSTIBLES |
| | SHALL NOT BE PERMITTED IN CONCEALED |
| | SPACES OF TYPES I, II OR IV |
| | CONSTRUCTION. BACKING IN WALLS CAN NOT |
| | BE COMBUSTIBLE MATERIALS. |
| | |
| | 2) FBC 1012.1.4 DURING ITS SWING, ANY |
| | DOOR IN A MEANS OF EGRESS SHALL LEAVE |
| | UNOBSTRUCTED AT LEAST ONE HALF OF THE |
| | REQUIRED WIDTH OF AN AISLE, CORRIDOR, |
| | PASSAGEWAY, OR LANDING, NOR PROJECT MORE |
| | THAN 7 IN.(17.8 CM)INTO THE REQUIRED |
| | WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY |
| | OR LANDING, WHEN FULLY OPEN.DOORS |
| | SHALL NOT OPEN IMMEDIATELY ONTO A STAIR |
| | WITHOUT A LANDING.THE LANDING SHALL |
| | HAVE A WIDTH AT LEAST EQUAL TO THE WIDTH |
| | OF THE DOOR SEE ?1021.3 FOR DOOR SWING |
| | IN GROUP E OCCUPANCIES. THE OFF SET |
| | SHOWN AT THE BATHROOM DOOR ON THE FLOOR |
| | PLAN WILL NOT ALLOW THE DOOR TO OPEN 180 |
| | DEGREES. |
| | |
| | 3) INDICATE THE CLEAR FLOOR SPACE AT |
| | LAVATORY AND WATER CLOSET. FBC 11-4.19.3 |
| | AND 11-4.16.2 |
| | |
| | 4) INDICATE THE UNOBSTRUCTED TURNING |
| | SPACE REQUIRED BY FBC 11-4.22.3. |
| | |
| | 5) PROVIDE BATHROOM ELEVATIONS ON THE |
| | PLANS. SHOW THE REQUIRED LOCATIONS |
| | CLEARANCES AND HEIGHTS OF ALL ACCESSIBLE |
| | FIXTURES. FBC CHAPTER 11. |
| | |
| | 7) THE DISTANCE FROM THE WALL TO THE |
| | CENTER OF THE WATER CLOSET IS 18". SEE |
| | FBC CHAP.11 FIGURE 28. |
| | |
| | 8) SIDE GRAB BAR IS REQUIRED TO BE 12" |
| | OFF THE REAR WALL. SEE FIGURE 29. |
| | |
| | 9) MIRRORS MUST COMPLY WITH FBC |
| | 11-4.19.6. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |
| | |
| | |
| | |