| Plan Review Notes For Permit 05080400 |
| Permit Number |
05080400 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-17 00:00:00 | DENIED: | | | 1.PLAN SHEET A4.0 & A8.0 DO NOT | | | CORRELLATE.WALL & PARTITION DETAIL 1 | | | INDICATES TYPE A EXISTING (DOES NOT | | | INDICATE A RATING).DETAIL 2 TYPE 'B' | | | INDICATES NON-RATED ON THE PICTORIAL & | | | UNDER THE WALL TYPE THE PLANS STATE 'A': | | | 1 HR RATED TENANT SEP WALL UL DESIGN | | | U465.PLEASE CLARIFY. | | | | | | 2.PLEASE NOTE FIRE DAMPERS REQUIRED | | | FOR PENETRATIONS THROUGH A RATED | | | PARTITION/WALL OR SHALL COMPLY WITH THE | | | EXCEPTIONS ALLOWED IN 2001 | | | FBC(M)607.1.3. | | | | | | 3.PER 2001 FBC(M)607.6, FIRE DAMPERS | | | ARE TO BE IDENTIFIED ON THE PLANS. | | | PLEASE PROVIDE INSTALLATION DETAILS. | | | | | | 4.NO COMBUSTIBLES ALLOWED ABOVE THE | | | CEILING IN THE RETURN AIR PLENUM PER | | | 2001 FBC(M)602.2.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|