2005-08-12 00:00:00DENIED
  
 1) FBC 707.1 CONCEALED SPACES IN TYPES
 I, II AND IV CONSTRUCTION.COMBUSTIBLES
 SHALL NOT BE PERMITTED IN CONCEALED
 SPACES OF TYPES I, II OR IV
 CONSTRUCTION. BACKING IN WALLS CAN NOT
 BE COMBUSTIBLE MATERIALS.
  
 2) FBC 1012.1.4 DURING ITS SWING, ANY
 DOOR IN A MEANS OF EGRESS SHALL LEAVE
 UNOBSTRUCTED AT LEAST ONE HALF OF THE
 REQUIRED WIDTH OF AN AISLE, CORRIDOR,
 PASSAGEWAY, OR LANDING, NOR PROJECT MORE
 THAN 7 IN.(17.8 CM)INTO THE REQUIRED
 WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY
 OR LANDING, WHEN FULLY OPEN.DOORS
 SHALL NOT OPEN IMMEDIATELY ONTO A STAIR
 WITHOUT A LANDING.THE LANDING SHALL
 HAVE A WIDTH AT LEAST EQUAL TO THE WIDTH
 OF THE DOOR SEE ?1021.3 FOR DOOR SWING
 IN GROUP E OCCUPANCIES. THE OFF SET
 SHOWN AT THE BATHROOM DOOR ON THE FLOOR
 PLAN WILL NOT ALLOW THE DOOR TO OPEN 180
 DEGREES.
  
 3) INDICATE THE CLEAR FLOOR SPACE AT
 LAVATORY AND WATER CLOSET. FBC 11-4.19.3
 AND 11-4.16.2
  
 4) INDICATE THE UNOBSTRUCTED TURNING
 SPACE REQUIRED BY FBC 11-4.22.3.
  
 5) PROVIDE BATHROOM ELEVATIONS ON THE
 PLANS. SHOW THE REQUIRED LOCATIONS
 CLEARANCES AND HEIGHTS OF ALL ACCESSIBLE
 FIXTURES. FBC CHAPTER 11.
  
 7) THE DISTANCE FROM THE WALL TO THE
 CENTER OF THE WATER CLOSET IS 18". SEE
 FBC CHAP.11 FIGURE 28.
  
 8) SIDE GRAB BAR IS REQUIRED TO BE 12"
 OFF THE REAR WALL. SEE FIGURE 29.
  
 9) MIRRORS MUST COMPLY WITH FBC
 11-4.19.6.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  